Danfoss AMEi 6 iSET Intelligent Electrical Actuator User Guide

June 16, 2024
Danfoss

Danfoss LOGO 2 ENGINEERING TOMORROW
AMEi 6 iSET/73695610

Operating Guide
Intelligent electrical actuator
AMEi 6 iSET

AMEi 6 iSET Intelligent Electrical Actuator

Danfoss AMEi 6 iSET Intelligent Electrical Actuator -
iNET| Danfoss AMEi 6 iSET Intelligent
Electrical Actuator - AFQMP| Danfoss
AMEi 6 iSET Intelligent Electrical Actuator - AFPQ
---|---|---
AMEi 6 intelligent actuator with iNET| AMEi 6 iNET + VFG 22(1) + AFQMP 2| AMEi 6 iNET + VFG 22(1) + AFPQ 2

www.danfoss.comDanfoss AMEi 6 iSET
Intelligent Electrical Actuator - QR Code virtus.danfoss.comDanfoss AMEi 6
iSET Intelligent Electrical Actuator - AMEi 6 iSET

Application principle

Danfoss AMEi 6 iSET Intelligent Electrical Actuator - Application
principle

SN 0 V Neutral
SP 24 V ac/dc, 230 V ac Power supply
Y 0(2)-10 V Input

0(4)-20 mA
X| 0(2)-10 V| Output
0(4)-20 mA
A| D−| Modbus
B| D+
GND| Ground

Danfoss AMEi 6 iSET Intelligent Electrical Actuator - FIGURE
1Danfoss AMEi 6 iSET Intelligent
Electrical Actuator - FIGURE 2Danfoss AMEi 6 iSET Intelligent Electrical Actuator - FIGURE
3Danfoss AMEi 6 iSET Intelligent
Electrical Actuator - FIGURE 4 7

Indication type Operating mode
Actuator is squeezing the spring;

is squeezing the spring;

Actuator is stretching the spring;| | | Constantly lit;| Normal mode – Actuator is stretching the spring;
Actuator is squeezing the spring;| | | Flashing (1s cycle);| Calibration mode – Actuator is squeezing the spring;

Actuator is stretching the spring;| | | Flashing (1s cycle);| Calibration mode – Actuator is stretching the spring;
Actuator has reached the upper end position (squeezed spring)| | | Constantly lit;| Normal mode – Actuator stops at the upper end position;
Actuator has reached the bottom end
position (stretched spring)| | | Constantly lit;| Normal mode – Actuator stops at the bottom end position;
Y signal is present, actuator reached Set-Point;
| | | Flashing;| Normal mode – Actuator stopped at the position which match Y set-point;

Y signal is not connected – (broken wire);| | | 2-fast Flash after
1 s period;| Normal mode – Y signal is not connected – (broken wire) motor stopped at position when Y was last present;

Stand-By-mode;| | | Constantly lit;| Stand-by-mode;

Error mode;| | | Flashing;| Error mode;
Actuator is squeezing the spring;| | | Flashing (1s cycle);| Manual mode – Button „ SQUEEZE SPRING“ >10 sec
Actuator is squeezing the spring;
Constantly lit;

Actuator is stretching the spring;| | | Constantly lit;| Manual mode – Button „ STRETCH SPRING“ >10 sec
Flashing (1s cycle);
Actuator is squeezing the spring;| | | Constantly lit;| Manual mode – Button „ SQUEEZE SPRING“ <10 sec
Actuator is squeezing the spring;

Actuator is stretching the spring;| | | Constantly lit;| Manual mode – Button „ STRETCH SPRING“ <10 sec
Actuator is stretching the spring;
Motor stopped in the “SQUEEZE
SPRING“ positioning mode;| | | Constantly lit;| Manual mode – Motor stopped in the “SQUEEZE SPRING“ positioning mode;

Motor stopped in the “STRETCH
SPRING“positioning mode;| | | Constantly lit;| Manual mode – Motor stopped in the “STRETCH SPRING“ positioning mode;

7

Indication type Modbus communication status

No power supply;
| | Dark;| No communication;
| | Flashing;| RX telegram is for me;
RX activity on BUS;
| Error in message interpretation;

Danfoss AMEi 6 iSET Intelligent Electrical Actuator - Symbol
36

Pressure actuators

Size(cm2) ØA AFP 2, AFD 2 AFA 2 AFPB 2 AFPA 2 AFPQ 2 AFQMP 2
H H H H ØA1 H1 ØA1 H1

mm
80| 175| 602| 558| 515| 612| –| –| –| –
160| 228| 622| 578| 605| 612| 228| 727| 295| 622
320| 295| 622| 578| 605| 612| 300| 727| 295| 622
630| 300| 747| 703| 730| 735| –| –| –| –

Safety Notes

To avoid personal injury and damage to devices, it is absolutely essential for these instructions and safety notes to be read carefully and reviewed prior to assembly and use.
Do not dismantle actuator with the safety spring function! There is risk of injury and death in the event of improper handling!
The actuator is heavy. Handle with care to avoid injury or product damage.

Wiring

Do not touch anything on the PCB!
Do not remove the service cover before the power supply is fully switched off.

Wiring length Recommended cross-sectional area of the wiring
0-50 m 0,75 mm²
> 50 m 1,5 mm²

Electrical connection ❶

iSET actuator mounting to pressure actuator ❷
Stand-By mode for manual operation and differential pressure setting ❸
Set-point range see rating plate on the pressure actuator*

  1. Start-up of system *
  2. Set flow rate on a motorized valve over which the differential pressure is controlled, to about 50 % *
  3. Adjustment
    • Observe pressure indica tors *
    Enter the Stand-By mode for manual operation
    • Pushing the button on the actuator increases the set-point (squeezing the spring)
    • Pushing the button redu ces the set-point (stretching the spring)

End switch setting for MIN/MAX set Δp ❹
Slider ① can be set to limit min. ∆p
Slider ② can be set to limit max. ∆p
Fix the sliders ①, ② with 2 srews ③
Slider ② may be sealed ④

  • see instruction for relevant combination pressure actuator/ valve
    DIP switch setting ❺

S1/DIP 1
Input signal type selector:
OFF: Input signal Y is set to voltage (V)
ON: Input signal Y is set to current (mA)
S1/DIP 2
Output signal type selector:
OFF: Output signal X is set to voltage (V)
ON: Output signal X is set to current (mA)
S1/DIP 3
Direct or inverse acting selector (Fig. 2):
OFF: Actuator is direct acting to input signal
ON: Not to be used for iSET
S1/DIP 4
Normal or sequential mode selector:
OFF: Actuator is working in range 0(2)-10 V or 0(4)-20 mA
ON: Actuator is working in sequential range; 0-5 V or (0-10 mA) or (5-10 V) or (10-20 mA)
Signal range selector S1/DIP 6 sets the sequential range.
S1/DIP 5
0-10 V/2-10 V – Input/output
OFF: 0-10 V; input signal is in the range from 0-10 V (voltage input) or from 0-20 mA (current input)
ON: 2 –10 V; input signal is in the range from 2-10 V (voltage input) or from 4-20 mA (current input)
Signal range selector S1/DIP 1 & DIP 2 sets Y and X signal.
S1/DIP 6
Sequential range selector:
OFF: 0-5 V or (0-10 mA)
ON: 5-10 V or (10-20 mA)
[S1/DIP 4 = ON!] S1/DIP 7
OFF: iSET
ON: iNET
S1/DIP 8
Not used
See AMEi 6 iNET data sheet

S2/DIP 1
OFF: analog MCV control signal
ON: 3-point MCV control signal
S2/DIP 2
OFF: analog MCV control signal
ON: 3-point MCV control signal
S2/DIP 3
Not used
**S2/DIP 4**
OFF: Analog signal (V/mA)
Actuator operates in analog mode
ON: MOD BUS
Actuator operates in digital mode
In analog mode S2/DIP 4 = OFF, DIP switches S1/DIP 1-7 work as active functions.
In digital mode S2/DIP 4 = ON , DIP switches S1/DIP 1-7 work as a digital addresses.
In digital mode Modbus RS485 could be used either for the monitoring purposes or for the AMEi 6 actuator positioning.

Danfoss AMEi 6 iSET Intelligent Electrical Actuator - digital
mode

Calibration ❻
Calibration to the desired pressure actuator stroke (min-max spring setting).
Before calibration drive the actuator out of end positions (minimal gap between sliders ①,② and pin on the end switch ③ has to be ensured).
To start calibration procedure, press and hold RESET button for 5 seconds until the green light starts flashing. End positions of the actuator are automatically adopted based on pre-set end switch positions sliders ①,②. Actuator goes to the stationary mode and starts responding to the control signal. Depends on min-max Δp setting (position of sliders ① and ②), calibration may take up to ~1 h (in case of max available Δp range-stroke is set).
Calibration procedure need to be repeated every time when min/max spring setting is changed (position of sliders ① and ② is changed).
LED signalisation ❼
Dimensions ❽

Danfoss A/S
Climate Solutions « danfoss.com +» +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

© Danfoss | 2023.12
AQ30568060085901-010203

Documents / Resources

| Danfoss AMEi 6 iSET Intelligent Electrical Actuator [pdf] User Guide
AMEi 6 iSET Intelligent Electrical Actuator, AMEi 6 iSET, Intelligent Electrical Actuator, Electrical Actuator, Actuator
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals