GROWATT ARK 12.8H Energy Storage Instructions
- May 15, 2024
- Growatt
Table of Contents
User Manual(A1) ARK High Voltage Battery System
ARK 12.8H Energy Storage
About this Document
This document describes the installation, electrical connection, operation,
commission, maintenance and troubleshooting of ARK High Voltage Battery
System. Before installing and operating ARK High Voltage Battery System,
ensure that you are familiar with product features, functions, and safety
precautions provided in this document.
Symbol | Description |
---|---|
Indicates a potentially hazardous situation, if not avoided, could result |
in serious injury or death.
Product Overview
1.1 Intended Use
The entire ARK High Voltage Battery System includes a HVC 60050-A1(high
voltage controller) and multiple ARK 2.5H-A1 (battery pack).
Each ARK 2.5H-A1 consists of 50Ah cells which form 51.2V voltage battery pack
via one parallel and sixteen serial connection (1P16S). Two to ten ARK 2.5H-A1
can be connected in serial to extend the capacity and power of energy storage
system.
The ARK battery system powers the loads through PCS at nighttime without
solar; when solar becomes available during daytime, solar energy powers the
loads as a priority and store residual solar power into the ARK battery
system.
1.2 Appearance
1.2.1 HVC 60050-A1 (high voltage controller)
The high voltage controller is composed of battery control unit, DC breaker,
power supply and communication terminals. The appearance of the product is
shown as below.
Location | Port | Function |
---|---|---|
1 | PCS | Communication with PCS |
2 | Link-In | Battery system parallel communication entrance |
3 | Pressure relief valve | Pressures inside is released via the vent |
4 | Link-Out | Battery system parallel communication export |
5 | BMU | Communication with battery module |
6 | Module+/ Module- | Connect to the power terminal of the battery string |
7 | **** | Ground terminal |
8 | PCS+/PCS- | The output from battery system to the PCS |
9 | **** | Ground terminal |
10 | USB interface | USB communication interface |
11 | LED | SOC and working status indication of the system |
12 | Breaker | Breaker to turn on/off the whole battery system |
13 | Power button | Wake up the battery system |
Dimension (unit: mm) 1.2.2 ARK 2.5H-A1 (battery pack)
ARK 2.5H-A1 consists of battery module (including cell and mechanical parts),
Battery management unit (BMU) as well as power and communication terminals.
Product appearance is shown as below.
Location | Port | Function |
---|---|---|
1 | Link0 | Communicate with the previous module Link1 |
2 | Link1 | Communicate with the next module Link0 |
3 | Module- | Connect to the positive terminal of the adjacent module |
4 | Module+ | Connect to the negative terminal of the adjacent module |
5 | **** | Ground terminal |
6 | Pressure relief valve | Pressures inside is released via the vent |
7 | **** | Ground terminal |
Dimension (unit: mm) 1.3 Working Principle and Function
The ARK high voltage battery system is composed of a high voltage controller
HVC 60050-A1 and battery pack ARK 2.5H-A1 in series. It contains
electrochemical batteries, battery control units, battery management units,
power and signal terminals, and mechanical parts.
Compared with other battery systems, it has better charging and discharging
performance, higher charging and discharging efficiency, more accurate status
monitor, longer cycle life and less self-discharge loss.
A single cluster system can connect 2 to 10 packs in series to increase the
capacity and power of the battery system. The entire battery system
communicates with the inverter through CAN communication, and the operation
stability is high.
- Monitoring: voltage, current and temperature detection of both single cells and battery system.
- Protection and Alarm: protection and alarm when overvoltage, under voltage, over current, over temperature or under temperature occurs. See Appendix I for the details.
- Report: report all alarm and status data to PCS.
- Series connection: support two to ten packs in Series connection.
- Power failure triggered by fault: 10 minutes after the battery system and PCS communication is disconnected or 15 minutes after undervoltage protection.
Safety
When installing or using a battery system, the safety information contained in this section must always be followed. For safety reasons, it is the installer’s responsibility to be familiar with this manual and all warnings before installation.
2.1 Basic security
The battery system has been designed and tested in accordance with strict
rules with international safety certification requirements. Before any
installation or use of the battery system, please read all safety instructions
carefully and always follow the relevant rules. Growatt is not responsible for
any consequences resulting from violation of the following regulations:
- Damage occurred during transportation.
- Incorrect transportation, storage, installation and use, or customer fails to convey the correct information about transportation, storage, installation and use to terminal. customers.
- Non-professional installation.
- Failure to obey the rules of this operation instructions and safety precautions in this document.
- Unauthorized modifications or removal of the software package.
- The product’s tamper label is damaged or the product lacks any parts (except authorized disassembly parts).
- Operation in extreme environments which are not allowed in this document .
- Repair, disassemble, or change packs without authorization and cause failure.
- Damage to shell labels or modifies date of production.
- Packs fail to be charge for more than six months.
- Damages due to force majeure (such as lightning, earthquakes, fire, and storms).
- Warranty expiration.
2.2 Safety Precautions
2.2.1 Environment requirements
- Do not expose the battery to temperature above 50℃ or heat sources.
- Do not install or use the battery in wet locations, moisture, corrosive gases or liquids, such as bathroom.
- Do not expose the battery to direct sunlight for extended periods of time.
- Place battery in safe place away from children and animals.
- Battery power terminals shall not touch conductive objects such as wires.
- Do not dispose the batteries in fire, which may cause an explosion.
- The battery system shall not come in contact with liquids.
2.2.2 Operation Precautions
- Do not touch the battery system with wet hands.
- Do not disassemble the battery system without permission.
- Do not crush, drop or pierce the battery pack and high voltage controller.
- Dispose the batteries according to local safety regulations.
- Store and recharge battery in accordance with this manual.
- Ensure the connection of ground wire reliable.
- Remove all metal objects such as watches and rings that could cause a short-circuit before installation, replacement and maintenance.
- The pack shall be repaired, replaced or maintained by skilled personal that has been recognized.
- When storing or handling batteries ,do not stack batteries without package.
- Do not broke the battery, the released electrolyte may be toxic and is harmful to skin and eyes.
- Packaged batteries should not be stacked more than specified number stipulated on the packing case.
- Do not use damaged, failed or deformed batteries, which may lead to high temperature or even dangerous accidents. Continued operation of damaged battery may result in electrical shock, fire or even worse.
2.3 Warning Labels
Symbols | Description |
---|---|
Do not dispose in trash | |
Lithium ion battery can be recycled | |
Certification in European union area | |
Electric shock hazard | |
Explosive gas | |
May leak corrosive electrolyte | |
Heavy enough to cause severe injury | |
Keep the Pack away from children | |
Make sure the battery polarity well connected | |
Do not expose to fire | |
Operate as the Manual |
ARK25HA1Lithium Ion Battery
Model| ARK 2.5H-A1
Nominal Voltage| 51.2V
Nominal/Rated Capacity| 50Ah/45Ah
Nominal/Rated Energy| 2560Wh/2300Wh
Rated Current| 25A
Ingress Protection| IP 65
Operating Ambient Temperature| -10°C ~ +50°C
Fig 2.1: Nameplate
ARK High Voltage Battery System
System Model/ Nominal Voltage/
Nominal Energy/ Rated Energy| ARK 5.1H-A1/102.4V/ 5.12kWh/4.6kWh
ARK 7.6H-A1/153.6V/ 7.68kWh/6.9kWh
ARK 10.2H-A1/204.8V/ 10.24kWh/9.2kWh
ARK 12.8H-A1/256.0V/ 12.80kWh/11.5kWh
ARK 15.3H-A1/307.2V/ 15.36kWh/13.8kWh
ARK 17.9H-A1/358.4V/ 17.92kWh/16.1kWh
ARK 20.4H-A1/409.6V/ 20.48kWh/18.4kWh
ARK 23.0H-A1/460.8V/ 23.04kWh/20.7kWh
ARK 25.6H-A1/512.0V/ 25.6kWh/23.04kWh
High Voltage Controller Model| HVC 60050-A1
Protective Class| I
Rated Current| 25A
Nominal/Rated Capacity| 50Ah/45Ah
Ingress Protection| IP65
OperatingAmbient Temperature| -10°C ~ +50°C
X
Fig 2.3: Nameplate
WARNING
- Do not disassemble or alter the PACK to avoid heat ,explosion or fire.
- Do not use the PACK beyond specifide conditions.It might cause heat generation,damage,or deterioration of its performance.
- Do not throw,drop,hit,drive a nail in,stamp on the PACK.It may cause heat generation,explosion,or fire.
- In case of electrolyte leakage,keep leaked electrolyte away from contact with eyes or skin.immediately clean with water and seek help from a doctor.
- Do not put the PACK into a fire.Do not use it or leave it on a place near fire,heaters,or high temperature sources.It may cause over temperature,explosion or fire.
- Do not submerge the PACK in water,or wet the product.It may cause heat generation,explosion ,or fire.
- Do not reversely connect the PACK positive(+)and negative(-)terminal.
- Do not short circuit by letting the PACK terminals(+and -)contact a wire or any meta .
- The unit is heavy enough to cause severe injury.
- Keep out of reach of children or animals.
The performance will be limited when the temperature is below 0°C.
2.4 Emergency Responses
Manufacturer takes foreseeable risk scenarios into consideration and is
designed to reduce hazards and dangers. However, if the following situation
occurs, do as below:
Situation Occurs | Description and action need |
---|---|
Leakage | Avoid touch of leaking liquid or gas. If you touch the leaking |
electrolyte, do as below immediately.
Inhalation: Evacuate the contaminated area, and seek medical help. Eye
contact: Rinse eyes with flowing water for 15 minutes, and seek medical help.
Skin contact: Rinse contacted area thoroughly with soap and water, and seek
medical help.
Ingestion: Vomiting, and seek medical help.
On fire| It’s hard for battery system ignite spontaneously. If the battery has
caught a fire, do not try to extinguish the fire but evacuate people
immediately.
Wet Packs| If the battery system is soaked or submerged in water, do not
access it. Contact Growatt or distributors immediately for technical
assistance.
Damaged shell| Damage to the shell is very dangerous, so special attention
must be paid. They are no longer suitable for use and may be dangerous to
personnel. If the battery case is damaged, please stop using it and contact
Growatt or a distributor.
Storage and Transportation
3.1 Storage Requirements
➢ Place the product follow the identification on the packing case during
storage.
➢ Do not put the product upside down or sidelong.
➢ The defective product needs to be separated from other product.
➢ The storage environment requirements are as follows:
- Place the product in a dry, clean and well ventilated place.
- The storage temperature for a short week(7 days) is between -20°C to 50℃.
- If you store the product over a long period of six months, the storage temperature is between -20°C to 40°C, relative humidity: 5%~95%RH.
- Place the product away from corrosive and organic substances (including gas exposure).
- Free from direct exposure to sunlight and rain.
- At least two meters away from heat sources (such as a radiator) .
- Free from exposure to intensive infrared radiation.
➢ If the battery is stored for more than six months, the battery pack shall be recharged to 40% SOC every six months using a charger.
If not follow the above instructions for long-term storage, the battery cycle life will be reduced or even damaged.
3.2 Transportation Requirement
Battery pack has been certified in UN38.3 (Section 38.3 of the sixth Revised
Edition of the Recommendations on the Transport of Dangerous Goods: Manual of
Tests and Criteria) and SN/T 0370.2-2009 (Part 2: Performance Test of the
Rules for the Inspection of Packaging for Exporting Dangerous Goods). Battery
pack is classified as category 9 dangerous goods.
- The battery pack shall not be transported with other inflammable, explosive or toxic substances.
- Ensure the original Package and label complete and recognizable.
- Prohibit direct exposure to sunlight, rain, condensing water caused by temperature difference and mechanical damages.
- Prohibit to pile up more than six battery pack.
- There will be a drop in capacity during transportation and storage.
- Transportation temperature is between -20°C to 40°C, relative humidity: 5%~95%RH.
Installation
| ➢ The installation and use of batteries involve a lot of expertise.
Therefore, please ensure that technicians have obtained relevant technical
certificates before operation.
➢ Ensure to read the Guidance before installation in order to understand
product information and safety cautions.
➢ Operators should be well trained technicians and fully understand the whole
photovoltaic system, grid network, battery system, working principle and
national regional standards.
➢ Installers must use insulating tools and wear safety equipment.
➢ Device damages caused by failure to comply with storage, transportation,
installation and use requirements specified in Guidance are not coved by
Warranty.
➢ Do not install or use battery near explosive or inflammable substances.
➢ Use battery in well-ventilated environment with temperature ranging from
-10℃ to 50℃.
➢ Maintain a minimum level of dust and dirt in the environment.
➢ Do not install battery in highly humid area such as bathroom.
➢ Please make sure that all battery pack connected in series are from the same
batch, the same model and the same manufacturer. Do not mix old batteries with
new batteries. A battery pack that does not exceed 300 cycles is defined as a
new battery.
---|---
| ➢ Before installing in series, make sure that the voltage difference of the
battery pack must be less than or equal to 0.5V.
➢ When installing the batteries, we recommend that the manufacturing date of
batteries in the same system should be within 3 months. The manufacturing date
of batteries can be interpreted through bar code (refer to Appendix 1).
4.1 Installation environment
- The battery system can be installed indoors or outdoors. The following conditions are allowed:
Do not place the battery pack upside down.
- When installing outdoors, it is necessary to install sunshades and rain shelters to avoid direct exposure to sunlight and rain.
4.2 Installation Required Tools
The following tools are required to install the battery system:It is recommended to wear the
following safety gear when dealing with the battery system. 4.3 Installation Procedures
4.3.1 Pre-installation Check
- Check the PACK package before open it. If any abnormity is detected, do not open the Package and contact your distributor.
- Check the quantity of all parts inside according to the package list. If there is any part missing or damaged, please contact your distributor.
4.3.1.1 Check the list of HVC 60050-A14.3.1.2 Check the list of ARK 2.5H-A14.3.1.3 Check the battery base and wall bracket
| ➢ The high voltage controller (HVC 60050-A1) and the battery pack (ARK
2.5H-A1) are standard accessories, please be sure to purchase both, a battery
system only needs a high voltage controller (HVC 60050-A1), battery pack (ARK
2.5H-A1) You can freely match the number within 2 to 10 .
➢ The battery base is only used for floor installation, and the wall bracket
is only used for wall installation .The battery base and wall bracket are
optional accessory, not standard accessory.
➢ You need to separately purchase the connection cable from the high voltage
controller (HVC 60050-A1) to the PCS.
➢ If you want to install the same battery system in two lines, you need to
purchase a extension cable separately for connection.
➢ The installation method can be selected wall Mounted installation or floor
standing installation as required.
---|---
4.3.2 Wall Mounted Installation
- Step 1: Please make sure that the weight capacity of the wall should exceed 150kg.
- Step 2: Put bracket on wall and mark drilling spots. Keep a minimum distance of 300mm between the wall and bracket; a minimum distance of 500mm between bracket and ground.
- Step 3: Choose an alloy drill with a diameter of 8mm, and drill at least 60mm mounting holes in the wall. Clean the soil and insert the expansion tube into the hole, then screw in the screw to fix the wall mount.
- Step 4: Fix the battery on the wall mount, make sure that the battery will not shake, and then lock the safety screw.
➢ The number of wall-mounted installations should not exceed 4 (including high
voltage controllers).
➢ If there are more than 4, please install them in two lines, and the spacing
should be greater than or equal to 300mm.
4.3.3 Floor Standing Installation
- Step 1: Place the battery base in the area to be installed, and mark the position of the installation hole with a marker. The minimum distance between the wall and the battery is 300mm.
- Step 2: Select an alloy drill with a diameter of 10mm and drill a mounting hole at least 60mm deep in the wall. Insert the expansion pipe into the hole and screw in the screws to secure the anti roll over plate.
- Step 3: Stack the battery on the base, connect the fixed connecting strip between the battery packs.
- Step 4: Make sure the battery will not shake, and then lock the safety screw.
| ➢ If more than 4 batteries are used , base mounting is recommended.
➢ For floor installation with base , the maximum stack number of the battery
is ten. But if the battery number is greater than six , we recommend stacking
them in two lines.
➢ The safety part needs to be installed at the top battery, however, once the
number of the battery pack is higher than 7, one more safety part should be
installed in the middle battery which is shown the last step.
---|---
4.4 Electrical Connection
➢ Do not forget wear ESD wrist strap and gloves, safety gloves and goggles.
4.4.1 Definition of RJ45 communication port pin4.4.1.1 Communication port definition of HVC 60050-A1
No. | PCS | LINK_IN | LINK_OUT | BMU |
---|---|---|---|---|
1 | RS485_B | Add_in | Add_out | \ |
2 | RS485_A | Master | GND | \ |
3 | GND | GND | Slaver | IMA_isoSPI |
4 | CAN_H | GND | GND | IPA_isoSPI |
5 | CAN_L | CANH | CANH | IMB_isoSPI |
6 | GND | CANL | CANL | IPB_isoSPI |
7 | WAKE- | GND | GND | \ |
8 | WAKE+ | Power_ON | Power_ON | \ |
4.4.1.2 Communication port definition of HVC 60050-A1
No. | LINK 0 | LINK 1 |
---|---|---|
1 | | \ | |
2 | | \ | |
3 | | \ | |
4 | | \ | |
5 | IMA_isoSPI | IMB_isoSPI |
6 | IPA_isoSPI | IPB_isoSPI |
7 | | \ | |
8 | | \ |
4.4.2 System connection diagram
| ➢ When connecting the power line, it must be the same color terminal to
connect , otherwise there may be dangers such as short circuit .
➢ A DC circuit breaker has been installed in the high voltage controller. If
you want to install a DC circuit breaker between the battery system and the
PCS, you need to purchase it yourself according to the following
specifications:
a. Voltage: 750Vdc/1000Vdc
b. Current: 63A
---|---
4.4.2.1 System connection diagram Note:
- The battery is not allowed to be installed in the running state. Turn off the system power before installation.
- To ensure system security, do not forget to install ground wire.
- Don’t forget to connect the communication plug of the last battery pack, otherwise it will cause system failure.
- When installing in two rows, please purchase the extended serial cable.
- The cable connecting PCS can be purchased from GROWATT.
4.4.2.2 Electrical wiring connection
A. HVC 60050-A1(High Voltage Controller) wiring
Step 1: Insert the power cable into the corresponding port, then there is
click sound indicating the connection is ok.
Step 2: Insert the communication cable into the “PCS” port and “BMU” port, and
then tighten the communication terminal clockwise. (“PCS” port connects to the
PCS. “BMU” port connects to the adjacent battery pack.)
Step 3: Connect to the PCS and adjacent battery pack using a 6mm2 grounding
wire through grounding terminal.
| ➢ For a single battery system, the “Link-in” and “Link out” port of the High
Voltage Controller don’t need to be connected, they are only used for parallel
connection of the battery systems.
➢ Please pay attention to the connector color when connection the power line.
Only the same color of the connector could be connected together.
➢ To ensure system security, do not forget to install ground wire.
---|---
B. ARK 2.5H-A1(Battery module) wiringStep 1: Insert the power cable into the
corresponding port, then there is click sound indicating the connection is ok.
Step 2: Insert the communication cable into the “Link0” and “Link1” port, and
then tighten the communication terminal clockwise. (“Link0” connects to
“Link1” of the previous module. For the battery adjacent to the high voltage
controller, “link0” is connected to the “BMU” of the high voltage controller.
“Link1” connects to “Link0” of the next module.)
Step 3: Insert a plug into the “Link1” port of the last battery module. The
plug is an annex of HVC 60050-A1 (high voltage controller).
Step 4: Connect to adjacent battery pack using a 6mm2 grounding wire through
grounding terminal.
| ➢ The battery module furthest from the HVC 60050-A1(high voltage controller)
is defined as the last battery module.
➢ Please pay attention to the connector color when connecting the power line.
Only the same color of the connector could be connected together.
➢ The power lines between the battery modules are connected in series.
Be careful not to short-circuit the battery modules during the connection
process.
---|---
Power on/off Battery system
| ➢ The installation and use of batteries need to be operated by professional
technicians.
➢ Do not contact any positions with potential difference.
➢ Prohibition sign should be hung on the battery: ” Non – professionals, do
not touch.
➢ If any abnormalities occur during the startup phase, power off the system
immediately. After problem confirmed, proceed again.
➢ Make sure the inverter is turned off before checking the battery system.
---|---
5.1 Power on Battery system ➢ Before turning on the battery, please check if the cable is properly connected.
Power on the battery system by pressing power button(t >5S)
Serial| Procedures| Acceptation criteria
1| Connect the battery and PCS| Make sure the wiring harnesses are well
connected
2| Close the breaker of the battery system| Make sure the breaker is ON
3| Press POWER button for 5 seconds. Observe the LED indication on panel..| 1.
If both RUN/ALM and SOC lights turn on normally, system is powered on
successfully.
2. If RUN/ALM light turns red, there is a failure and should solve it before
power on again.
5.2 Power off
Turn the DC breaker of the HVC 60050A1(High Voltage Controller) to “Off” to turn off the entire battery system.
Maintenance Guide
6.1 Preparation
Before maintenance, please make sure that the battery system is powered off
and the DC circuit breaker is off.
6.2 Battery pack or high voltage controller replacement
-
Wear safety gloves.
-
Close the breaker and power off the battery system.
-
Disconnect power lines and CAN communication lines of the battery system.
-
Uninstall the safety screws on both sides of the battery pack or high voltage controller.
Lift up the battery pack or high voltage controller. -
Put the battery pack or high voltage controller into the packing box according to the repair procedure and transport the battery pack or high voltage controller to the designated repair site.
-
Install new battery pack or high voltage controller based on procedure specified in Section 4.
| ➢ Before replacing the battery, use the charger to charge the new battery
and the existing battery to full (SOC 100%).
➢ If the battery is not used, it is recommended to charge and discharge the
battery every 3 months to activate the chemical characteristics, and the
maximum interval shall not exceed 6 months.
---|---
6.3 System Failure Information List and Troubleshooting Suggestions
Error Indication| Error description| Error cause| Suggested
actions
---|---|---|---
ALM
(ALM Light Flickers)| Discharge under voltage protection| Single cell voltage
below the threshold for under-voltage protection.| There is over discharge
risk. User should stop discharging and arrange recharge
Charge over voltage protection| Single cell voltage exceeding threshold for
protection threshold.| 1. There is no safety threat;
2. User should stop charging. Wait for the battery system to automatically
resolve the fault
External CAN Communication failure| Communication loss between PCS and battery
system.| 1. There is no safety threat and user should stop using battery.
2. Check if PCS and battery communication terminal is well connected.
3. If PCS and battery system cannot communicate when the communication wire
is confirmed well connected, user should contact installer to repair battery.
| Interior Communication failure|
Communication loss between two packs
| 1. Check whether the communication line between the battery pack and the
battery pack is connected OK;
2. Check whether the communication line between the high voltage controller
and the battery pack is connected OK.
---|---|---|---
High temperature protection| The temperature exceeds the protection value| It
is dangerous, please stop using the battery immediately, wait for the battery
temperature to drop, the fault will be automatically resolved.
Low temperature protection| The temperature is below the protection value| No
safety risk, wait for the temperature to rise, the fault will be automatically
resolved.
(ALM Light on)| Discharge short circuit| External short circuit of battery
system| There is safety risk and user should stop using battery.
User should contact installer to repair PCS and battery.
Precharge short circuit
Precharge overtime
Voltage sampling anomaly protection| BMS Voltage sampling failure| There is
safety risk and user should stop using battery.
User should contact installer to repair battery.
Current sampling fault| BMS current sampling failure
Main circuit fault| BMS main power circuit failure| There is safety risk and
user should stop using battery.
User should contact installer to repair battery.
Technical Specifications
7.1 System Data
System Model| ARK 5.1H-A1| ARK 7.6H-A1| ARK 10.2H-A1| ARK 12.8H-A1| ARK
15.3H-A1
---|---|---|---|---|---
Nominal energy| 5.12kWh| 7.68kWh| 10.24kWh| 12.8kWh| 15.36kWh
Rated energy| 4.608kWh| 6.912kWh| 9.216kWh| 11.52kWh| 13.82kWh
Rated Power| 2.56kw| 3.84kw| 5.12kw| 6.4kw| 7.68kw
Max Power| 4.915kw| 7.372kw| 9.83kw| 12.288kw| 14.745kw
Nominal capacity| 50Ah(@25℃)
Rated capacity| 45Ah(@25℃)
Nominal voltage| 102.4V| 153.6V| 204.8V| 256V| 307.2V
Voltage range| 94.4V~113.6V| 141.6V~170.4V| 188.8V~227.2V| 236V-284V|
283.2V~340.8V
Dimensions (mm)| 650/260/555| 650/260/740| 650/260/925| 650/260/1110|
650/260/1295
Weight| 64kg| 91kg| 118kg| 45kg| 172kg
Rated current| 25A(@25℃)
Max current| 48A(@25℃)
Fault current| 49A(@25℃)
DoD| 90%
Operating ambient temperature| -10℃~50℃
RTE| ≥95%
Battery pack in series| Maximum support 10 units in series, series voltage
difference △V≤0.5V
Humidity| 5%~95%
Storage temperature| ﹣20℃~50℃/7 days; -20℃~40℃/6 months; 95%RH
cooling method| Natural cooling
Installation| Wall-mounted/floor stacking installation
Altitude| ≤2000m
communicati on method| CAN(to PCS)
Certified product| IEC62619/IEC 62040/IEC 62477/VDE 2510-50 / RCM+ CEC /CE
Transport certification| UN38.3
IP rating| IP65
Environmental requirements| RoHS,Reach
Battery System| Secondary Li-ion Battery System
System Model| ARK 17.9H-A1| ARK 20.4H-A1| ARK 23.0H-A1| ARK 25.6H-A1
---|---|---|---|---
Nominal energy| 17.92kWh| 20.48kWh| 23.04kWh| 25.6kWh
Rated energy| 16.13kWh| 18.43kWh| 20.74kWh| 23.04kWh
Rated Power| 8.96kw| 10.24kw| 11.52kw| 12.8kw
Max Power| 17.203kw| 19.66kw| 22.118kw| 24.576kw
Nominal capacity| 50Ah(@25℃)
Rated capacity| 45Ah(@25℃)
Nominal voltage| 358.4V| 409.6V| 460.8V| 512V
Voltage range| 330.4V~397.6V| 377.6V~454.4V| 424.8V~511.2V| 472V~568V
Dimensions (mm)| 650/260/1480| 650/260/1665| 650/260/1850| 650/260/2035
Weight| 199kg| 226kg| 253kg| 280kg
Rated current| 25A(@25℃)
Max current| 48A(@25℃)
Fault current| 49A(@25℃)
DoD| 90%
Operating ambient temperature| -10℃~50℃
RTE| ≥95%
Battery pack in series| Maximum support 10 units in series, series voltage
difference △V≤0.5V
Humidity| 5%~95%
Storage temperature| ﹣20℃~50℃/7 days; -20℃~40℃/6 months; 95%RH
cooling method| Natural cooling
Installation| Wall-mounted/floor stacking installation
Altitude| ≤2000m
communication method| CAN(to PCS)
Certified product| IEC62619/IEC 62040/IEC 62477/VDE 2510-50 / RCM+ CEC /CE
Transport certification| UN38.3
IP rating| IP65
Environmental requirements| RoHS,Reach
Battery System| Secondary Li-ion Battery System
| ➢ Method for calculating rated capacity:
Rated capacity of the measured module: 45 Ah
Number of modules connected in series: 2~10
Calculated rated capacity (Ah) = 45 Ah *1 =45Ah
➢ The performance will be limited when the temperature is below 0°C.
---|---
7.2 Battery System designation
Model | Battery designation | Recommended charge instructions |
---|---|---|
ARK 5.1H-A1 | IFpP/41/150/102/[(1P16S) 2S]M/-10+50/90 | 1.Constant current 25A |
charging to 108V; 2.Constant current 10A charging to 110V; 3.Constant current
2A charging to 110V;
ARK 7.6H-A1| IFpP/41/150/102/[(1P16S) 3S]M/-10+50/90| 1.Constant current 25A
charging to 162V; 2.Constant current 10A charging to 165V; 3.Constant current
2A charging to 165V;
ARK 10.2H-A1| IFpP/41/150/102/[(1P16S) 4S]M/-10+50/90| 1.Constant current 25A
charging to 216V; 2.Constant current 10A charging to 220V; 3.Constant current
2A charging to 220V;
ARK 12.8H-A1| IFpP/41/150/102/[(1P16S) 5S]M/-10+50/90| 1.Constant current 25A
charging to 270V; 2.Constant current 10A charging to 275V; 3.Constant current
2A charging to 275V;
ARK 15.3H-A1| IFpP/41/150/102/[(1P16S) 6S]M/-10+50/90| 1.Constant current 25A
charging to 324V; 2.Constant current 10A charging to 330V; 3.Constant current
2A charging to 330V;
ARK 17.9H-A1| IFpP/41/150/102/[(1P16S) 7S]M/-10+50/90| 1.Constant current 25A
charging to 378V; 2.Constant current 10A charging to 385V; 3.Constant current
2A charging to 385V;
ARK 20.4H-A1| IFpP/41/150/102/[(1P16S) 8S]M/-10+50/90| 1.Constant current 25A
charging to 432V; 2.Constant current 10A charging to 440V; 3.Constant current
2A charging to 440V;
ARK 23.0H-A1| IFpP/41/150/102/[(1P16S) 9S]M/-10+50/90| 1.Constant current 25A
charging to 486V; 2.Constant current 10A charging to 495V; 3.Constant current
2A charging to 495V;
ARK 25.6H-A1| IFpP/41/150/102/[(1P16S) 10S]M/-10+50/90| 1.Constant current 25A
charging to 540V; 2.Constant current 10A charging to 550V; 3.Constant current
2A charging to 550V;
7.3 HVC 60050-A1
No. | Items | Specification |
---|---|---|
1 | Model | HVC 60050-A1 |
2 | Input/output voltage range | 90~585V |
3 | Rated current | 25A |
4 | Operating ambient temperature | -10~50℃ |
5 | IP rating | IP65 |
6 | communication method | CAN2.0 |
7 | Dimensions (W/D/H) | W650D260H185 mm ±2mm |
8 | Weight | 8.5±1kg |
9 | Certification | CE-EMC |
10 | Environmental requirements | RoHS |
7.4 ARK 2.5H-A1
No. | Items | Specification |
---|---|---|
1 | Battery pack Module | ARK 2.5H-A1 |
2 | Nominal Capacity/Energy | 50Ah/2.56kWh |
3 | Rated Capacity/Energy | 45Ah/2.3 kWh |
4 | Nominal Voltage | 51.2V |
5 | Operating Voltage | 47.2 – 56.8V |
6 | Rated current(25℃) | 25A |
7 | Battery Type | Cobalt Free Lithium Iron Phosphate (LFP) |
8 | Operating ambient temperature | -10~50℃ |
9 | Storage conditions | ﹣20℃~50℃/7 days; -20℃~40℃ /6 months; 95%RH |
10 | Cooling | Natural cooling |
11 | Dimension (W/D/H) | W650D260H185 mm ±2mm |
12 | Weight | 27±1kg |
13 | Installation | Wall-mounted installation/floor standing installation |
14 | Ingress protection | Ip65 |
15 | Cell safety certification | IEC62619/UL1642 |
16 | safety certification | IEC62619/IEC 62040/IEC 62477/VDE 2510-50 / RCM+ CEC |
/CE
17| Transportation test standard| UN38.3
18| Environmental requirements| RoHS
19| Battery designation| IFpP/41/150/102/[1P16S]M/- 10+50/90
➢ Barcode coding rules
Bar code number position:
- The 1th to 3th digits indicate the product code : refer to the product naming table and code correspondence table for details.
- The 4th represents the software version code , refer to GROWATT controlled “Software code history table”.
- The 5th to 8th digits represent the supplier code. GROWATT is 0000, the supplier D is 0001, and other outsourced suppliers are 0002/0003… , and so on, please refer to the corresponding relationship table of the supplier code.
- The 9th to 12th digits represent the production date, which is represented by 4 digits, the year is represented by the first 2 digits, and the week is represented by the last 2 digits, for example, the 38th week of 2013 is 1338.
- The 13th to 16th digits represent the serial number, 34 base , represented by 4 digits, and the characters 0 to Z are used. I and O in the letters are discarded.
For example, the product number is SD00.0002100, the product code is ARJ, the software version is 0, the supplier D is 0001, the production date is 21th week in 2021, and the first barcode of the work order is ARJ0000121210001.
Appendix II
LED indication Control Mechanism
LED light definition
Status| Items| SOC indication| RUN/ALM| Remark
LED1| LED2| LED3| LED4| LED5
Charge SOC| 0%-25%| (t=1S)| | | | | RUN/ALM light on and one SOC lights
flicker
26%-50%| | (t=1S)| | |
51%-75%| | | (t=1S)| |
76%-99%| | | | (t=1S)|
100%| | | | | |
Discharge SOC| 100%-76%| | | | | |
75%-51%| | | | | |
50%-26%| | | | | |
25%-5%| | | | | |
5%-0%| | | | | (t=1S)| RUN/ALM light flicker
Idle| 100%-76%| | | | | |
75%-51%| | | | | |
50%-26%| | | | | |
25%-5%| | | | | |
5%-0%| | | | | (t=1S)| RUN/ALM light flicker
Protection| Cell charge overvoltage alarm| LED1-LED4 indicates current
remaining capacity| (t=1S)| RUN/ALM light flicker green
Cell charge overvoltage protection| (t=1S)| RUN/ALM light flicker green
Cell discharge undervoltag e alarm| (t=1S)| RUN/ALM light flicker green
Cell discharge undervoltag e protection| (t=1S)| RUN/ALM light flicker green
Charge and discharge high temperatur e alarm| (t=1S)| RUN/ALM light flicker
green
| Charge and discharge high temperature protection| | (t=1S)| RUN/ALM light
flicker green
---|---|---|---|---
Charge and discharge low temperature alarm| (t=1S)| RUN/ALM light flicker
green
Charge and discharge low temperature protection| (t=1S)| RUN/ALM light
flicker green
PACK charge overvoltage alarm| (t=1S)| RUN/ALM light flicker green
PACK charge overvoltage protection| (t=1S)| RUN/ALM light flicker green
PACK discharge undervoltag e alarm| (t=1S)| RUN/ALM light flicker green
PACK discharge undervoltag e protection| (t=1S)| RUN/ALM light flicker green
High temperature environment alarm| (t=1S)| RUN/ALM light flicker green
High temperature environment protection| (t=1S)| RUN/ALM light flicker green
Cell Large voltage difference alarm| (t=1S)| RUN/ALM light flicker green
Cell Large voltage difference protection| (t=1S)| RUN/ALM light flicker green
| Warning of high temperature difference of PACK module| | (t=1S)| RUN/ALM
light flicker green
---|---|---|---|---
Fault,perso nnel handling required| Discharge short circuit| SOC indicates
current remaining capacity| (t=1S)| RUN/ALM light flicker red
Precharge short circuit| (t=1S)| RUN/ALM light flicker red
Precharge overtime circuit| (t=1S)| RUN/ALM light flicker red
External CAN communicat ion failure| (t=1S)| RUN/ALM light flicker red
Interior communicat ion failure| (t=1S)| RUN/ALM light flicker red
Voltage sampling anomaly protection| (t=1S)| RUN/ALM light stays red
Current sampling fault| (t=1S)| RUN/ALM light stays red
Main circuit fault| (t=1S)| RUN/ALM light stays red
Download
Manual
http://oss.growatt.com:80/common/knowledgeShareH5No?lang=en&type=63
Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park,
Hangcheng Ave, Bao’an District, Shenzhen, China
T +86 755 2747 1942
E service@ginverter.com
W www.ginverter.com
GR-UM-223-A-02