AIRZONE AZCE8CB1MOT 3.0 Main Control Board
Product Information
Specifications:
- Power: Externally powered at 110 / 230 Vac
- Stand-by Consumption: 2.10 W (110 Vac), 3.12 W (230 Vac)
- Current: 250 mA
- Communication Protocol: Airzone
- Frequency: 868.12 MHz (EU), 915.2 MHz (EEUU, Canada, Australia, Nueva Zelanda)
- Transmission Power: 0 dBm
- Max Distance: 40 m
- Storage Weight: 554 g
- Bluetooth Protocol: Bluetooth v5.0 and BLE specification
- Bluetooth Class: Class-1, class-2 and class-3 transmitter
Product Usage Instructions
Mounting:
To mount the Airzone Flexa 3.0 system, follow the assembly instructions below:
- Identify the mounting location on the wall where you want to install the main control board.
- Use appropriate screws and wall anchors to securely mount the board on the wall.
- Ensure that the board is mounted at a suitable height and in a convenient location for easy access.
Wiring:
Proper wiring is essential for the functioning of the Airzone Flexa 3.0 system. Follow the wiring instructions below:
- Connect the power supply to the main control board using a 110/230 Vac power source.
- Connect the shielded twisted pair cables (AZ1, AZ2, AZ3, IU, CAN) to their respective terminals on the board.
- Connect the necessary cables for ON/OFF module, AI1, DI1, O1, O2, and M1…M8 to their respective terminals.
- Ensure all connections are secure and properly insulated.
Configuration:
To configure the Airzone Flexa 3.0 system, follow the steps below:
- Refer to the user manual or visit myzone.airzone.es for detailed configuration instructions.
- Follow the provided guidelines to set up and customize the system according to your preferences.
- Ensure that all settings are saved and applied for proper system functionality.
Frequently Asked Questions
Q: Where can I find more information about Airzone products?
A: For further information about our products, please visit myzone.airzone.es.
Q: What is the power consumption in stand-by mode?
A: The stand-by consumption is 2.10 W (110 Vac) and 3.12 W (230 Vac).
Q: What is the maximum transmission distance for the Airzone Flexa 3.0 system?
A: The maximum transmission distance in open space is 40 meters.
AIRZONE FLEXA 3.0 MAIN CONTROL BOARD
Configurable electronic board that controls the system through wired and wireless devices. Externally powered at 110 / 230 Vac. Wall mounted.
Functionalities
- Control and management of the thermostats (up to 8 zones).
- Power outputs for motorized elements.
- Relay outlet configurable as CMV (Controlled Mechanical Ventilation) or boiler.
- Control gateway management.
- Communication with units of integral control of the installation.
- Communications with other external control systems through integration bus.
- For further information about our products, go to myzone.airzone.es
TECHNICAL SPECS
N L|
---|---
V máx.| 110/230 Vac
I máx.| 250 mA
Frequency| 60/50 Hz
Stand-by consumption
/ Consumo em stand-by
| 2.10 W (110 Vac)
3.12 W (230 Vac)
Protección sobre corriente módulo
/ Module over-current protection
| ****
250 mA
AZ1 – AZ2 – AZ3 – IU – CAN|
Cable apantallado
| 2 x 0,22 + 2 x 0,5
mm2
| 12 V
DM1|
Cable apantallado y trenzado
| 2 x 0,22 + 2 x 0,5
mm2
Communications protocol
| MODBUS RS-485
Par – 19200 bps
P3|
Communications protocol
| ****
Airzone
Frequency
| 868.12 MHz (EU)
915.2 MHz (EEUU, Canada, Australia, Nueva Zelanda)
Radiation power| 0 dBm
Maximum distance in open
| 40 m
|
| M1 … M8|
---|---|---
Nº of outputs| 8
Maximum number of outputs| 2
| V max| 12 V
| I max| 150 mA
| O1 – O2|
Nº of relays| 2
| V max| 250 Vac / 24 V
| I max| 12 A
Operating temperaturas
| Storage
| -20 … 70 ºC
Operation| 0 … 50ºC
Mechanical aspects
Protection class| IP 21
| Weight| 554 g
| Bluetooth|
protocol| Bluetooth v5.0 and BLE specificaction
Class| Class-1, class-2 and class-3 transmitter
ASSEMBLY
DEVICE ELEMENTS
Description
AZ1/2/3| / Airzone connection bus
P3| Wireless module
SW1| SW1
DM| Automation bus
CAN| CAN connection bus
IU| AC unit bus
M1…M8| Actuator outputs
DI1| Alarm input (normally close)
AI1| Temperature probe
O1| AC start-stop relay
O2| CMV/Boiler
N L| Power
ON/OFF| Contact on/off (optional))
SELF- DIAGNOSIS
Nº | Meaning |
---|
D1
| Data reception from automation bus
| Blinking
| Verde Green
Verde
D2
| Data transmission from automation bus
| Blinking
| Rojo Red
Vermelho
D3
| Main control board activity| Blinking| Verde
Green Verde
D4
| Data transmission from connection bus
| Blinking
| Rojo Red
Vermelho
D5
| Data reception from connection bus
| Blinking| Verde
Green Verde
D6
| AC unit On/Off
| Switches
| Verde Green
Verde
D7
| CMV/Boiler| Switches| Verde
Green Verde
D8
| Data transmission from AC unit bus
| Blinking| Rojo Red
Vermelho
D9
| Data reception from AC unit bus
| Blinking| Verde
Green Verde
D10
| Wireless data packets reception
| Switches
| Verde Green
Verde
D11
| Main control board power
| Fixe
| Rojo Red
Vermelho
D18
| Associated element|
Fixed
| Verde
Green Verde
D19
| Association channel: active
| Fixe
| Rojo Red
Vermelho
D80
| Data transmission from CAN| Blinking| Rojo Red
Vermelho
D79
| Data reception from CAN
| Blinking
| Verde Green
Verde
A
| Open dampers
| On
| Verde Green
Verde
Close dampers| o On
| Rojo Red
Vermelho
CONNECTION
Do not connect the “-“ pole to the “+” terminal. It may damage the device.
EU.BAC
Type | Airzone AZCE8CB1MOT |
---|---|
Licence | 22184 |
Application
| Variable air volume system (without h/c coil)
Heating| Cooling
Control accuracy (K)| 0.2| 0.3