SmartGen CMM366-4G Cloud Monitoring Communication Module User Manual

June 16, 2024
SmartGen

CMM366-4G
CLOUD MONITORING COMMUNICATION MODULE
USER MANUALSmartGen CMM366 4G Cloud Monitoring Communication Module -
cover SMARGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
Registered trademark
No. 28 Xuemei Street, Zhengzhou, Henan, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: sales@smartgen.cn

CMM366-4G Cloud Monitoring Communication Module

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Note
01-09-17 1 Original release.
20-04-22 1.1 Update the manual format, information and logo of SmartGen.
09-08-23 1.2 Update description of RS485 access to 120Ω resistor.

OVERVIEW

CMM366-4G Cloud Monitoring Communication Module is 4G (fits all kinds of networks) wireless network communication protocol switch module, which can achieve gen-set (with SCI) connect to Internet. The module gains gen-set data via RS485 port, USB port, LINK port or RS232 port of gen-set  controller modules of international first-class brands including SmartGen, DeepSea, ComAp, etc. Then it transmits the data to corresponding cloud server via 4G wireless network for achieving user’s real-time monitoring to running status and searching of running records via APP (IOS or Android) and PC terminal devices.
CMM366-4G module has already integrated protocols of mainstream gen-set control module. It not only can achieve gen-set monitoring but also can insert some digital alarm input/output signals to achieve monitoring of generator room entrance guard, guard against theft and fire facilities. This module, which has GPS locate function, can upload gained longitude, latitude and elevation to corresponding cloud server.

PERFORMANCE AND CHARACTERISTICS

  • Connect to cloud server via 4G wireless network, one to one monitoring;
  • Multiple ports for communication with gen-set control module: RS485, RS232, LINK and USB (Host); can monitor great majority gen-set control modules of international first-class brands;
  • Widely power supply: DC (8~35)V, can direct use gen-set build-in battery;
  • With ARM-based 32-bit SCM, high integration of hardware and strong programming ability;
  • Include with GPS locate function to achieve gain location information and locate gen-set;
  • Take JSON network data communication protocol, upload real-time data variation and take compression algorithm to vastly reduce network flow at the same time;
  • Users can set up history data upload rest to upload monitoring data to server (history data can be analyzed);
  • When alarm occurs it can upload data to server immediately;
  • 2 configurable digital input ports which can receive external alarm signal;
  • 1 configurable relay output port which can output various of alarm signal;
  • Power and multiple communication status indicators on front panel that working status is clear at a glance;
  • Lamp test function;
  • Parameter adjust function: users can adjust parameters via USB port;
  • Take standard π-type 35mm guide-rail installation or screw-fixed installation that the module can be installed in the gen-set control box;
  • Modular design, self extinguishing ABS plastic shell, light weight, compact structure with easy installation.

SPECIFICATION

Table 2 Technical Parameters

Items Contents
Operating Voltage DC 8.0V~35.0V, continuous power supply.
Power Consumption Standby: ≤2W

Working: ≤5W
Auxiliary Input| Digital Input, connect (B-) is active.
Auxiliary Output| 1A  DC30V  Volts free output
USB Host| A-type USB female port
RS485| Isolated type
RS232| General type
LINK| SmartGen exclusive port
USB Device| B-type USB female port
GPRS Port| Standard SMA port (female), SMA port (male) for antenna.
GPS Port| Standard SMA port (female), SMA port (male) for antenna, active antenna.
Wireless Network| LTE-TDD/LTE-FDD/HSPA+/TD-SCDMA/EVDO GSM/GPRS/EDGE
Case Dimensions| 73mmx105mmx33mm
Working Temperature| (-25~+70)°C
Storage Temperature| (-25~+70)°C
Working Humidity| (20~93)%RH
Weight| 0.15kg

PANEL AND TERMINAL DESCRIPTION

4.1 PANEL INDICATOR AND BUTTONS

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 1

Fig.1 CMM366-4G Panel Drawing

Table 3 Indicator Description

Icon Note
POWER/ALARM Green LED Light: Power supply normal indicator

Red LED Light: Common alarm indicator
RS485(Red)| Normally Extinguish: RS485 disabled
Normally Light: Communication fail
Blink: Communication normal
USB(Red)| Normally Extinguish: USB(Host) disabled
Normally Light: Communication fail
Blink: Communication normal
GPS(Red)| Normally Extinguish: GPS disabled
Normally Light: GPS not gained satellite signal
Blink: GPS gained satellite signal
LINK(Red)| Normally Extinguish: Disabled
Normally Light: Communication fail
Blink: Communication normal
RS232(Red)| Normally Extinguish: RS232 disabled
Normally Light: Communication fail
Blink: Communication normal
GPRS/4G(Red)| Extinguish: CMM366-4G login with server unsuccessfully
Light: Login with server successfully
Blink: Real-time communication normal

Lamp test/Rest:
Press this button for 1s, all the LEDs are illuminated; hold and press for 10s, reset the module to default and all the LEDs blink for 3 times.
NOTE: After reset the module, set up the parameters via PC software is recommended. Please operate cautiously.

4.2 GPRS
Connect GPRS antenna to GPRS/4G port.
Antenna: 50Ω/SMA female.
4.3 GPS
GPS enabled, connect GPS antenna to CMM366-4G.
NOTE: GPS antenna needs to be placed to open outdoors, otherwise location information may not accurate or cannot be gained.
Antenna: 50Ω/SMA female, active antenna.

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 1 Fig.2 CMM366-4G Antenna Connection

NOTE: GPRS antenna and GPS antenna cannot be connected reversely.

4.4 SIM INSTALLATION
Insert 4G, 3G or 2G SIM card. CMM366-4G will connect to servers via wireless mobile network.

NOTE: All 4G wireless networks are supported. Use standard SIM card (25mmX15mm); if GPS indicator and GPRS indicator blink in the same time, which means SIM card hasn’t been inserted or bad contacts.
After removing the head cover, the installation steps are as below:

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 2 Fig.3 SIM Card Installation

4.5 RS485
Receive gen-set data information by RS485 port connecting with gen-set controller RS485 port.
If communication is abnormal, 120Ω terminal resistance is recommonded. If 120Ω resistor is required, please short connect A(+) of RS485 port on CMM366-4G to 120Ω.

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 3

Fig.4 RS485 ConnectionSmartGen CMM366 4G Cloud Monitoring Communication
Module - PANEL AND TERMINAL DESCRIPTION 4 Fig.5 RS485 Access to 120Ω Resistor

4.6 RS232
Receive genset data information by RS232 port connecting with gen-set controller RS232 port.

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 5 Fig.6 RS232 Connection

4.7 LINK
Receive genset data information by LINK port connecting with gen-set controller LINK port.
SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 6 Fig.7 LINK Connection

4.8 USB HOST
Receive genset data information by A-type USB mother port connecting with gen- set controller USB port.

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 7 Fig.8 USB Host Connection

4.9 USB DEVICE
Set up all the parameters and view CMM366-4G ID&Login password by CMM366 USB port connecting with PC USB disk port.

SmartGen CMM366 4G Cloud Monitoring Communication Module - PANEL AND
TERMINAL DESCRIPTION 8 Fig.9 USB and PC Configuration Connection

4.10 TERMINAL

Table 4 Terminal Descritption

No. Function Cable Size Note
1 B- 1.0mm2 Connected with negative of starter battery.
2 B+ 1.0mm2 Connected with positive of starter battery. 3A fuse is

recommended.
3| Aux. Input 1| 1.0mm2| Active when connect to B-.
4| Aux. Input 2| 1.0mm2| Active when connect to B-.
5| Aux. Output| Normally Open| 1.0mm2| Normally open outputs, rated lA DC30V.
6| Common| 1.0mm2
7| Normally Close| 1.0mm2
8| RS485 B(-)| 0.5mm2| If 1200 is used, please short connect A (+) with 1200.
9| RS485 A(+)| 0.5mm2
10| 1200| 0.5mm2
11| RS232 RX| 0.5mm2| RS232 port.
12| RS232 TX| 0.5mm2
13| RS232 GND| 0.5mm2

PROGRAMMABLE PARAMETERS

5.1 CONTENTS AND SCOPES OF PARAMETERS
Table 5 Parameter Configuration

No. Items Parameters Defaults Description

Gateway
1| Site Name| | 20 Chinese characters, letters or numbers
2| Server URL| | cm.smangen.com.cn 40 characters
3| Server Port| (65535)| 81
4| Security Code| | 123456                          16 characters
GPS
1| GPS Enabled| (0-1)| 1| 0. Manual Input                    1: GPS Location
2| Longitude| (-180-180)| 0.000000| GPS location, altitude
3| Latitude| (-90-90)
| 0.000000
4| Altitude| (-9999.9-9999.9)| 100.0m
GSM
1| GSM Enabled| (0-1)| 1| Cr.Disabiect 1:Enabled
2| GPRS Password| Reserved| |
3| SMS Center Number| Reserved| |
4| PIN Enabled| (0-1)| 0| 0 Disabled. 1:Enabled
5| APN| | 40 characters|
6| SMS Enabled| (0-1)| 0| tr. Chinese; 1:English
7| SMS  Language Alarm| (0-1)| 0|
8| Telephone Number| Max. 20 numbers| | Phone number need to be added area code, such as China 8613666666666.
Cloud Server
1| Auto Gain Communication Port| (0-1)| 1| 0:Disabled; 1:Enabled
2| Module ID| (1-254)| 1| Module ID
3| Communication Port| (0-4)| 2| 0: Disabled 1: LINK
2 RS485
3:RS232
4:USB
4| Baud Rate| (0-2)| 0| 0: 96001A/s
1: 19200bit/s 2:115200 bit/s
5| Location Information| (0-1)| 1| 0: Manual input location info lo
1: Use GPS to gain location
6| Longitude| (-180.180)| 0.000000| Manually set module location and elevation.
7| Latitude| (-9090)
| 0.000000
8| Altitude| (-9999.9-9999.9)| 100.0|
9| Gen-set Model| | HGM6110| See: Form4
10| Module Name| | Module Names(20 Chinese characters, letters or numbers)
11| Debugger Name| 20 Chinese characters, letters or numbers
12| Phone Number| 20 Chinese characters, letters or numbers
13| Installation Date| 20 Chinese characters, letters or numbers
14| Historical Upload Interval| (0-3600)s| 0| History data upload rest.
Note: No upload when it is Os
15| Time Zone| (-12-12)| 8| Time Zone
16| Live Data Uploaded Interval| (1-20)s| 5| Interval time of uploading data.
Module Configuration Information
1| Module Type| (0-5)| 1| O:AMF module
1: Single-unit self-starting module
2: Single-single parallel module
3: Mains-genset parallel module
4: Mains-bus parallel module
5: Bus-bus parallel module
Note: The parameter will auto change according to gen-set type.
2| Rated Speed| (0-6000)t/min| 1500| Rated Speed
3| AC Supply| (0-3)| 0| a 3P4W; 1: 3P3W: 2: 2P3W. 3: 1P2W
4| Rated Voltage| (30-30000)V| 230| Rated Volt
5| Rated Frequency| (10-600)Hz| 50| Rated Freq
6| Rated Current| (5-6000)A| 500| Rated Current
7| Rated Power| (0-6000)kW| 276| Rated Power
8| Description 1| | Custom Description (20 Chinese characters, letters or numbers)
9| Description 2| | Custom Description (20 Chinese characters, letters or numbers)
10| Description 3| | Custom Description (20 Chinese characters, letters or numbers)
11| Description 4| | Custom Description (20 Chinese characters, letters or numbers)
12| Description 5| | Custom Description (20 Chinese characters, letters or numbers)
Digital Input
Digital Input 1
1| Options| (0-9)| 0| Default: Not used
2| Activate Type| (0-1)| 0| 0: Close to activate
1: Open to activate
See: Table6
3| Delay| (0-20.0)| 0.0| Action delay
Digital Input 2
3| Options| (0-9)| 1| Default: Lamp test
4| Activate Type| (0-1)| 0| 0: Close to activate
1: Open to activate
See: Table6
5| Delay| (0-20.0)| 0.0| Action delay
Digital Output
1| Options| (0-14)| 0| Default: Not used
See: Table7

Table 6 Definition Content of Inputs

No. Item Description
0 Not Used Not used.
1 Lamp Test All the indicators are illuminated when input is active.
2 Remote Control InhibitedAccess Alarm Input Cloud start/stop control is

prohibited when input is active.
3| Fire Alarm Input| Access alarm is uploaded to server when input is active.
4| Alarm Input| Fire alarm is uploaded to server when input is active.
5| Reserved| External alarm is uploaded to server when input is active.
6| Reserved|
7| Reserved|
8| Factory Test Mode| It is only used for factory hardware port test when active.

Table 7 Definition Content of Outputs

No. Item Description
0 Not used Description
1 Digital Input 1 Active Output port won’t output when this item is

selected.
2| Digital Input 2 Active| Output when auxiliary input 1 is active.
3| RS485 Communication Failure| Output when auxiliary input 2 is active.
4| Network Communication Failure| RS485 communication fails.
5| LINK Communication Failure| Network communication fails.
6| RS232 Communication Failure| LINK communication fails.
7| Common Alarm| RS232 communication fails.
8| Remote Control Output| Output when there is an alarm.
9| Reserved| Send remote control commands via cloud platform with fixed output delay 20s.
10| Reserved|
11| Reserved|
12| Reserved|
13| Reserved|
14| Reserved|

Table 8 Genset Module Type

Manufachrers Type Note
SmartGen
liGM6110/HGM6110CAN Genset auto-start module
HGM6120/HGM6120CAN AMF module
HGM7x10 Genset auto-start module
IIGM7x20 AMF module
HGM410 Genset auto-start module
FIGM420 AMF module
IIGM9120 AMF module
HGM9210 Genset auto-start module
HGM9220 AMF module
HGM9310 Genset auto-start module
HGM9320 AMF module
HGM9410 Genset auto-start module
FiGM9420 AMF module
HGM9510 Genset parallel module
HGM9520 Mains-genset parallel module
HGM9530 Genset parallel module
HGM9540 Mains-genset parallel module
HGM9560 Mains-bus parallel module
FiGM9580 Bus-bus parallel module
HGM9610 Genset auto-start module
HGM9620 AMF module
HGM4010N Genset auto-start module
HGM4020N AMF module
HGM1790N Genset auto-start module
TC1.0 AMF module
TC2.0 AMF module
TC3.0 Genset parallel module
ALC708 Genset auto-start module
ZX9320 AMF module
HSC943 Genset auto-start module
DeepSea DSE7110MKII Genset auto-start module
DSE7120MKII AMF module
DSE7210 Genset auto-start module
DSE7220 AMF module
DSE7310 Genset auto-start module
DSE7320 AMF module
DSE7410 Genset auto-start module
DSE7420 AMF module
DSE7450 Genset auto-start module
DSE8610 Genset parallel module
DSE8620 Mains-genset parallel module
ComAp MRS10 Ⅱ Genset auto-start module
MRS16 Ⅱ Genset auto-start module
AMF25 Ⅱ AMF module
IGNT Genset parallel module
MINT Genset parallel module
SPTM Mains-genset parallel module
MC-NT Mains-bus parallel module
Harsen GU620A Genset auto-start module
GU621A AMF module
GU630A Genset auto-start module
GU631A AMF module
GU620A-00 Genset auto-start module
GU621A-00 AMF module
GU630A-00 Genset auto-start module
GU631A-00 AMF module
GU320A Genset auto-start module
GU320B Genset auto-start module

5.2 PC CONFIGURATION INTERFACE
The USB port of CMM366-4G communication module connects PC port to configure the parameters.

SmartGen CMM366 4G Cloud Monitoring Communication Module - PROGRAMMABLE
PARAMETERS 1 Fig.10 Gateway ConfigurationSmartGen CMM366 4G Cloud Monitoring
Communication Module - PROGRAMMABLE PARAMETERS 2 Fig.11 Cloud Server ConfigurationSmartGen CMM366 4G Cloud Monitoring Communication Module -
PROGRAMMABLE PARAMETERS 3 Fig.12 Module Monitoring Interface

SMS FUNCTION AND REMOTE CONTROL

6.1 SMS ALARM
When controller detects alarm, it will send short message to phone automatically.
NOTE: SMS alarm function only suit for SmartGen HGM7000 series and HGM9000 series controllers.
NOTE: All alarms about shutdown, trip and stop and trip alarms will be sent to the pre-set phone. Warnings are sent to the phone according to the pre-set.

6.2 SMS CONTROL
Users send order message to the module, then controller will make actions according to this SMS order and pass back corresponding operations information. Controllers only execute  the orders by pre-set.

Table 9 SMS Orders List

No. SMS Orders Pass Back Information Description
1 SMS GENSET GENSET ALARM When gen-set is stopping alarm
SYSTEMIN STOP MODE GENSET AT REST At rest status in stop mode
SYSTEM IN MANUAL MODE GENSET AT REST At  rest  status  in manual mode
SYSTEM IN TEST MODE GENSET AT REST At rest status in test mode
SYSTEM IN AUTO MODE GENSET AT REST At rest status in auto mode
SYSTEMIN STOP MODE GENSET IS RUNNING Running   status   in  stop mode
SYSTEMIN MANUAL MODE GENSET IS RUNNING Running status in manual mode
SYSTEMIN TEST MODE GENSET IS RUNNING Running status in test mode
SYSTEMIN AUTO MODE GENSET IS  RUNNING Running  status  in  auto mode
2 SMS START GENSET ALARM Generator    is    shutdown alarm or trip alarm

Start gen-set
STOP MODE NOT START| Cannot start in stop mode
SMS START OK| Start in manual/test  mode
AUTO MODE NOT START| Cannot start in auto mode
3| SMS     STOP MODE| SMS STOP OK| Set as stop mode
4| SMS MANUAL MODE| SMS MANUAL MODE OK| Set as manual mode
5| SMS TEST MODE| SMS TEST MODE OK| Set as test mode
6| SMS AUTO MODE| SMS AUTO MODE OK| Set as auto mode
7| SMS DETAIL| Pass back information can be set via controller software.| Gets details information of gen-set

NOTE: When sending orders, users need to follow SMS orders in above form and all the letters must be capital.
NOTE: Pass back information from SMS DETAIL including: working mode, mains voltage, generator voltage, load current, mains frequency, generator frequency, active power, apparent power, power factor, battery voltage, D+ voltage, water temperature, oil pressure, oil level, engine speed, total running time, gen-set status, and alarm status.

SYSTEM DIAGRAM

One CMM366-4G module connects with one gen-set monitor module. It can be connected via RS485 port, LINK port, RS232 port or USB port.

SmartGen CMM366 4G Cloud Monitoring Communication Module - SYSTEM DIAGRAM
1 Fig.13 CMM366 System Diagram

CASE DIMENSION AND INSTALLATION

2 ways for installation: 35mm guide rail in box or screw (M4) installation as below:

SmartGen CMM366 4G Cloud Monitoring Communication Module - CASE DIMENSION
AND INSTALLATION 1 Fig.14 CMM366-4G Case Dimension Fig.15 CMM366-4G Guide Rail Installation Fig.16 CMM366-4G Screw Installation

FAULT FINDING

Table 10 Fault Finding

Symptoms Possible Solutions

Controller No Response with
Power| Check power voltage:
Check controller connection wirings.
GPRS/4G Indicator Not Light| Check SIM card is inserted or not;
Check GPRS antenna is connected or not.
GPS Not Gained Location| Check GPS parameters are enabled or not
Check GPS antenna is connected or not and placed outdoor or not.
RS485 Communication Abnormal| Check connections:
Check RS485 port is enabled or not;
Check settings of gen-set ID and baud rate are correct or not. Check RS485’s connect ions of A and B is reverse connect or not.
RS232 Communication Abnormal| Check connections;
Check RS232 port is enabled or not;
Check settings of gen-set ID and baud rate are correct or not.
LINK Communication Abnormal| Check connections;
Check LINK port is enabled or not:
Check settings of gen-set ID and baud rate are correct or not.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals