S311AK Analogue Panel Indicator with 4-Digit Display
Installation Guide
MI00173-6-EN
MODULE LAYOUT
Weight:
100 g;
Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
DRILLING TEMPLATE
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol **indicates conditions or
actions that put the user’s safety at risk.
The word CAUTION preceded by the symbol **indicates conditions or
actions that might damage the instrument or the connected equipment. The
warranty shall become null and void in the event of improper use or tampering
with the module or devices supplied by the manufacturer as necessary for its
correct operation, and if the instructions contained in this manual are not
followed.
**| WARNING : The full content of this manual must be read before any
operation. The module must only be used by qualified electricians. Specific
documentation is available using the QR-CODE shown on page 1.
---|---
| The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate
measures during any operation.
**| Electrical and electronic waste disposal (applicable in the European
Union and other countries with recycling).
The symbol on the product or its packaging shows the product must be
surrendered to a collection center authorized to recycle electrical and
electronic waste.
TECHNICAL SPECIFICATIONS
STANDARDS| EN61000-6-4 Electromagnetic emissions, industrial environment.
EN61000-6-2 Electromagnetic immunity, industrial environment.
EN60950 Safety
---|---
INSULATION|
POWER SUPPLY| Voltage: 10 = 40 Vac, 19 ÷ 28 Vdc; max. absorption 0.9 W
ENVIRONMENTAL
CONDITIONS| Temperature: -10°C ÷ +65°C
Humidity: 30% ÷ 90% non condensing.
Storage temperature: -30°C = + 85°C
Altitude: up to 2000 m above sea level
ERRORS| REFERRING TO THE MEASUREMENT RANGE FOR INPUT VOLTAGES AND CURRENTS
SOLUTION| 16 bit 40000 points max
ACCURACY| 0.05%
THERMAL
COEFFICIENT| 0’005 %°K
LINEARITY
ERROR| 0.05%
SENSOR
POWER SUPPLY| 16V (Max 25mA)
CONNECTIONS| 2-way removable screw terminals, 5.08 mm pitch (Supply) 3-way
removable screw terminals, 5.08 mm pitch (Inputs)
INSTALLATION REGULATIONS
The module is designed to be panel-mounted. For optimal operation and
duration, ensure adequate ventilation.
Avoid mounting modules over heat-generating equipment.
MENU PARAMETER MODIFICATION
The modification is done digit by digit. The digit to be modified flashes: in
the figure, this digit is larger than the others.
The example diagram below refers to 4-digit indicators.
| Increases the value of the figure by one unit.
---|---
| Decreases the value of the digit by one unit.
| Confirms the value of the digit and moves to the next one. If the last
digit: confirms the value of the digit and subsequent pressing returns to the
parameter just set.
N.B.: Negative values:
The last digit allows entering even the “-” or the value “-1”.
CAUTION
THE VALUES OF THE PARAMETERS ENTERED OUTSIDE THE RANGE ARE AUTOMATICALLY RESET
WITHIN THE RANGE AND THEN DISPLAYED.
Example:
If parameter is set with a value of 40.0 this will be automatically set to
the maximum value which is 20.00.
The same applies to negative values.
PARAMETER CONFIGURATION EXAMPLE
You want to set the instrument to display a 0 ÷ 10 V voltage input with an
activated filter:
Access the menu by pressing DOWN + MENU / OK for 3 seconds until the menu
appears;
Press the OK/MENU button and access the sub-menu and set:
Press the OK/MENU button and
access the sub-menu and set:
ELECTRICAL CONNECTIONS
POWER SUPPLY | CURRENT INPUT | VOLTAGE INPUT |
---|---|---|
With an external power supply from the sensor |
With an external power supply from the sensor
|
With the power supply supplied by the instrument| With the power supply
supplied by the instrument
ERROR TYPE
| A)The value to be displayed is 3% higher than the parameter set.
B)The value to be displayed is higher than
---|---
| A)The value to be displayed is 3% higher than the parameter set.
B)The value to be displayed is higher than
| Quick transition from to : overcurrent protection activated (input > 25mA).
MENU PARAMETER
PARAMETER | FUNCTION | Default value | |
---|---|---|---|
Password |
enabling for
menu access| By setting a value other than 5477, the password will be
requested
to access the menu (always 5477)| 5477:
Password
disabled.
PARAMETER| FUNCTION| **| Default value
| Input type| 1= Current
0= Voltage|
| Electrical Scale
Start| Start of scale in volts (voltage input) or in mA (current input).
It also defines the value of the input quantity associated with the
the minimum value is shown on the display (LO-d). Minimum settable
value 0 (current input), -10.00 (voltage input), maximum value
20.00 (current input), 10.00 (voltage input).|
(mA)
| Electrical full
scale| Full scale in volts (voltage input) or in mA (current input).
It also defines the value of the input quantity associated with the
maximum value shown on the display (HI-d). Minimum settable
value 0 (current input), -10.00 (voltage input), maximum value
20.00 (current input), 10.00 (voltage input).|
(mA)
PARAMETER| FUNCTION| **| Default value
| Display full scale| Integer values between a minimum of -1999 and a maximum
of
9999|
| Start of the
display scale| Integer values between a minimum of -1999 and a maximum of
9999|
| Position of
decimal point| 0= No decimal point
1= Decimal point on the 1 st digit 000.0
2= Decimal point on the 2 nd digit 00.00 etc.| No decimal point
| Filter level| 0= No filter
1….5 = Filter activated with level 1 … 5|
PARAMETER| FUNCTION| **| Default value
| Default settings| 1 = Overwrites the set parameters with the default values
and exits
the menu|
| Contrast| 0…3= Adjusts the display contrast.|
PARAMETER| FUNCTION| **| Default value
| Menu exit| By confirming with OK \ MENU, all the set parameters are saved
on the flash memory. The module can be used immediately with the new settings
without the need for a reboot.|
CONTACT INFORMATION
Technical support| supporto@seneca.it| Product
information| commerciale@seneca.it
---|---|---|---
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorized.
The content of this document corresponds to the described products and
technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
ACCESS TO THE PROGRAMMING MENU
Press the two buttons simultaneously for a few seconds