nVent CADDY PYRAMID H-Series Support System Instructions
- June 12, 2024
- nVent Caddy
Table of Contents
nVent CADDY PYRAMID H-Series Support System Instructions
INSTRUCTION SHEET
CADDY® PYRAMID H-Series Support System
H-Frame Supports
GLOBAL PART NUMBER | DESCRIPTION | MAX STATIC LOAD* |
---|---|---|
LBS | N | |
PHK | RPS FRB 12X12IN, FM, H | 1500 (750 per foot) |
PHKR | RPS FRB 12X12IN, RBR, H | 1500 (750 per foot) |
360420 | RPS FRB 314X314MM, FM, H | 1500 (750 per foot) |
360421 | RPS FRB 314X314MM, RBR, H | 1500 (750 per foot) |
*Strut framing must be provided and evaluated by end user to ensure it can support applied loads.
*Maximum recommended load at 5.22psi (36KPa) roof loading. Contact project or roofing engineer for maximum allowable load on individual project roofing system.
ERICO does not recommend the use of CADDY® PYRAMID H-Series Supports on sloped
rooftops with more than 1/12 pitch unless there is a structural attachment of
the supports to the roof structure.
WARNING:
- ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICO customer service representative.
- ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
- All instructions must be completely followed to ensure proper and safe installation and performance.
- Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death.
- Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.
- All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any other purpose.
NOTE : All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted. The customer is responsible for:
a. Conformance to all governing codes.
b. The integrity of structures to which the products are attached,
including their capability of safely accepting the loads imposed, as evaluated
by a qualified engineer.
c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be
observed. Always use appropriate safety equipment such as eye protection, hard
hat, and gloves as appropriate to the application
Installation steps:
- Sweep off loose gravel, if gravel exists.
- Attach vertical strut members as shown.
- Strut must be installed all the way down.
- Level system as needed.
Configuration of pipe hanging
Configuration of duct mounting
Configuration of conduit/pipe supply
Configuration of Cable Tray
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com CFS441_B INSTRUCTION SHEET 3 OF 3 ©
2011, 2013 ERICO International Corporation.