RATH 2500-LUPSM Relay Control Card Installation Guide
- June 5, 2024
- RATH
Table of Contents
RATH 2500-LUPSM Relay Control Card Installation Guide
-
On the back of RP7701500, locate the “Expansion Port” and unscrew the two screws holding the cover in place.
-
Insert the Relay Control Card from the 2500-LUPSM into the Expansion Port and screw into place.
-
Plug the serial side of the supplied DB9 cable into the Relay Control Card.
-
Use pigtail wires to connect the 2500-LUPSM to monitoring device or fire panel. Each pair monitors a different fault. See Chart 1 for function.
Note: All pairs will be Normally Open and Close when in a fault.
Chart 1:
Pin Assignment | Function | I/O |
---|---|---|
Pin 1 | UPS Fault | O/P |
Pin 2 | Summary Alarm | O/P |
Pin 5 | Common (For Relays) | O/P |
Pin 7 | Battery Low | O/P |
Pin 9 | Utility Line Fail | O/P |
APPENDIX A: Relay Control Card RELAYIO500
Function Description:
Status | Condition |
---|---|
Blue Pair Pin 1 to Pin 5 | **UPS Fault (Inverter Fault / DC Bus Fault / |
Over Temperature / Output Short / Battery Over Charge / Battery Test Fail 1 /
Fan Error 1)
Orange Pair Pin 2 to Pin 5| Summary Alarm (Inverter Fault / DC Bus
Fault / Output Short / Over Temperature / Over Load / Battery Missing /
Battery Over Charge / Battery Low / Wiring Fault / Runtime Low 2 / Battery
Test Fail 1 / Load Over Setting Level 1 / Fan Error 1)
Green Pair Pin 7 to Pin 5| Battery Low
Brown Pair Pin 9 to Pin 5| Utility Line Fail (AC Power Loss / Ground
Fault / External AC Failure**
Warranty
2 YEAR WARRANTY
N56W24720 N. Corporate Circle • Sussex, WI 53089
800-451-1460 •
www.rathcommunications.com