GOODWE SBP Series AC-Coupled Battery Storage Retrofit User Manual
- June 6, 2024
- GOODWE
Table of Contents
SBP SERIES USER MANUAL
AC-COUPLED BATTERY STORAGE RETROFIT
Ver. 1.5
JIANGSU GOODWE POWER SUPPLY TECHNOLOGY CO., LTD
No. 90 Zijin Rd., New District, Suzhou, 215011, China
www.goodwe.com
service@goodwe.com
INTRODUCTION
GoodWe S-BP series bi-directional inverter is designed for both indoor and outdoor use, which could be used with or without existing grid-tied inverter systems to store energy using batteries. The energy produced from grid-tied inverters shall be used to optimize self-consumption, excess energy will be used to charge the batteries, if the battery is already full, power excess power could be exported to the grid. Loads will be supported in priority by the grid-tied system, then battery power, if there is insufficient energy, power will be supported by the grid.
Note:
The introduction describes the general behavior of the S-BP system. The
operation mode can be adjusted on PV Master App depending on the system
layout. Below are the general operation modes for BT system:
Operation Modes Introduction
S-BP system normally has the following operation modes based on your configuration and layout conditions.
Mode Ⅰ
Energy from grid-tied inverters optimize loads, excess energy will be used to
charge the battery, if it is full, the excess power
Mode Ⅱ
When energy from grid-tied inverters is weak, the battery will discharge to
support the load in priority together with the grid.
Mode Ⅳ
The battery could be charged by the grid, and charge time/power could be set
flexibly on PV Master APP.
Safety & Warning
The S-BP series inverter of Jiangsu GoodWe Power Supply Technology Co., Ltd.
(hereinafter called as GoodWe) strictly complies with related safety rules for
product design and testing. Please read and follow all the instructions and
cautions on the inverter or user manual during installation, operation, or
maintenance, as any improper operation might cause personal or property
damage.
Symbols explanation
| Caution!
Failure to observe a warning indicated in this manual may result in injury
---|---
| Danger of high voltage and electric shock!
**| Danger of hot surface!
**| Components of the product can be
recycled.
| This side up! The package must always be transported, handled, and stored
in
such a way as the arrows always point upwards.
| No more than six (6) identical packages are stacked on each other.
| Products should not be disposed of as household waste.
| Fragile – The package/product should be handled carefully and never be
tipped over or slung.
| Refer to the operating instructions.
| Keep dry! The package/product must be protected from excessive humidity and
must be stored undercover.
| Signals danger due to electric shock and indicates the time to wait (5
minutes)
before it is safe to touch the internal parts of the inverter after it has
been
disconnected from it power source
| CE Mark
Safety warning Any installation and operation on inverter must be performed by
qualified electricians, in compliance with standards, wiring rules or
requirements of local grid authorities or companies (like AS 4777 and AS/NZS
3000 in Australia). Prohibit inserting and pulling the AC and DC terminals
when the inverter is running.
Before any wiring connection or electrical operation on the inverter, all DC
and AC power must be disconnected from the inverter for at least 5 minutes to
make sure the inverter is totally isolated to avoid electric shock.
The temperature of the inverter surface might exceed 60℃ during operation, so
please make sure it has cooled down before touching it, and make sure the
inverter is out of reach of children.
Do not open the inverter’s cover or change any components without the
manufacturer’s authorization, otherwise, the warranty commitment for the
inverter will be invalid. Usage and operation of the inverter must follow
instructions in this user manual, otherwise, the protection design might be
impaired and warranty commitment for the inverter will be invalid.
Appropriate methods must be adopted to protect inverters from static damage.
Any damage caused by static is not warranted by the manufacturer.
The inverter, with built-in RCMU, will exclude the possibility of DC residual
current to 6mA, thus in the system, an external RCD (type A) can be
used(≥30mA).
In Australia, the inverter internal switching does not maintain neutral
integrity, which must be addressed by external connection arrangements like in
the Off-Grid System Connection Diagram in page 17.
In Australia, the output of backup side in switch box should be labeled “Main
Switch UPS Supply”, the output of the normal load side in the switch box
should be labeled “Main Switch Inverter Supply”.
Product Overview
INSTALLATION INSTRUCTIONS
Unacceptable Installations
Please avoid the following installations,which will damage the system or the Inverter.
Packing List
On receiving the S-BP series inverter, please check to make sure all the components as below are not missing or broken.
Mounting
2.3.1 Select Mounting Location
For inverter’s protection and convenient maintenance, mounting location for
inverter should be selected carefully based on the following rules:
Any part of this system shouldn’t block the switch and breaker from
disconnecting the inverter from DC and AC power.
Rule 1. The inverter should be installed on a solid surface, where is suitable
for the inverter’s dimensions and weight.
Rule 2. Inverter installation should stand vertically or lie on a slop by a
max of 15°.
Rule 3. The ambient temperature should be lower than 45°C.
(High ambient temperature will cause power derating of the inverter.)
Rule 4. The inverter installation should be protected under shelter from
direct sunlight or bad weather like snow, rain, lightning, etc.
Rule 5. The inverter should be installed at eye level for convenient
maintenance.
Rule 6. The product label on the inverter should be clearly visible after
installation.
Rule 7. Leave enough space around the inverter according to the below
figure.
**** The inverter cannot be installed near flammable, explosive or strong electromagnetic equipment.[1]
2.3.2 Mounting
**** Deliver the inverter carefully.
- Pack the inverter securely for transport.
- Carefully transport the inverter using the carrying handles in the boxes.
- Do not subject the inverter to shocks during the transport.
- Make sure that the arrows on the box always point upwards during the transport.
- Secure the inverter firmly in place for transport.
The inverter cannot be installed near flammable, explosive or strong
electromagnetic equipment.[1] The inverter is suitable for mounting on
concrete or another non-combustible surface only.
Lift the inverter from the packing case and move it to the specified
installation position.
Note:
- Move the inverter with care to prevent device damage and personal injury.
- Do not use the wiring terminals and ports at the bottom to support any weight of the inverter.
- Place a foam pad or cardboard under the inverter to protect the inverter enclosure from damage
Step 1
- Please use the mounting bracket as a template to drill 6 holes in the right positions (10mm in diameter, and 80mm in depth)
- Use expansion bolts in the accessory box and fix the mounting bracket onto the wall tightly
Note: The bearing capacity of the wall must be higher than 25kg, otherwise it may not be able to keep the inverter from dropping.
Step 2
Carry the inverter by holding the heating sink on both sides and placing the
inverter on the mounting bracket.
Note: Make sure the heat sink on the inverter joints with mounting
bracket.
Step 3
Ground cable shall be connected to the ground plate on-grid side.
Step 4
A lock could be used for anti-theft purposes if it is necessary for individual
requirement
The lock is not included in the package, It can be purchased by the user.
Electrical Wiring Connection
2.4.1 Battery Wiring Connection
- For lithium battery (pack) the capacity should be 50Ah or larger. lead-acid batteries are not allowed for use with GoodWe hybrid inverters without GoodWe’s authority. Battery cable requirements are shown below.
Cable | Description | Value |
---|---|---|
A | Outside Diameter | 10-12mm |
B | Isolation section | NA |
C | Conductor Core | 20-35mm |
- Please be careful against any electric shock or chemical hazard
- Make sure there is an external DC breaker (≥125A) connected for batteries without a build-in DC breaker
Battery wiring connection steps as below:
**** Make sure the battery switch is off and battery nominal voltage meets
S-BP specification before connecting the battery to the inverter and make sure
the inverter is totally isolated from PV and AC power.[4]
Step 1
Prepare battery cables and accessories and put battery power cable through
battery cover.
Note:
- Please use accessories from the GoodWe box
- The battery power cable should be 25-35mm
Step 2
Make battery terminals:
- Strip cable coat, revealing 10mm length of metalcore
- Use special crimper to compress battery terminal tightly
Step 3
Connect battery terminal onto inverter.
Note: Please make sure polarity (+/-) of battery are not reversed
- For the compatible lithium batteries (LG / PYLON / BYD / GCL / DYNESS / ALPHA) connection, please refer to battery connection part in S-BP QUICK INSTALLATION INSTRUCTIONS.
Battery Protection Description
The battery will act as protective charge/discharge current limitation under
any condition as below:
- Battery SOC is lower than I-DOD
- Battery voltage lower than discharge voltage
- Battery over-temperature protection
- Battery communication abnormal for lithium battery
- BMS limitation for lithium battery
When charge/discharge current limitation protection happens:
- Under on-grid mode, battery charge/discharge operation could be abnormal
- Under off-grid mode, Back-Up supply will shut down
Note:
- Under on-grid mode, the battery is protected from over-discharge by DOD and discharge voltage, under the off-grid mode, it is protected by only discharge voltage in priority.
- The DOD setting of a battery prevents the inverter from discharging battery reserve power. As soon as the DOD is reached a load of the building will only be supported by either PV power or from the grid. If there are continuous days when little or no battery charging occurs, the battery may continue to self-consume energy to support communications with the inverter. This behavior is different between battery manufacturers’ products, however, if the SOC of the battery reaches a certain level the inverter will boost the SOC back up. This protection mechanism safeguards the battery to fall to
2.4.2 On-Grid & Back-Up Connection
An external AC breaker is needed for the On-Grid connection to be isolated
from grid when necessary. Below are the requirements of the On-Grid AC
breaker.
- Use a separate AC break for individual inverter
- On AC side, the individual break should be connected before loads (between inverter and loads)
- The on-grid wiring connection process is as below:
**** Make sure the inverter is totally isolated from any DC or AC power before connecting AC cable.[5]
Step 1
Prepare the terminals and AC cables according to the right table.
Grade | Description | Value |
---|---|---|
A | Outside diameter | 11-12 mm |
B | Isolation section | NA |
C | Conductor wire length | 7-9 mm |
D | Conductor core section | 4-6 mm2 |
Note:
- Neutral cable shall be blue, line cable is black or brown (preferred) and protective earth cable yellow-green.
- For AC cables, PE cable shall be longer than N&L cables, so that if in any case the AC cable slips
Step 2
Put AC cable through the terminal cover in the following sequence.
Note: Please use the terminals in GoodWe components box
Step 3
Press the six connectors on cable conductor core tightly.
Note: Make sure cable jacket is not locked within the connector.
Step 4
-
Connect the assembled AC terminals onto the inverter.
Note: Make sure it is not connected to the wrong side. -
Lock the cover and screw the cap on.
Declaration for backup function
The below statement lays out the manufacturer’s general policies governing the
energy storage inverters of the series ES, EM, SBP, ET, EH and BH.
- For Hybrid inverters (Series ES, EM, EH and ET), the standard PV installation typically consists of the connection of the inverter with both panels and batteries. In the case where the systems are not connected to the batteries, the backup function is strongly not advised for use. GoodWe shall not cover the standard warranty and be liable for any consequences arising from users not following this instruction.
- Under normal circumstances, the backup switching time is less than 10 ms (the minimal condition to be considered as the UPS level). However, some external factors may cause the system to fail on Back-Up mode. As such, we recommend the users to be aware of conditions and follow the instructions as below:
- Do not connect loads if they are dependent on a stable energy supply for a reliable operation.
- Do not connect the loads which may in total exceed the maximum backup capacity.
- Try to avoid those loads which may create very high start-up current surges such as Inverter Air-conditioner, high-power pump, etc.
- Due to the condition of the battery itself, battery current might be limited by some factors including but not limited to the temperature, weather, etc.
Declaration for backup loads
GoodWe S-BP inverter is able to supply a continuous 5000VA output(max 5500VA
within 10s) on the Back-Up side. And the inverter will shut down when it is
full loading with high ambient temperature if the grid is absent.
- Accepted Back-Up loads: television, computer, fridge, fan, illumination lamps, microwave oven, electrical rice cooker, and router etc.
- Unacceptable house loads for Back-Up side: air conditioner, water pump, heaters, washing machine, electromagnetic oven, compression engine, hair drier and dust cleaner etc. with high power and other loads with high inrush current at start-up.
Special adjustable settings
The inverter has field adjustable settings like tripping point, tripping
time, reconnect time, active and invalid QU/PU curves, etc. They can be
adjusted using special firmware, please contact after-sales for the special
firmware and adjustment methods.
For convenient maintenance, an SP3T switch could be installed on the Back-Up
and On-Grid sides. Then it is adjustable to support load by Back-Up or by grid
or left alone.
- Load is supplied from Back-Up side
- Load is isolated
- Load is supplied from grid side
Declaration for Back-Up overload protection
The inverter will restart itself if overload protection occurs. The
preparation time for restarting will extend (max one hour) if overload
protection repeats. Take the following steps to restart the inverter
immediately:
- Decrease Back-Up load power within max limitation.
- On PV Master APP → Advanced Setting → Click “Reset Back-Up Overload History”
2.4.3 Smart Meter & CT Connection
The single-phase Smart Meter with 2 CTs or 3-phase in product box is
compulsory for S-BP system installation, used to detect grid voltage, current
direction and magnitude, further to instruct the operation condition of S-BP
inverter via RS485 communication.
**** Make sure S-BP and grid-tied inverters are totally isolated from AC and
DC power before connecting Smart Meter and CT Single-phase Smart Meter & CT
connection diagram
Note:
- The Smart Meter and CT are well configured, please do not change any setting of the Smart Meter.
- CT must be connected to the same phase with a Smart Meter power cable.
- Do not connect CT2 to the power line when the CT2 is not in use.
Three-phase Smart Meter & CT connection diagram
Note:
- Please use the Smart Meter with 3 CTs in the GoodWe product box.
- CT cable is 3m as default could be extended to a max of 5m.
- Smart Meter communication cable (RJ45) is attached on the inverter (“Too Smart Meter” cable), could be extended to a max of 100m, standard RJ45 cable and plug must be used, as Detailed pin function of each port on S-BP
BMS: CAN communication is configured by default. If 485 communication is used, please contact GOODWE to replace it with the corresponding communication line.
Position | Color | BMS Function | Smart Meter Function | EMS |
---|---|---|---|---|
1 | Orange&white | 485_A2 | NC | 485_A |
2 | Orange | NC | NC | 485_B |
3 | Green&white | 485_B2 | 485_B1 | 485_A |
4 | Blue | CAN_H | NC | NC |
5 | Blue&white | CAN_L | NC | NC |
6 | Green | NC | 485_A1 | 485_B |
7 | Brown&white | NC | 485_B1 | NC |
8 | Brown | NC | 485_A1 | NC |
Smart Meter LED Indications
| OFF| ON| Blinking
---|---|---|---
POWER| Not working| Working| /
ENERGY| /| Importing| Exporting
COM| Blinks once when transferring data to the inverter
Anti-reverse function connection
If S-BP system (connected with grid-tied inverters) requires an anti-reverse
function, it is operable but please note:
- This diagram is only for installation where there is exporting power limit function requirement.
- For the anti-reverse function, it can be set on PV Master App → Advanced Setting → Power Limit.
- This diagram will only apply if the grid-tied inverter has an anti-reverse function build-in. And the power limit value can be set on a grid-tied inverter.
- When using the anti-reverse function, it would buy about 100W from the grid.
DRED & Earth Fault Alarm
2.5.1 DRED Connection
DRED is used for Australia and New Zealand installation (also used as remote
shutdown function in European countries), in compliance with Australia and New
Zealand safety requirements( or European countries). And DRED device is not
provided by GoodWe.
Detailed connection of the DRED device is shown below:
Step 1
Screw this plate off from the inverter.
Note: DRED / Remote Shutdown device should be connected through “DRED port” as
the figure shows.
- Plug out the 6-pin terminal and dismantle the resistor on it.
- Plug the resistor out, leave the 6-pin terminal for the next step.
Note: The 6-pin terminal in the inverter serves the same function as DRED / Remote shutdown device. Please leave it in the inverter if no external devices are
Step 3-1 For DRED
- Put the cable through the plate.
- Connect the cable on the 6-pin terminal.
The function of each connection position as below:
NO | 1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|---|
Function | DRM1/5 | DRM2/6 | DRM3/7 | DRM4/8 | REGEN | COM / DRMO |
Step 3-2 For Remote Shutdown
- Put the cable through the plate.
- Connect cable on the 6-pin terminal.(Wiring from the No. 5 and 6 holes respectively.)
The function of each connection position as below:
NO | 5 | 6 |
---|---|---|
Function | REGEN | COM / DRMO |
Step 4
Connect the terminal to the right position onto the inverter.
Earth Fault Alarm Connection
S-BP series inverter complies with IEC 62109-2 13.9. Fault indicator LED on
the inverter cover will light up and the system will email the fault
information to the customer.
Wiring System For S-BP Series hybrid inverter
For 3-phase Smart Meter wiring connection, please refer to the “3-phase Smart
Meter & CT Connection Diagram”
Please select Breaker according to the specifications below
| ①| ②| ③ ④
---|---|---|---
GW3600S-BP| 125A/60V| 40A/230V AC breaker| Depends on household loads
GW5000S-BP| DC breaker| 50A/230V AC breaker|
- For batteries with attached switch, the external DC switch is not necessary.
- Only for lithium battery which has BMS communication.
- The direction of the CT cannot be connected in reverse, please follow the “House → Grid” direction to do the connection.
- AC Breaker ≥40A for GW3600S-BP, and ≥50A for GW 5000S-BP.
SYSTEM CONNECTION DIAGRAMS
Note: For Australian safety country, the neutral cable of the on-grid side and
backup side must be connected together, the otherwise backup function will not
work.
This diagram is an example for Australia,South Africa and New Zealand’s grid
system.
This diagram is an example for a grid system without special requirements on
electrical wiring connections.
Note: The Back-Up PE line and rack earth must be grounded properly and
effectively.
Otherwise, the Back-Up function may be abnormal when the grid fails.
Note: After the inverter is installed and in order to avoid problems connected, please turn off the grid power to check whether the Back-Up function is normal, in order to avoid problems in subsequent uses.
MANUAL OPERATION
Wi-Fi Configuration
This part shows configuration on the web page.
Wi-Fi configuration is absolutely necessary for online monitoring and
maintenance.
Preparation:
- The inverter must be powered up with a battery or grid power.
- Router with available internet access to the website www.semsportal.com is required.
Step 1
- Connect Solar-WiFi to your PC or smartphone ( its name the last 8 characters of the inverter’s serial No.).
- Open browser and login 10.10.100.253 Admin (User): admin; Password: admin.
- Then click “OK”.
Step 2
- Click “Start Setup” to choose your router.
- Then click “Next”.
Step 3
- Fill in the password of ther router, then click “Next”.
- Click “Complete”.
Note:
- Please make sure the password, Encryption method/algorithm is the same as the routers.
- If everything is correct, the Wi-Fi LED on the inverter will change from double blink to quartic blink then to solid status, which means Wi-Fi has connected to the server successfully.
- Wi-Fi configuration could also be done on PV Master App, details please check on PV Master App.
Wi-Fi reset & reload
Wi-Fi reset means restarting the Wi-Fi module. Wi-Fi settings will be
reprocessed and saved automatically. Wi-Fi Reload means setting the Wi-Fi
module back to the default factory setting.
Wi-Fi reset
Short press the touch button for about one second, Wi-Fi LED on the inverter
will blink once a second;
Wi-Fi reload
Long press the touch button (3~5 seconds) Wi-Fi LED on the inverter will
quartic blink
Note: Wi-Fi Reset & Reload function is only used when:
- Wi-Fi lost connection to the internet or cannot connect to PV Master APP successfully.
- Cannot find “Solar-WiFi signal” or have other Wi-Fi configuration problems.
- Please do not use this button if Wi-Fi monitoring works well.
PV Master App
PV Master is an external monitoring/ configuration application for hybrid inverters, used on smartphones or tablets for both Android and iOS systems. The main functions are as below:
- Edit system configuration to make the system work as customer needs.
- Monitor and check the performance of the hybrid system.
- Wi-Fi configuration.
Please download “PV Master App” from www.goodwe.com or scan the QR code on the back of this user manual.
CEI Auto-Test Function
PV auto-test function of CEI is integrated in PV Master App for Italy’s safety
country requirements.
For detailed instruction of this function please refer to “PV Master Operation
Instructions”.
Startup/shutdown Procedure
3.4.1 Startup Procedure
Note: Before closing the AC breaker between the inverter and the grid, you
need to use a multimeter to measure whether the AC voltage is within the
allowable range.
step 1 Turn on the breaker between the inverter and the battery.
step 2 Turn on the AC breaker between the inverter and the grid.
step 3 Please wait for about 1 minute, observe the LED indicator of the
inverter, and check the running status of the inverter
3.4.2 shutdown Procedure
Note: After the inverter system is shut down, the machine still has residual
electricity and heat, which may cause electric shock or burns. So after the
inverter system is powered off for 5 minutes, wear protective gloves before
operating the inverter.
step 1 Turn off the AC breaker between the inverter and the grid.
step 2 Turn off the DC breaker between the inverter and the battery.
OTHERS
Error Message
The error messages below will be displayed on PV Master App or report by Email if the error occurs.
ERROR MESSAGE | EXPLANATION | REASON | SOLUTIONS |
---|---|---|---|
Utility Loss | Public grid power is not available |
(Power lost or on-grid connection
fails)| Inverter does not detect the connection of grid| 1. Check (use multi-
meter) if AC side has voltage . Make sure grid power is available.
2. Make sure AC cables are connected tightly and well.
3. If all is well, please try to turn off AC breaker and turn on again after 5
mins.
VAC Failure| Grid voltage is not within
permissible range| Inverter detects that AC voltage is beyond the normal range
required by the safety country| 1. Make sure safety country of the inverter
is set right.
2. Check (use multi-meter) if AC voltage (Between L & N) is within a normal
range (Also on AC breaker side)
a. If AC voltage is high, then make sure AC cable complies with the
requirements on user manual and AC cable is not too
long.
b. If voltage is low, make sure AC cable is connected well and the jacket of
AC cable is not compressed into AC terminal.
3. Make sure the grid voltage of your area is stable and within normal range.
FAC Failure| Grid frequency is not within
permissible range| Inverter detects that Grid frequency is beyond the
normal range required by the safety country| 1. Make sure safety country of
the inverter is set right.
2. If safety country is right, then please check the inverter display if AC
frequency (Fac) is within normal range.
3. If FAC failure only appear a few times and is resolved soon, it should be
caused by occasional grid frequency unstability.
Over Temperature| The temperature inside of the inverter is too high| Inverter
working environment leads to a high-temperature condition| 1. Try to decrease
the surrounding temperature.
2. Make sure the installation complies with the instruction of the inverter
user manual.
3. Try to turn off the inverter for 15 mins, then start up again.
Relay Check Failure| Self-checking of relay fails| Neutral & ground cable are
not connected well on
AC side or just occasional failure| Check using multi-meter if there if there
is high voltage (normally should be lower than 10V) between N&PE cable on AC
side.
If the voltage higher than 10V, it means the netural & ground cable are not
connected well on AC side or restart inverter.
DC Injection High| /| Inverter detects a higher DC component in AC output| Try
to restart inverter, check if it still occurs, if not, means it is just an
occasional situation or contact GoodWe.
EEPROM R/W Failure| /| Caused by a strong external magnetic field etc.| Try to
restart inverter, check if it still occurs, if not, means it is just an
occasional situation or contact GoodWe.
SPI Failure| Internal communication fails| Caused by a strong external
magnetic field etc.| Try to restart inverter, check if it still occurs, if not,
means it is just an occasional situation or contact GoodWe.
DC Bus High| BUS voltage is too high| /| Try to restart the inverter, check if
it still occurs, if not, means it is just an occasional situation or contact
GoodWe.
Back-up Over Load| Backup side is overloaded| Total backup load power is
higher than the back-up
nominal output power| Decrease Back-Up loads to make sure the total load power
is lower than back-up nominal output power
(please refer to page 12).
NOTE: All the errors about battery happen only on Lithium batteries with BMS communication.
Troubleshooting
Checking Before Starting S-BP Up
Battery connection:
Confirm the connection between S-BP and battery : polarity (+/-) are not
reversed, refer to 4.2-1.
On-Grid & Back-Up connection:
Confirm On-Grid connected to power gird and Back-Up to loads: polarity (L/N)
are not reversed, refer to 4.2.2.
Smart Meter & CT Connection:
-
If the connection between Smart Meter and CT (port 1 and 4 on Smart Meter) is OK.
Note: After turning on AC power, the COM led on Smart Meter should be blinking. -
Make sure CT is connected between house loads and grid. And it follows the House Grid direction on CT, refer to 4.2.3.
Note: For three-pahse Smart Meter, please refer to page 13 to check if the connection and communication of Smart Meter is
OK.
Battery Settings, BMS Communication and Safety Country:
After connecting Solar-WiFi ( means the last 8 characters of the inverter
serial No.), check on PV Master APP Param to make sure battery type is right
what you have installed, and Safety Country is right. If not right, please set
it right in “Set”.
- For lead-acid battery: All the settings should comply with the parameter of the battery, and please contact after-sales for advice before use it.
- For lithium batteries, BMS status is “Communication OK”.
Note: If BMS Status says “NG”, then please make sure battery communication cable wiring connection and all settings are all right, refer to battery connection SOP in S-BP QUICK INSTALLATION INSTRUCTIONS.
Possible problems during operation
S-BP does not start up with only battery Solution:
Make sure the voltage of battery is higher than 48V, otherwise battery cannot
start S-BP up. No discharge or output from S-BP to support loads
Possible Reason:
- There is a grid-tied inverter connected in the system, and the output power is higher than power.
- Load is connected between gird and CT, thus the system cannot detect load power, which is supported by grid power.
- Load power is lower than 150W, as the battery will only discharge if load power is higher than 150W.
- Smart Meter communication fails or CT is connected in the wrong direction, which gives S-BP wrong data.
- Battery is not in the condition fort discharging, such as low SOC, battery communication fail for lithium batteries etc.
Solution:
-
Make sure communication between S-BP and SmartMeter is OK;
-
Make sure load power is higher than 150W;
a. Battery will does not discharge continuously unless load power is higher than 150W;
b. If the battery still not discharge when Meter power is higher than 150W, then please check SmartMeter & CT connection and direction; -
Make sure SOC is higher than I-DOD. Or if battery is discharged to below I-DOD, then battery will only discharge again when SOC charged to [20% + (I-DOD)]/ 2 and SOC > 105% – DOD (if battery discharge is required immediately, battery should be restarted);
-
Check on App if it is charge time,, during charge time, the battery will not discharge (battery will charge in priority during a coincident time of charge/ discharge).
Battery does not charge:
Possible reason:
- Smart Meter communication fails or CT is connected in the wrong direction, which gives S-BP wrong data.
- The battery is not in the condition for charging, such as high SOC, battery communication fail for lithium batteries etc.
Solution:
- Make sure BMS communication is OK on PV Master (for lithium batteries);
- Check if CT is connected in the right position and in the right direction as stated in the user manual page 13;
Question & Answers (Q&A)
About Wi-Fi configuration
Q: Why can’t I find the Solar-WiFi signal on a smartphone?
A: Normally Solar-WiFi signal can be found after the inverter is powered up.
Please check if the Wi-Fi module is connected well, and make sure inverter is
powered up normally.
Note: If Wi-Fi LED on the inverter is single-blinking (0.5s on & off ), then
it means Wi-Fi module is not connected or not connected well.
Q: Why can’t I find the Solar-WiFi* signal on smart phone?
A: It can connect to only device at a time. So please make sure other devices
are not already connected to the signal.
Note: Please make sure the password of the Wi-Fi signal (12345678) is not
wrong.
About battery operation
Q: Why does the battery not discharge when grid is not available, while it
discharge normally when grid is available?
A: On App, off-grid output and back-up function should be turned on to make
battery discharge under off-grid mode.
Q: Why is there output on the Back-Up side?
A: For backup supply, the Back-Up function on PV Master App must be turned on.
Under off-grid mode or grid power is disconnected, Off-Grid output function must
be turned on as well.
Note: When turning on Off-Grid output, don’t restart the inverter or battery,
otherwise the function will switch off automatically.
Q: Why battery switch always trip when starts it up (Lithium battery)?
A: For lithium batteries like LG, normally the switch trips for the following
reasons:
- BMS communication fails.
- Battery SOC is too low, battery trips to protect itself.
- An electrical short circuit occurred on the battery connection side. Or other reasons please contact GoodWe for details.
Q: Which battery should I use for S-BP?
A: For S-BP inverters, it could connect lithium batteries, with nominal
voltage 48V, max charge voltage 60V.
Compatible lithium batteries please refer to S-BP QUICK INSTALLATION
INSTRUCTIONS
About PV Master operation and monitoring
Q: Why can’t I save settings on PV Master APP
A: This could be caused by losing connection to Solar-WiFi*.
- Make sure you are connected to Solar-WiFi (make sure no other devices are connected) or router (if connected Solar-WiFi to router) and on APP home page shows the connection is stable.
- Make sure S-BP is under wait mode (on App) before you change any settings on PV Master App disconnect grid/load, only leave the battery connected and then restart S-BP till the work mode displays “wait” on the App.
Q: On the App, why are the data displayed on the homepage and param page
different, like charge/discharge, load or grid value?
A: The data refresh frequency is different, so there will be a data in
conformity between different
pages on App as well as between that on the portal and App.
Q: On the App, some columns show NA, like battery SOH, etc. why is that?
A: NA means App does not receive data from inverter or server, normally it is
due to communication problems, such as battery communication, and
communication between the inverter and the App. (For lead-acid battery, NA is
normal)
About Smart Meter and Power Limit Function
Q: Is power limit function possible for S-BP system?
A: Please refer to page 11 for details of this function on S-BP system.
Q: Can I use other brand’s Meter to take over Smart Meter in the S-BP system
or change some settings on Smart Meter?
A: No, because the communication protocol between inverter and Smart Meter is
in-build in the Smart Meter, other brands’ Meter cannot communicate. Also any
setting change could cause Smart Meter communication failure.
Q: What is the max current allowed going through CT on Smart Meter?
A: The max current for CT is 120A
Other questions
Q: Is there a quick way to make the system work?
A: The shortest way, please refer to S-BP QUICK INSTALLATION INSTRUCTIONS
Q: What kind of load can I connect on the Back-Up side?
A: Please refer to user manual on page 11.
Q: Will the warranty of the inverter still be valid if for some special
conditions we cannot
100% follow the installation or operation instructions of the user manual?
A: Normally we still provide technical support to problems caused from
disobeying the instructions of the user manual, but we cannot guarantee a
replacement or returns. So if there is any special condition when you cannot
100% follow the instructions, please contact after-sales for suggestions.
Disclaimer
The S-BP series inverters are transported, used and operated under environmental and electrical conditions. The manufacturer has the right not to provide after-sales services or assistance under the following conditions:
- The inverter is damaged during the transfer.
- Inverter’s warranty has expired and extended warranty is not bought.
- The inverter is installed, refitted or operated in improper ways without authorization from the manufacturer.
- The inverter is installed or used under improper environment or technical condition mentioned in this user manual, without authorization from the manufacturer.
- Installation or configuration of the inverter does not follow the requirements mentioned in this user manual.
- The inverter is installed or operated against the requirements or warnings that are mentioned in this user manual.
- Inverter is broken or damaged by any force majeure like lightning, earthquake, fire hazard, storm and volcanic eruption etc.
- The inverter is disassembled, changed or updated on software or hardware without authorization from the manufacturer.
- Inverter is installed, used or operated against any related items in international or local policies or regulations.
- Any non-compatible batteries, loads or other devices connected to BT system.
- The Battery-Ready inverter activation code is obtained through illegal channels.
Note: The manufacturer will keep right to explain all the contents in this user manual. To insure IP65, the inverter must be sealed well, please install the inverters within one day after unpacking, otherwise please seal all unused terminals/holes, terminals/holes are not allowed to be kept open, confirm that there is no risk of water or dust entering the terminals/holes. Maintenance The inverter requires periodical maintenance, details are shown below:
- Make sure inverter is totally isolated from all DC and AC power for at least 5 mins before maintenance.
- Heat sink: Please use a clean towel to clean up heat sink once a year.
- Torque: Please use torque wrench to tighten AC and DC wiring connection once a year.
- DC breaker: Check DC breaker regularly, active the DC breaker 10 times in a row once a year.
- Operating DC breaker will clean contacts and extend lifespan of DC breaker.
- Water-proof covers: Check if water-proof covers of RS485 and other part are replaced once a year.
Technical Parameters
Technical Data | GW3600S-BP | GW5000S-BP |
---|
Battery Input Data
Battery Type1| | U-Ion
Nominal Battery Voltage (V)| | 48
Max. charging voltage (V)| | 460 (Configurable)
Max. Charging Current (A)l| 75| 100
Max. Discharging Current (A) 3| 75| 100
Battery Capacity (Ah)2| | 50-2000
Charging Strategy for Li-Ion Battery| Self-adaption to BMS
AC Output Data (On-grid)
Nominal Power Output to Utility Grid (W| |
Max. Apparent Power Output to Utility Grid (VA).4| 3680| 5000
Max. Apparent Power from Utility Grid (VA)| 7360|
9200
Nominal Output Voltage (V)| | 230
Nominal Output Frequency (Hz)| | 5060
Max. AC Current Output to Utility Grid (A)| 16|
Max. AC Current From Utility Grid (A)| 32|
40
Output Power Factor| -1 (Adjustable from 0.8 leading to 0.8 lagging)
Output THDi (@Nominal Output)| <3%
AC Output Data (Back-up)
Max. Output Apparent Power (VA) *6| 3680| 5000
Peak Output Apparent Power (VA) .6| 4416, lO sec| 5500, lO sec
Automatic Switch Time (ms)| | <10
Nominal Output Voltage (V)| | 230 (±2%)
Nominal Output Freqency (Hz)| | 50/60 (±0.2%)
Max. Output Current (A)| 16| 123.
Output THDy (@Linear Load)| | <3%
Efficiency
Max. Efficiency| | 95.5%
Protection
Anti-islanding Protection| | Integrated
Output Over Current Protection| | Integrated
Output Short Protection| | Integrated
Output Over-Voltage Protection| | Integrated
General Data
Operating Temperature Range (℃Relative Humidity| -25~60
Operating Altitude (m)| 0~95%
Cooling| 4000
Noise (dB)| Nature Convection
User Interface| <25
Communication with BMS| LED & APP
Communication with Meter| RS485; CAN
Communication with Portal| RS485
Weight (kg)| Wi-Fi
Size (WidthHeightDepth mm)| 18.5
Mounting| 347432190
Protection Degree| Wall Bracket
Standby Self Consumption (W)| IP65
Topology| <15
Certifications & Standards| Battery Isolation
Grid Regulation| VDE-AR-N 4105; VDE 0126-1-1
EN 50549-1; G98, G100; CEI 0-21; AS/NZS 4777.2 NRIEC62477-1,
Safety Regulation| IEC62040-1, IEC62040-1
EMC| EN 61000-6-1, EN 61000-6-2, EN
- The actual charge and discharge current also depend on the battery.
- Battery capacity could be not less than 100Ah where the backup function is to be applied.
- 4600 for VDE0126-1-1&VDE-AR-N 4105 and CEI 0-21.
- For CEI 0-21 GW3600S-BP is 4050,GW5000S-BP is 5100; for VDE-AR-N4105 GW5000S-BP is 4600.
- 21.7A for AS4777.2.
- Can be reached only if battery capacity is enough, otherwise will shut down.
- CAN communication is configured by default. If 485 communication is used, please replace the corresponding communication line.
- Not all certifications & standards are listed, check the official website for details.
CERTIFICATES OF S-BP SERIES
Other Test
For Australian requirements, in the THDi test, Zref should be added between
inverter and mains.
RA, XA for Line conduvtor
RN, XN for Neutral conductor
Zref:
RA=0, 24; XA=j0,15 at 50Hz;
RN=0, 16; XN=j0,10 at 50Hz
Quick Check List To Avoid Danger
- The inverter cannot be installed near flammable, explosive or strong electro-magnetic equipment, please refer to page 06
- Remember that this inverter is heavy! Please be careful when lifting out from the package, please refer to page 07
- Make sure battery breaker is off and battery nominal voltage meets S-BP specification before connecting the battery to the inverter and makes sure inverter is totally isolated from AC power, please refer to page 10
- Make sure inverter is totally isolated from any DC or AC power before connecting AC cable, please refer to page 11
- Make sure AC cable is totally isolated from AC power before connecting Smart Meter & CT, please refer to page 14
Appendix protection category defintion
Overvoltage category definition
Category I| Applies to equipment connected to a circuit where measures have
been taken to reduce transient overvoltage to a low level.
---|---
Category II| Applies to equipment not permanently connected to the
installation. Examples are appliances, portable tools and other plug-connected
equipment.
Category III| Applies to a fixed equipment downstream, including the main
distribution board. Examples are switchgear and other equipment in an
industrial installation.
Category IV| Applies to equipment permanently connected at the origin of an
installation (upstream of the main distribution board). Examples are
electricity meters, primary overcurrent protection equipment and other
equipment connected directly to outdoor open lines.
Moisture location category definition
| Level
---|---
Moisture Parameters| 3K3| 4K3| 4K4H
Temperature Range| 0~+40℃| -33~+40℃| ~20~+55℃
Moisture Parameters| 5%~85%| 15%~100%| 4%~100%
Environment category definition
Environment Condition | Ambient Temperature | Relative Humidity | Applied to |
---|---|---|---|
Outdoor | -20~50℃ | 4%~100% | PD3 |
Indoor Unconditioned | -20~50℃ | 5%~95% | PD3 |
Indoor conditioned | 0~40℃ | 5%~85% | PD2 |
Pollution degree definition
Pollution Degree I| No pollution or only dry, non-conductive pollution occurs.
The pollution has no influence.
---|---
Pollution Degree II| Normally only non-conductive pollution occurs.
Occasionally,
however, a temporary conductivity caused by condensation
must be expected.
Pollution Degree III| Conductive pollution occurs, or dry. non-conductive
pollution
occurs, which becomes conductive due to condensation,
which is expected.
Pollution Degree IV| Persistent conductive pollution occurs, for example, the
pollution caused by conductive dust, rain or snow.
https://www.linkedin.com/company/jiangsu-goodwe-power-supply-technology-co-
ltd-/
https://www.semsportal.com/home/AppDownload
https://www.semsportal.com/home/pvmaster
https://www.semsportal.com
http://en.goodwe.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>