Growatt AT-5000ES Solar Inverter User Guide

October 27, 2023
Growatt

Growatt AT-5000ES Solar Inverter

Growatt-AT-5000ES-Solar-Inverter-product

Introduction

The auto-transformer(AT-S000ES) is used for backup power only, its input connects to the AC side of the inverter, for the purpose of providing the split phase power to the loads.

The AT-S000ES in the System

Growatt-AT-5000ES-Solar-Inverter-fig-1

As shown in the picture, the input side of AT-S000ES is connected to the output of the inverter, and the output side is connected to the critical load. There is a transformer in AT-S000ES, it can transfer 240V to 120V /240V split phase to provide the power to load.

Configuration

Model name AT- SOOOES
Input Rated Voltage 240/208V
Input Rated Frequency 50/60Hz
Input Rated Current 21A/24A
Load Rated Voltage 120/240V or 104/208V

(split phase)

Load Max. Continued Current (L-L)| 21A/24A
Load Max. Continued Current (L-N)| (21A/24A)2
Load Rated Power (L-L)| S000VA
Load Rated Balanced Power (L-N)| 2500VA
2
Load Max. Unbalanced Power (L-N)| 2500W
Cooling Concept| Natural
Ingress Protection| IP 20
Installation| Wall Mountable
Operation Ambient Temperature| -25°C~ +50°((-13 to+122°F)
Weight| 13.5kg/30Ib
Size| 3852101 OSmm/15.168.274.13in

General Information Parts List

Growatt-AT-5000ES-Solar-Inverter-fig-2

Part List

Item| Item Name| Qty| Item| Item Name| Qty


A

| AT-S000ES

(Auto-transformer)

| | ****

D

| ****

O -type terminal

| ****

2

B| User Manual| | E| Cold pressed| 6
C| Anchor Bolt| 2| | |

Tools

Growatt-AT-5000ES-Solar-Inverter-fig-4

NO. Description
Press terminal connector
2 Screwdriver
3 Knock explosion bolt
4 Drill holes on the wall

Wall Mount Installation

Growatt-AT-5000ES-Solar-Inverter-fig-5

  • A) Please reserve the space of 300mm (11.8in) from AT-SO0OES.
  • B) Place the ruler horizontally on the wall and mark the position of 2 holes for screws.
  • C) Remove the ruler and drill 2 holes were marked, Drill holes with cp10 drill Depth: at least 40mm (1.575in).
  • D) First knock the expansion pipe into the hole with a Rubber hammer and then place the AT-S0O0ES align with the marked position on the wall. Last, screw the self-tapping screwing into the expansion pipe.

Open the AT-5000ES

Growatt-AT-5000ES-Solar-Inverter-fig-6

As shown in the picture, please use the screwdriver to get out the 2 screws at the bottom of the AT-S000ES, then pull back to take out the bottom cover.

Wiring Connection

Wires Making

  1. The wires below are needed before installation.Growatt-AT-5000ES-Solar-Inverter-fig-7
    Cable description

    Cable| Type| Conductor Cross­ sectional Area Range| Source

Input power cable

|

1. Use cables that can withstand 90°C (194°F) or 105°C (221°F).

2. Three single-core outdoor copper cables (L, N, PE)

|

L, N: 10-6AWG PE: 10-6AWG

|

Purchased by customer

Output power cable

|

1. Use cables that can withstand 90°C (194°F) or 105°C (221°F).

2. use four single-core outdoor copper cables (L1, N, L2, PE).

|

L, N, L2: 10-6AWG PE: 10-6AWG

| Purchased by customer

  1. Use the diagonal plier to trip 15mm of insulation from one side of the 1 0AWG wires. Use the diagonal plier to trip one side of the GND wire about 7mm.Growatt-AT-5000ES-Solar-Inverter-fig-8
  2. There are two types of wire that need to be machined, please check ref to 9.1 wired diagram. The following two type of wires are show below (type1 is used for power line connection, type2 is used to ground connection):Growatt-AT-5000ES-Solar-Inverter-fig-9

Input Wires Connection

Growatt-AT-5000ES-Solar-Inverter-fig-10

Use the screwdriver to remove the nut on the input terminal strip, and the red 1 0AWG short wire ends were inserted into the input port L, and the black 1 0AWG short wire ends were inserted into the input port N. Use a screwdriver to lock the ground wire on the earth bus bar.

Output Wires Connection

Growatt-AT-5000ES-Solar-Inverter-fig-11

Use the screwdriver to remove the nut on the output terminal strip, and the red 1 0AWG short wire ends were inserted into the output ports L 1 and L2, The Black 1 0AWG short wire ends were inserted into the output port N. Use a screwdriver to lock the ground wire on the earth bus bar.

Checking
Please make sure that all wiring in the AT-5000ES is tightened.

AT-5000ES USA e methods
After connecting the AT-5000ES internal wire, close the cover and the input end of the AT-5000ES is connected with the output of the inverter, the output end of the AT-5000ES access load. Run the system, and loaded into normal operation.

Troubleshooting

Please turn off the inverter and open the AT-5000ES cover, and check the input wiring and the output wiring properly.

Caution

  1. Please use the equipment within the scope of the specification. Excessive current or voltage may cause device damage.
  2. To avoid personal injury due to energy hazards, remove wristwatches and jewelry when repairing. Use tools with insulated handles.
  3. The rated power of the secondary side L 1-N and L2-N could be up to 5KVA respectively, and the power difference between the two split phases can not exceed 2.5KW.
  4. Don’t connect N of AT-5000ES output together with N of input.
  5. Don t connect N of AT-5000ES to PE of AT-5000ES or PE of the grid.
  6. Repair is to be performed only by qualified technical personnel authorized by the manufacturer.
  7. The rated balanced power(L-N)means the Load of L 1-N and L2-N is equal.
  8. The rated unbalanced power(L-N)means the load of L 1-N and L2-N is different.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals