nVent CADDY TSR122 038RL Rod Lock Telescoping Strut Owner’s Manual

June 16, 2024
nVent Caddy

nVent CADDY TSR122 038RL Rod Lock Telescoping Strut

nVent-CADDY-TSR122-038RL-Rod-Lock-Telescoping-Strut-
product

Product Information

Specifications

  • Catalog Number: TSR122038RL
  • Material: Steel
  • Finish: Pre-galvanized
  • Rod Size (RS): 3/8″
  • Thickness (T): 0.040″
  • A: 1 5/8″
  • B: 7/8″
  • C: 1 3/8″
  • Static Load 1 (F1): 300 lb
  • Static Load 2 (F2): 200 lb

Product Usage Instructions

Step 1: Preparing the Installation Area
Before installing the NVENT CADDY Rod Lock Telescoping Strut Replacement, ensure that the installation area is clean and free from any debris or obstructions. Step 2: Mounting the Rod Lock Telescoping Strut

  1. Identify the appropriate location for the strut installation.
  2. Using suitable mounting hardware (not included), secure the strut in place.
  3. Make sure the strut is level and securely fastened.

Step 3: Adjusting the Telescoping Strut Length
The NVENT CADDY Rod Lock Telescoping Strut Replacement allows for adjustable length to accommodate different installation requirements.

  1. Loosen the locking mechanism on the strut.
  2. Extend or retract the strut to the desired length.
  3. Tighten the locking mechanism to secure the strut in place.

Step 4: Load Capacity
The NVENT CADDY Rod Lock Telescoping Strut Replacement has two static load capacities:

  • Static Load 1 (F1): Suitable for distributed loads between 12 – 20 inches (300 – 500 mm) or point loads between 12 – 16 inches (300 – 400 mm).
  • Static Load 2 (F2): Suitable for point loads between 16 – 20 inches (400 – 500 mm).

Ensure that the load does not exceed the specified capacity for safe usage.

FEATURES

  • Easy “push-to-install” design allows installers to simply push the threaded rod through the mounting hole, instantly holding it in position
  • Telescopes to the desired length and are locked in place by snapping closed a spring retainer clip
  • The standard strut profile runs the entire length of the part, allowing most standard fittings to be placed anywhere between the rods
  • Allows installers to prefabricate complex assemblies and quickly lift and lock them into place
  • The lock nut can be finger-tightened, locking the rod in place
  • Allows for the quick creation, installation, and adjustment of multi-level trapeze assemblies
  • Captive threaded nuts enable fastening to the threaded rod supports without loose parts
  • Integrated ruler displays space between hanger rods in inches and centimeters
  • Supports up to seven 2″ (50 DN) conduits, six 2″ (50 DN) water-filled pipes at 10′ (3 m) spacing, or up to 18″ (450 mm) cable tray
  • Conduit can be supported on the top and bottom, eliminating the need for double-sided strut
  • Conduit and pipe can be placed directly on the strut profile, saving vertical space in buildings with limited room for installation

SPECIFICATIONS

Catalog Number

|

Material

|

Finish

|

Rod Size(RS)

|

Thickne ss(T)

|

A

|

B

|

C

|

D

|

E

| Static Load 1(F1)| Static Load 2(F2)
---|---|---|---|---|---|---|---|---|---|---|---
TSR122 038RL|

Steel

| Pregalva nized|

3/8″

|

0.040″

| 12 1/2″

– 20″

| 14″ – 21

1/2″

|

1 5/8″

|

7/8″

|

1 3/8″

|

300 lb

|

200 lb

ADDITIONAL PRODUCT DETAILS

Static Load 1 represents a distributed load for 12″ – 20″ (300 – 500 mm) installations and a point load for 12″ – 16″ (300 – 400 mm) installations. Static Load 2 represents a point load for 16″ – 20″ (400 – 500 mm) installations.

DIAGRAMS

nVent-CADDY-TSR122-038RL-Rod-Lock-Telescoping-Strut-
fig-1

WARNING

nVent products shall be installed and used only as indicated in nVent’s product instruction sheets and training materials. Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.

FAQ

  • Q: Where can I find nVent’s product instruction sheets?
    A: Instruction sheets are available at www.nvent.com and from your nVent customer service representative.

  • Q: What should I do if I encounter issues during installation or usage?
    A: If you experience any difficulties or have questions regarding installation or usage, please contact nVent customer service for assistance. Contact information for different regions:

    • Europe Netherlands: +31 800-0200135
    • Europe France: +33 800 901 793
    • Europe Germany: 800 1890272
    • Other Countries: +31 13 5835404
    • APAC Shanghai: +86 21 2412 1618/19
    • APAC Sydney: +61 2 9751 8500
  • Q: Can I modify the product specifications?
    A: No, nVent reserves the right to change specifications without notice. Modifying the product may result in voiding your warranty and compromising its functionality.

Contact Information

North America

  • +1.800.753.9221
  • Option 1 – Customer Care
  • Option 2 – Technical Support

Europe

  • Netherlands: +31 800-0200135
  • France: +33 800 901 793

Europe

  • Germany: 800 1890272
  • Other Countries: +31 13 5835404

APAC

  • Shanghai: + 86 21 2412 1618/19
  • Sydney: +61 2 9751 8500

Our powerful portfolio of brands:
nVent.com

  • CADDY
  • ERICO
  • HOFFMAN
  • RAYCHEM
  • SCHROFF
  • TRACER

© 2023 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.

nVent reserves the right to change specifications without notice.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

nVent Caddy User Manuals

Related Manuals