White-Rodgers 21M51U-843 120V Hot Surface Ignition Control Kit Instruction Manual

June 16, 2024
WHITE RODGERS

White-Rodgers logo 2

White-Rodgers logo

21M51U-843
Universal Integrated Two-Stage
120V Hot Surface Ignition Control Kit
INSTALLATION INSTRUCTIONS

21M51U-843 120V Hot Surface Ignition Control Kit

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

The 21M51U-843 is an aftermarket universal replacement control kit for two- stage furnace products with PSC blower and inducer motors.
This control replaces Goodman/Amana, Lennox/Armstong, Trane/American Standard, and York applications.
TWINNING: 21M51U-843 can be twinned. Both control boards must be from the same manufacturer for proper functionality.

Parts included:

  • 50M51-843 Integrated Furnace Control
  • 21D64-2 HotRod Universal Ignitor Kit (120V)
  • Trane Ignitor Mounting Bracket
  • 3 – Mounting Screws
  • 5 – Motor Lead Extensions
  • Installation Instructions

SPECIFICATIONS

ELECTRICAL RATINGS:
Input Voltage: 120 VAC, 60 Hz (Class II transformer required)
Max. Input Current @ 24 VAC: 800mA + MV
Relay & Triac Load Ratings:
Gas Valve Relays: 1.5 amps @ 24 VAC, 60 Hz
Ignitor: 4.0 amps @ 132 VAC, 60 Hz
Inducer Relays: 2.2 FLA – 3.5 LRA @ 120 VAC
Circulator Relays: 14.5 FLA – 25.0 LRA @ 120 VAC
Humidifier Load: 1.0 A max @ 120 VAC
Electronic Air Cleaner Load: 1.0 A max @ 120 VAC

Flame Current Requirements:
Minimum current to ensure flame detection: 0.3 µA DC
Measured with a DC microammeter in series with flame probe lead

Operating Temperature Range:
-40° to 175°F (-40 to 80°C)

Humidity Range:
5% to 93% relative humidity (non-condensing)
Gases Approved: Natural, Manufactured, Mixed, Liquid Petroleum, and LP Gas Air Mixtures are all approved for use.

CAUTION

| Risk of Electric Shock.
Disconnect electric power to system until installation is complete. Do not use on circuit exceeding  specified voltage. Higher voltage will damage control and could cause shock or fire hazard.
---|---
| This control is not intended for use in locations where it may come in contact with water.
| May cause flame rollout.
Shut off main gas to heating system until installation is complete.

INSTALLATION

MOUNTING AND WIRING
Refer to Typical System Wiring Diagram on page 3
NOTE: All wiring should be installed according to local and national electrical codes and ordinances.

  1. Disconnect electrical power and gas supply to unit, then remove unit access panel.

  2. Mark and disconnect all wires from the existing control, then remove the old control.

  3. Mount and new control board in the unit and reconnectall the wires.

  4. Verify Stage Delay, Heat Off Delay, Trial for Ignition, Heat On Delay, and Cool Off Delay settings by matching prior boards configuration or refer to Dipswitch Configuration section of instructions and original OEM install manual
    and wiring diagrams.

  5. If replacing 50A51 control, set Trial for Ignition for 7 seconds.

  6. Secure any wiring with the provided cable ties as necessary.

  7. Reinstall unit access panels and reconnect electric power and gas supply to the unit.

  8. Verify unit operation by placing thermostat in heating mode and initiating a call for heat by adjusting thermostat 5 degrees above room temperature.

NOTES:

  • Motor lead extensions are included to be used if the original wiring does not reach the control after mounting.
  • Lennox applications will require connection to the stand alone flame probe terminal.
  • The installer may have to modify existing ignitor hole to accommodate the larger 21D64-2 (ceramic diameter 0.394″)
  • When replacing Amana 50A51-225, Amana 50A51-235, and York 50A51-243, “CIRC INPUT” is a redundant line voltage connection which should be taped and tied off.

DIPSWITCH CONFIGURATION

White-Rodgers 21M51U-843 120V Hot Surface Ignition Control Kit - DIPSWITCH
CONFIGURATION

NOTES:

  • Cycle power after changes are made.
  • For best results, set dip switches to prior boards configuration or refer to original OEM install manual for further details.
  • Only use Stage W2 delay with single-stage thermostat.
  • AUTO mode is based on an algorithm method of energizing the second stage gas valve based on the recent average of the heating duty cycle.

WIRING DIAGRAM

White-Rodgers 21M51U-843 120V Hot Surface Ignition Control Kit - WIRING
DIAGRAM

OPERATION

HEAT MODE

White-Rodgers 21M51U-843 120V Hot Surface Ignition Control Kit - HEAT
MODE

COOL MODE

White-Rodgers 21M51U-843 120V Hot Surface Ignition Control Kit - COOL
MODE

FAN MODE

White-Rodgers 21M51U-843 120V Hot Surface Ignition Control Kit - FAN
MODE

TROUBLESHOOTING

Green LED Flash| Amber  LED Flash| Red LED Flash| Error/Condition| Comments/Troubleshooting
---|---|---|---|---
| | 1| Flame sensed when no flame should be present| Verify the gas valve is operating and shutting down properly. Flame in burner assemble should extinguish promptly at the end of the  cycle. Check orifices and gas pressure.
| | 2| Pressure switch stuck closed/ inducer error| Pressure switch stuck closed. Check switch function, verify inducer is turning off.
| | 3| 1st-stage pressure switch stuck  open/inducer error| Check pressure switch function and tubing. Verify inducer is turning on the pulling sufficient vacuum to engage switch.
| | 4| Open limit switch| Verify continuity through rollout switch circuit.
| | 5| Open rollout/open fuse detect| Verify continuity through rollout switch circuit, check fuse.
| | 6| 1st-stage pressure switch cycle lockout| If the first stage pressure switch cycles 5 times (open, closed) during one call for heat from the thermostat the control will lockout. Check pressure switch for fluttering, inconsistent closure or poor vacuum pressure.
| | 7| External lockout (retries)| Failure to sense flame is often caused by carbon deposits on the flame sensor, a disconnected or shorted flame sensor lead or a poorly grounded furnace. Carbon deposits can be cleaned with emery cloth. Verify sensor is not contacting

the burner and is located in a good position to sense flame. Check sensor lead for shorting and verify furnace is

grounded properly.

| | 8| External lockout (ignition recycles exceeded where flame is established and then lost)| Check items for exceeded retries listed above and verify valve is not dropping out allowing flame to be established and then lost.
| | 9| Grounding or Reversed polarity| Verify the control and furnace are properly grounded. Check and reverse polarity (primary) if incorrect.
| | 10| Control valve contacts energized with no call for heat| Verify valve is not receiving voltage from a short. If a valve wiring is correct and condition persists, replace control.
| | 11| Limit switch open – possible blower failure overheating limit| Possible blower failure, restricted air flow through appliance or duct work. Verify continuity through limit switch circuit and correct overheating cause.
| | 12| Ignitor contact failure| Fault code indicates the control ignitor contacts are not functioning properly. Replace control.
| | Solid| Internal fault condition| Control contacts for gas valve not operating or processor fault. Reset control. If condition persists replace control.
| | Rapid| Twinning error| Check wire connections. If condition persists, replace control.
| | 3 Double| 2nd-stage Pressure Switch Stuck Open/Inducer Error| Check pressure switch function and tubing. Verify inducer is turning on and pulling sufficient vacuum to engage switch.
| 1| | Normal Operation with call for first stage heat| Normal operation – first stage
| 2| | Normal Operation with call for second stage heat| Normal operation – second stage
| 3| | W2 present with no W1| Second stage call for heat on thermostat circuit with no call for first stage. Verify dip switches are set for two stage thermostat and check  thermostat first stage circuit. Configured for a multi- stage thermostat  the control will not initiate heating unless first stage call  from thermostat is received.
| 4| | Y present with no G call| Control will allow cooling to operate with only a “Y” signal from the thermostat but will also trigger this code. Verify thermostat is energizing both “Y” and “G” on call for cool. Check “G” terminal connections.
| Rapid| | Low flame sense current| Low flame sense current is often caused by carbon deposits on the flame sensor, a poorly grounded furnace or a mis- aligned flame sense probe. Carbon deposits can be cleaned with emery cloth. Check for improve furnace and module ground. Verify sensor is located in or very near flame as specified by the appliance manufacturer.
1| | | Call for cool| Normal operation.
Solid| | | Standby| Waiting for call from thermostat or receiving thermostat call for cool.

FAULT RECALL
When the control is in standby mode (no call for heat or cool), press the “LAST ERROR” button for approximately one – five seconds. The LED will flash up to five stored fault codes, beginning with the most recent. If there are no fault  codes in memory, the LED will flash two green flashes.

FAULT CODE RESET
When the control is in standby mode (no call for heat or cool), press the “LAST ERROR” button for five to ten seconds or until the diagnostic LED begins to rapid flash. The LED will flash three green flashes when the memory has been  cleared.

CONTROL RESET

  1. Interrupt the call for heat at the thermostat for at least one second but less than 20 seconds (if flame is sensed with the gas valve de-energized, interrupting the call for heat at the thermostat will not reset the control).
  2. Interrupt the 24 VAC power at the control for at least 20 seconds. You may also need to reset the flame rollout sensor switch.
  3. After 1 hour in lockout, the control will automatically reset itself.

Emerson and White-Rodgers are
trademarks of Emerson Electric
Co. ©2017 Emerson Electric Co.
All rights reserved.

White-Rodgers logo 2

white-rodgers.com
emerson.com

White-Rodgers logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

WHITE RODGERS User Manuals

Related Manuals