Beca BHP-8000 C Room Thermostat

Technical date

Power Supply 24VDC/AC +10%
Current Load 1A (Inductive) 3A (Resistance)
Sensor NTC3950, 10K
Set Temp. Range 42-122 ℉ (5~50℃)
Accuracy ±1 F
Display Temp. Range 41~210 ℉ (5~99℃)
Ambient Temp 32~113 ℉ (0~45℃)
Ambient Humidity 5~95%RH(Non Condensing)
Storage Temp 23~113℉ (-5~45℃)
Timing Error <1%
Power Consumption <1.5W
Shell Material PC+ABS(Fireproof)
Available Installation 1 Wall mounted
Available Iallation 2 Distance of 62±5mm

(Europe, China and Japan)
Available Itallation 3| Hole Distance of 86±3mm
(USA and Italy etc,)
Wire Terminals| Wire 2×1.5mm2  or 1×2.5mm2
Protection Class| IP20
Buttons| Capactive Touch Buttons

More settings

Beca BHP-8000 C Room Thermostat - settings

Service
Your thermostat carries an 24 months warranty from date of purchase. Service outwith the warranty period mayincur a charge. More detail please contact with us directly.

Welcome

Thank you for your purchase.
Your new thermostat will provide uniform and comfortable temperature Control throughout every room in your peoperty.
We bring together technology craftsmanship and the highest quality materials to provide you with a safe, reliable productcombined with sleek, contemporary design. Please read this installation/programming manual for comprehensive instructions on installing  and operating your thermostat.
Please also ensure a suitably qualified person installs your thermostat and complies with all local regulations.

In The Box

Thermostat *1;  Marking tape *1;  Screws *4;
Power Module *1; QC Passed *1; User Guide *1;

CAUTION

  1. Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
    Disconnect power supply before installation.

  2. Check whether the power supply is 24V, if it is 95-220V, Thermostat can’t be used.

Dimension

Unit:mm( inch)

Beca BHP-8000 C Room Thermostat - Dimension

APP operation interface description (Heat pump thermostat)

Beca BHP-8000 C Room Thermostat - interface

Syetem mode:Display the current system mode.tap it to swich the mode.
Fan mode: Display the current fan mode. Tap it to swich the mode.
Hold mode: Display’s the current hold mode,Tap it to swich the mode.
Targe temperture: Turn up/down the target temperature.
Setting:You can edit the setting of device, such as Schedule,Holiday mode,fan run time etc.

Beca BHP-8000 C Room Thermostat - interface 2

After connecting to this hotspot, return to the “smartlife” APP

Beca BHP-8000 C Room Thermostat - interface 3

Main Page

Beca BHP-8000 C Room Thermostat - Main Page

  1. System
    Beca BHP-8000 C Room Thermostat - System

  2. Fan
    Beca BHP-8000 C Room Thermostat - Fan

  3. MenuBeca BHP-8000 C Room Thermostat - Menu

  4. Touch Button

  5. ScreenBeca BHP-8000 C Room Thermostat - ScreenBeca BHP-8000 C Room Thermostat - Screen 2

AP Mode
Press and hold until the icon of the thermostat slowly blinks (if the icon is blinking quickly, press and hold until the wifi icon slowly blinks), then follow the following figure (Fig. 2.11- Fig. 2.16). Beca BHP-8000 C Room
Thermostat - Screen 3 Method 3: Ordinary distribution network guidance (Fig. 2. 1&Fig. 2.5.1)

Network distribution mode:
EZ Mode

Press and hold the “ “until the thermostat screen flashes quickly and displays the “ ” icon, and then operate according to the following figure (Fig 2.6-Fig 2.10).

Beca BHP-8000 C Room Thermostat - Network

Installation

  1. Power off,remove the old thermostat.
    Note: Do not remove the wall plate;
    Beca BHP-8000 C Room Thermostat - Network 2

  2. Take a picture of your old thermostat wires how to connect to the terminal;

  3. Label the wires with Tags;

  4. Please confirm old thermostat if have C wiring(Blue line)
    Yes → Plan A
    No → Plan B

Terminal designation

Terminals

|

What it means

---|---
Rh| 24VAC primary for heating
Re| 24VAC primary for cooling
C| 24VAC Common Wire
W1| Heat Relay (Stage 1)
W2| Heat Relay (Stage 2)
Y1| Compress Relay (Stage 1)
Y2| Compress Relay (Stage 2)
G| Fan Relay
0/B| Heat Pump Changeover Valve
S| Optional wiring module terminal to combine Y and G, while reserve an extra in-wall wire to power on the thermostat

Beca BHP-8000 C Room Thermostat - Terminal

Method 2: Scan the QR code to configure the network guide ( Fig 2.1&Fig 2.5-Fig 2.6)Beca BHP-8000 C Room Thermostat - Terminal
2

This QR code must be scanned in the APP, Quick jump thermostat pairing.

https://smartapp.tuya.com/s/p?p=N8bUqOZ8HBQjU0K0&v=1.0

ABOUT WIFI CONNECTION
Before using your Wi-Fi thermostat for the first time, you must configure the Wi-Fi signal and settings through your smartphone or tablet ,This will allow communication between your connected devices.
Step 1 Downlosd your APP(Fig1-1)

Beca BHP-8000 C Room Thermostat - qr code 2http://app.yimusmart.com/smartlife

Search for “Smartlife” in Apple Store or Google Play or use a browser to scan the QR code above (Figure 1-2), and complete account r egistration and installation according to the guidance of the APP.
Step 2. Connect the thermostat
Check the tutorial below to complete the connection and set up Method 1:Connect the mobile phone to WiFi and turn on Bluetooth. Add according to figure (Fig 2.1-Fig2.4)Beca BHP-8000 C Room Thermostat -
Bluetooth

Plan A:

  1. Remove the wall plate
    Unscrew the wallplate from the wall and gently pull it to ensure the wires do not fall back into the hole

  2. Connect the mounting plate
    Wire the cables through the holes in the temperature controller mounting plate.

  3. Connect the wires to the base
    Note: Connect the R or RC wire into the RC terminal, Connect other wires to the corresponding terminals.

  4. DIP Switch
    If you have connected both the RC-wire and the RH-wire to the wall plate, adjust the DIP on the back of the thermostat to Disconnect , otherwise switch it to Connect

09 Whether to turn on the outdoor compressor at the lowest temperature| • 0: no 1: Yes , default 0
---|---
10 Compressor outdoor minimum outdoor temperature| • °C: 0-20,°F: 32-68 default °C: 2,°F: 32
11 Turn on the maximum temperature of the
auxiliary heat| • O:no 1:Yes , default 0
12 Auxiliary heat on outdoor maximum temperature| • °C : 0-18,°F : 32-64 default °C:18,°F: 64
13 Whether the heat pump compressor and auxiliary heat are turned on at the same time| • O:no 1:Yes , default 1
14 Interval temperature| • °C : 1.5-5 ,°F : 3-9 default °C: 1.5 ,°F: 3
15 Cool& Heat set| • 0 to 3 , default 3
16 °F&°C display| • 0: °F 1: °C , default 1
17 Reset to facture set| • O:no 1:Yes , default 0
18 Filter replacement countdown reminder| • 0 to 180 , default 180 days
19 Enable dual energy| • 0:no 1:Yes , default 0
20 Production line test| •0 : Normal Code ,1: test Code default 0
21 Verison number| •Ul

Such as:

Schedu Time Heat Cool
Wake 6:00AM 72℉(22℃) 72℉(22℃
Away 8:00AM 72℉(22℃) 72℉(22℃)
Home 17:30PM 72℉(22℃) 72℉(22℃)
Sleep 21.30PM 72℉(22℃) 72℉(22℃)

Advance Options:
Press & for 3 seconds at the same time, Press to change the different items, you can press/arrows to change settings.

01 Temperature Calibration -9 to 9 , default -4
02 Standby brightness 3 to 99 , default 20
03 Min temp set ℃:5-15 ,℉:9-27

default ℃:5,℉:9
04 Max temp set| ℃:15-35 ,℉:27-63
default ℃: 35,℉:63
05 1 stage compressor delay time| 1-5, default 1
06 2 stage compressor delay time| 1-5, default 1
07 Fan off delay time| 1-5, default 1
08 Cycle time for fan cycle mode| 1-11(5-55), default 2 (10)min

Attach the thermostat on base

Beca BHP-8000 C Room Thermostat - thermostat

Power on your system
Once powered up, the thermostat screen will light up and display the setup wizard to complete configuration.Beca BHP-8000 C Room Thermostat - system
2

Plan B:
What is Power Module?
Power module requires your system to have the following wires:

Beca BHP-8000 C Room Thermostat - wires

The C-wire is used to provide power to the thermostat.
If your system does not have the “C” wire, can use the power module to power your thermostat using the existing wires.
There are 2 sides with connections, 4 terminals is for thermostat, 5 terminals is for the control board connections.

Operation

  1. Selectiong System Mode
    Press to select the mode of: Cool(Cooling only);Heat( heat only) ; Auto( Automatic control of heating and cooling based on ambient temperature); EM heat( emergency heating); Off( Off system)

  2. Selectiong Fan Mode
    Press to select the fan mode of: On( Runs continuously); Auto ( Automatically adjust the running time of the fan according to the system);Circ( Runs at intervals to circulate indoor air)

  3. Selectiong Menu
    Press to select the operating mode of: Permanent Hold ( Manual mode) ; Temporary Hold ( emergency heating); Using Schedule(programming mode)

  4. Set time
    Press , the min of time will flash,touch incon / to set your time
    Press , the hour of time will flash, touch the icon / set your hour
    Press , the week of time will flash,
    Wait for 4-5 seconds, the settings will be saved automatically.

  5. Child lock
    Press & 3sec to set locked or unlocked

  6. Programa mode
    Press Four times, Hour will flase, you will see the wake on the screen,means you start setting schedule for programming mode.
    Press / to set time and temperture.
    You can set Wake,Away,Home,Sleep 4 time period temperature.

Boiler or radiant system with air handler and conventional cooling or heat pump

Beca BHP-8000 C Room Thermostat - pump

| For dual heat and cooling system,if applicable For heat pump only.
---|---

Remove the jumper between Rh, Rc, or R terminals, adjust the DIP switch on the back of the thermostat to ‘Disconnect’ if you have connected both RC-wire and RH-wire to the wallplate, otherwise switch it to the ‘Connect’ side.

Install the Power Module

  1. Find the HVAC terminals
    Find and open the HVAC system’s cover.take a picture of the wires connected to the terminals of your old thermostat, you may need to reference this photo later.
    Beca BHP-8000 C Room Thermostat - Install

  2. Label the wires
    Only label the wires from the control board to the old thermostat
    Beca BHP-8000 C Room Thermostat - Label

  3. Disconnect the wires
    Disconnect wires of W/W1, Y/Y1, R to thermostat from control board.

  4. Connect the wiring module
    Reconnect these wires to the 4-terminal side of the power module.
    The wires and corresponding terminals are show below.

Heat pump (air or geothermal) with auxiliary heat

Beca BHP-8000 C Room Thermostat - Heat pump

Remove the jumper between Rh, Rc, or R terminals, adjust the DIP switch on the back of the thermostat to ‘Disconnect’ if you have connected both RC-wire and RH-wire to the wallplate, otherwise switch it to the ‘Connect’ side.

Wiring diagrams

Below are the wiring diagrams for common HVAC equipment.
Conventional heating and cooling systemBeca BHP-8000 C Room Thermostat -
diagrams

Remove the jumper between Rh, Rc, or R terminals, adjust the DIP switch on the back of the thermostat to ‘Disconnect’ if you have connected both RC-wire and RH-wire to the wallplate, otherwise switch it to the ‘Connect’ side

Connect the wires
5-terminal connect to HVAC control board side.

Position the wiring module
The power module should be installed between your thermostat wiring and your control board. Install it at the right position then close the HVAC coverpanel securely and return to your thermostat.Beca BHP-8000 C Room Thermostat -
wiring module

Add new tags
Add new tas to the follwing tags to simplify your wiring: R/RC/RH→RC; G→C;Y/YI→S
Beca BHP-8000 C Room Thermostat - tags Connect the wires to the wallplate
First connect 3 wires as shown below
RC,C,S

DIP Switch
Adjust the DIP switch on the back of the thermostat to the Connect.

Attach the thermostat on base
Power on your system
Once powered up, the thermostat screen will light up and display the setup wizard to complete configuration.Beca BHP-8000 C Room Thermostat -
base

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals