SENECA R-32DIDO Profinet System

June 16, 2024
SENECA

SENECA R-32DIDO Profinet

Product Information

  • Specifications
    • Weight: 170 g
    • Enclosure: UL94-V0 self-extinguishing PC/ABS material, black
    • Insulation: 1500 Vac With integrated WEB Server
    • Digital Inputs: 32
    • Digital Outputs: 32
    • Counters: Yes
    • Ports: 1 Ethernet (R-32DIDO-1 model), 2 Ethernet (R-32DIDO-2 model), 1 RS485 port (only R-32DIDO-1/R-32DIDO-2 versions)
    • Power Supply: PWR AUX

Product Usage Instructions

  • Installation
    • Read the entire manual before starting any operation.
    • The module must only be used by qualified electricians.
    • Ensure that you have the necessary documentation available via the QR-CODE shown on page 1.
    • Take appropriate measures to prevent electrostatic discharges during any operation.
    • If the module needs repair, damaged parts should be replaced by the Manufacturer.
  • Connections
    • The module has the following ports:
    • ETH1 PORT1
    • ETH2 PORT2
    • PWR AUX
  • DIGITAL INPUT/OUTPUT
    • USB POWER SUPPLY
    • Connect the module to the appropriate devices using the provided terminal blocks and cables. Ensure that the connections are secure.
    • LED Indicators
    • The module has LED indicators on the front panel, which have the following meanings:
LED Meaning
PWR Device powered
IO1/IO32 Digital input/output active
OUT SUP STS (Status) Digital output OK (R-32DIDO-P version only)
FAIL Digital output in FAIL
RX (R-32DIDO version only) Reception of data packet completed on RS485
TX (R-32DIDO version only) Transmission of data packet completed on RS485
ETH TRF (Yellow) Packet transit on Ethernet port
ETH LNK (Green) The Ethernet port is connected (LINK)

Frequently Asked Questions (FAQ)

  • Q: Can I use the module without being a qualified electrician?
  • A: No, the module must only be used by qualified electricians.
  • Q: What should I do if the module needs repair?
  • A: If the module needs repair, damaged parts should be replaced by the Manufacturer. Contact the technical support at support@seneca.it. for assistance.
  • Q: How can I dispose of the product?
  • A: The product must be surrendered to a collection centre authorized to recycle electrical and electronic waste. Look for the appropriate symbol on the product or its packaging for guidance.
  • Q: Where can I find additional documentation for the module?
  • A: Additional documentation can be found via the QR-CODE shown on page 1 of the manual. For specific product information, you can contact sales@seneca.it.

PRELIMINARY WARNINGS

  • The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk.
  • The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment.
  • The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.SENECA-R-32DIDO-Profinet-FIG-1 \(9\)

MODULE LAYOUT

SENECA-R-32DIDO-Profinet-FIG-1 \(2\)

  • Weight: 170 g;
  • Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR On Device powered
Off Device not powered
IO1/IO32 On Digital input/output active
Off Digital input/output not active
OUT SUP On Digital inputs/outputs powered
Off Digital inputs/outputs not powered
STS (Status) On IP address set
Flashing Waiting for the IP address from the DHCP
COM (R-32DIDO-P version only) Off No Profinet communication
Flashing Profinet communication present
FAIL On Digital output in FAIL
Off Digital output OK
RX (R-32DIDO version only) On RS485 port wiring error
Flashing Reception of data packet completed on RS485
TX (R-32DIDO version only) Flashing Transmission of data packet completed on

RS485
ETH TRF (Yellow)| Flashing| Packet transit on Ethernet port
ETH LNK (Green)| Flashing| The Ethernet port is connected (LINK)
CERTIFICATIONS| https://www.seneca.it/products/r-32dido/doc/CE_declaration.
---|---
INSULATION|
---|---
POWER SUPPLY| Voltage: 10÷40Vdc; 19÷28Vac; 50÷65Hz; Absorption: 3W max; Dissipation: 6.5W max
ENVIRONMENTAL CONDITIONS| Operating temperature: from -25°C to +65°C Humidity: 10% ÷ 90% non-condensing.

Storage temperature: from -30°C to +85°C

Protection rating: IP20

CONFIGURATION| With an integrated WEB Server
CONNECTIONS/ COMMUNICATION PORTS| 3.5 mm pitch terminal block, 1.5 mm2 max cable section 1 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 (R-32DIDO-1 model) 2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 (R-32DIDO-2 model) 1 RS485 port on terminals 23-24-25 (only R-32DIDO-1/ R-32DIDO-2 versions)
DIGITAL INPUTS| Number of channels: 32; Voltage: Threshold ON: >9V; Threshold OFF: < 4 V; Vmax: 24 V; Impedance 9kΩ Individually configurable
DIGITAL OUTPUTS| Number of channels: 32, MOSFET, PNP; Max voltage/current: 0.2 A / 24 V Individually configurable
COUNTERS:| Number of counters: 32 at 32-bit, maximum speed: 50 Hz

ELECTRICAL CONNECTIONS

CAUTION: The upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs.

To meet the electromagnetic immunity requirements:

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  • separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).SENECA-R-32DIDO-Profinet-FIG-1 \(5\)

CAUTION

  • The power supply must be sized according to the expected load at the outputs.
  • Terminals 18-64 and 19-65 can be connected to the same power supply.

CAUTION

  • *For correct instrument operation, power the I/Os via the I/O Ext Supply 1 and 2 terminals at the same time.

DAISY-CHAIN (R-32DIDO-2 / R-32DIDO-2-P ONLY)

CAUTION: IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES

  • Using the daisy-chain connection it is not necessary to use switches to connect the devices.
  • The following examples show the correct connections.SENECA-R-32DIDO-Profinet-FIG-1 \(6\)
  • There must be no loops in the Ethernet cabling, otherwise, the communication will not work.
  • The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.SENECA-R-32DIDO-Profinet-FIG-1 \(7\)
  • The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure.
  • If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible.
  • This function has a limited duration: the connection remains active for a few days, typically 4.
  • The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched-off module is less than 100m.

ETHERNET CONNECTION RULES

  • For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.
  • CAT6 for industrial environments.

FACTORY IP ADDRESS

  • The default module IP address is static: 192. 168. 90. 101

WEB SERVER

  • To access the maintenance Web Server with the 192.168.90.101 factory IP address
  • (Default user: admin; Default password: admin) http://192.168.90.101.

CAUTION: DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

DIP – SWITCH SETTINGS

WARNING: The DIP-switch settings are read-only at boot time. At each change, perform a restart.
DIP-SWITCH SW1: through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:

WARNING

  • DIP-SWITCHES are located on the back of the device.
  • To access the DIP-SWITCH it is necessary to remove the bottom of the instrument.
  • MI00596-0-

CONTACT INFORMATION

  • SENECA s.r.l.;
  • Via Austria,
  • 26 – 35127 – PADOVA – ITALY;
  • Tel. +39.049.8705359
  • Fax + 39.049.8706287

Technical support| support@seneca.it| Product information| sales@seneca.it
---|---|---|---