WHITE RODGERS Integrated Two-Stage Variable Speed Motor Hot Surface Ignition Control Kit Installation Guide
- June 7, 2024
- WHITE RODGERS
Table of Contents
21V51U-843
Integrated Two-Stage/Variable Speed Motor
Hot Surface Ignition Control Kit
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
The kit Includes:
- 50V51-843 Ignition Control Module
- 21D64-2 Ignitor Kit
- Set of Interconnect Harnesses (for Goodman)
The 50V51-843 is a two-stage automatic gas interrupted ignition control employing a microprocessor to continually monitor, analyze, and control the proper operation of the gas burner and inducer. The 50V51-843 provides signals for the proper operation of a variable fan speed circulator blower.
Signals interpreted during continual surveillance of the two-stage thermostat
and flame sensing element initiate automatic ignition of the burner, sensing
of the flame, and system shut off during normal operation.
The control incorporates system fault analysis for quick gas flow shutoff,
coupled with automatic ignition retry upon sensing a fault correction.
PRECAUTIONS
Installation should be done by a qualified heating and air conditioning
contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or low voltage, have
it inspected by a qualified heating and air conditioning contractor or
licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument and should be handled carefully. Rough
handling or distorting components could cause the control to malfunction.
Following installation or replacement, follow the manufacturer’s recommended
installation/service instructions to ensure proper operation.
CAUTION
Do not short out terminals on gas valve or primary control. Short or incorrect
wiring may damage the thermostat.
WARNING
| |
Failure to comply with the following warnings could result in personal injury
or property damage.
FIRE HAZARD
- Do not exceed the specified voltage.
- Protect the control from direct contact with water (dripping, spraying, rain, etc.).
- If the control has been in direct contact with water, replace the control.
- Label all wires before disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
- Route and secure wiring away from flame.
SHOCK HAZARD
- Disconnect electric power before servicing.
- Ensure proper earth grounding of appliance.
- Ensure proper connection of line neutral and line hot wires.
EXPLOSION HAZARD
- Shut off main gas to appliance until installation is complete.
emerson.com/white-rodgers
PART NO. 37-7115001 Replaces 37-7115D 2005
SPECIFICATIONS
ELECTRICAL RATINGS [@ 77°F (25°C)]:
Input Voltage: 25 VAC, 60 Hz (Class II transformer required)
Max. Input Current @ 25 VAC: 500mA + MV
Relay Load Ratings:
Gas Valve Relays: 1.5 amps @ 25 VAC, 60 Hz
Inducer Relays: 2.2 FLA – 3.5 LRA @120 VAC
Ignitor Relay: 4.0 amps @ 120 VAC (Resistive)
Humidifier/EAC: 120 VAC/1 Amp
Flame Current Requirements:
Minimum current to insure flame detection: 0.3 µa DC
Maximum current for non-detection: 0.1 µa DC
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:
-40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
5% to 93% relative humidity (non-condensing)
Timing Specs: (@ 60 Hz) maximum
Flame Establishing Time: 0.8 sec
Flame Failure Response Time: 2.0 secs
Gases Approved: Natural, Manufactured, Mixed, Liquefied Petroleum, and LP Gas Air Mixtures are all approved for use.
21V51U-843 TIMING TABLE
(All times are in seconds, unless noted otherwise)
Event
| Definition|
50M51-843
---|---|---
Pre-purge Time| The period of time intended to allow for the dissipation of
any unburned gas or residual products of combustion at the beginning of a
furnace operating cycle prior to initiating ignition|
15
Igniter Warm-up Time| The length of time allowed for the igniter to heat up prior to the initiation of gas flow.|
17
Trial for Ignition Period (TFI)| The period of time between initiation of gas flow and the action to shut off the gas flow in the event of failure to establish proof of the supervised ignition source or the supervised main burner flame.|
4
Ignition Activation Period (IAP)| The period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TFI|
3
Retries| The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period.|
2 times
Valve Sequence period| Valve sequence period equals 4 seconds trial for ignition period x (1 initial try + 2 retries) + 12 seconds.|
12
Inter-purge| The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion between the failed trial for ignition and the retry period.|
60
Post-purge Time| The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion at the end of a furnace burner operating cycle. Post-purge begins at the loss of flame sense.|
15
Lock-Out Time| ANSI standard rated module timing.|
300
Heat Delay-To-Fan-On| The period of time between proof of the supervised main burner flame and the activation of the blower motor at Heat speed.|
45
Heat Delay-To-Fan-Off*| The period of time between the loss of a call for heat and the deactivation of the blower motor at Heat speed.|
90/120/150/180
Cool Delay-To-Fan-On| The period of time after a thermostat demand for cool before energizing the circulator blower motor at Cool speed.|
5
Cool Delay-To-Fan-Off| The period of time between the loss of a call for cool and the deactivation of the blower motor at Cool speed.|
60
Automatic Reset Time| After one (1) hour of internal or external lockout, the control will automatically reset itself and go into an auto restart purge for 60 seconds.|
60 minutes
*These times will vary depending on option switch position.
INSTALLATION
MOUNTING AND WIRING
All wiring should be installed according to local and national electrical
codes and ordinances. The control must be secured to an area that will
experience a minimum of vibration and remain below the maximum ambient
temperature rating of 175°F.The control is approved for minimum ambient
temperatures of -40°F.
Any orientation is acceptable. Refer to the wiring diagram and wiring table
when connecting the 50V51 control to other components of the system. UL
approved, 105°C rated 18 gauge min., stranded, 2/64″ thick insulation wire is
recommended for all low voltage safety circuit connections. Refer to 50V51
specification sheet for recommended terminals to mate with those on the
control. UL approved, 105°C rated 16 gauge min., stranded, 4/64″ thick
insulation wire is recommended for all line voltage connections. Refer to
50V51 specification sheet for recommended terminals to mate with those on the
control.
LENNOX NOTE
CERTAIN CONTROLS SUCH AS P/N 100870-01 HAVE A SPLIT IN THE OEM LIMIT CIRCUIT
AND REQUIRE A MINOR WIRING CHANGE OR THEY WILL PRODUCE A FLAME SENSE ERROR.
CUT THE FACTORY WIRE CONNECTING TO 12-PIN MAIN CONNECTOR PIN 3 (FLAME PROBE).
SEE WIRING TABLE ON PAGE 7.
ALL LIMITS WILL BE PROPERLY MONITORED THROUGH PIN 11. THE FLAME PROBE IS
CONNECTED TO ¼” SPADE FP / E34, UPPER LEFT OF PCB.
The 50V51-843 has only one serviceable part an automotive type fuse, which
protects the low voltage transformer from damage if the output is short-
circuited. If the fuse has opened up, remove whatever caused the short circuit
and replace the fuse with only a 3 Amp automotive type fuse. If the fuse does
not correct the condition, replace the entire 50V51 control. There are no
other user-serviceable parts.
Following installation or replacement, follow the appliance manufacturer’s
recommended installation or service instructions to insure proper operation.
INSTALLER MUST-READ FOR PROPER INSTALLATION
- Wiring harnesses are included in this package to complete the installation of the “UNIVERSAL 50V51-843” for certain Goodman applications.
- Installer must-read Option Switch Settings section and set switches for proper control operation.
- For replacing the ignitor, a UNIVERSAL 21D64-2 is included. For proper installation, refer to the instructions included in the 21D64-2 kit.
- IMPORTANT: The installer may have to enlarge the existing ignitor hole to accommodate 21D64-2 larger (.394″) diameter.
GOODMAN NOTE
HARNESSES A & B ARE PIN TO SOCKET CONVERTERS AND ARE ONLY USED IF THE BOARD
BEING REPLACED HAS SOCKETS.
THIS ALLOWS THE ORIGINAL FACTORY FURNACE WIRING TO WORK WITH THE NEW 50V51-843
(21V51U-843 KIT) WHICH HAS PINS.
OPTION SWITCH SETTINGS
MOTOR OPTIMIZATION
Amana/Goodman/Trane/Lennox/Thermo Pride The motor configuration DIP
switches S3 and S4 must be set to match
IMPORTANT: Be sure to use proper switches for new board settings. Switch
locations on old board may not be the same location as on the new board.
York The existing board has four shunt jumper banks to set motor function
configuration. The four jumper banks are designated DELAY (E45), COOL (E43),
HEAT (E46), ADJ. (E44). Each jumper bank has four pair of pins to have
jumper installed to determine the type of voltage to the motor. These pin
pairs are A (no signal) B (positive Half-wave rectified), C (negative Half-
wave rectified), D (Full-wave unrectified).
On the new board, the motor functions must be duplicated on DIP switched S3
and S4 per the following table.
On the new
board, the motor functions must be duplicated on DIP switched S3 and S4 per
the following table.
FURNACE MANUFACTURER
DIP Switch Selection for OEM Applications
S2
|
OEM
|
---|---|---
1| 2
OFF| OFF| Trane
OFF| ON| Thermo Pride/Goodman
ON| OFF| Lennox
ON| ON| York
IMPORTANT: Switch selection must match furnace manufacturer for proper
motor operation.
Set DIP switches S2-1 and S2-2 to match the equipment using the table above.
NOTE: DIP switch S2-3 is not used.
THERMOSTAT TYPE AND HEAT-FAN-OFF-DELAY
DIP Switches
| Switch Settings|
Options
|
---|---|---|---
Thermostat Type and W2 Delay S7-1, S7-2| S7-1| S7-2| Time
Off| Off| Off
On| Off| 10 Minutes
Off| On| Auto
On| On| 20 Minutes
Heat Fan Off Delay S7-3, S7-4| S7-3| S7-4| Time
Off| Off| 90 Secs
Off| On| 120 Secs
On| Off| 150 Secs
On| On| 180 Secs
Multi-stage Thermostat Set-up,
Factory Default
DIP switches S7-1 and S7-2 (see table above) are set to the “Off” position from the factory for use with a multi-stage thermostat. This allows the thermostat to control staging between low and high fire.
Single Stage Thermostat Set-up,
Module Controls Staging
DIP switches, S7-1 and S7-2 (see table above) configure for a single-stage thermostat. Options include a 10-minute delay on second stage, 20-minute delay on second stage or an Auto setting allowing the module to calculate the time delay for second stage based on average demand. The “Average Calculated Duty Cycle” table shows how the module calculates staging based on demand.
Average Calculated Duty Cycle % Equals| or is less than| Low to
High Stage Delay| Demand
---|---|---|---
0
| 38| 12 minutes|
Light
38
| 50| 10 minutes|
Light to Average
50
| 62| 7 minutes|
Average
62
| 75| 5 minutes|
Average to Heavy
75
| 88| 3 minutes|
Heavy Light
88
| 100| 1 minute|
Heavy
Heat Fan Off Delay Timing
DIP switches S7-3 and S7-4 (see table above) configure the number of seconds the blower will run after the call for heat ends. Factory default is 90 seconds.
HEAT PUMP AND DE-HUMIDIFICATION
DIP Switches
|
Switch Settings
|
Options
|
---|---|---|---
Heat Pump
S5-1
| S5-1|
Off
| Installed
On|
Not Installed*
De-humidifier
S5-2
| S5-2|
Off|
Installed
On|
Not Installed*
*Factory Settings
Heat Pump Systems
DIP switch S5-1 (see table above) is set to “On” from the factory for use with
conventional (non-Heat Pump systems). For heat pump systems move the S5-1 DIP
switch to the “Off” position. This will continuously output an O signal to the
motor whenever there isY signal and run the circulator blower at a constant
speed when the pump is operating.
De-Humidification Connection
DIP switch S5-2 (see table above) is set to “On” from the factory for systems
that do not have a dehumidification terminal connection from the thermostat.
For systems using a thermostat that provides a De-Humidification option move
DIP switch S5-2 to “Off”.
MOUNTING HOLE TEMPLATE
WIRING
50V51-843 TYPICAL SYSTEM WIRING DIAGRAM
*Flame sensor probe may connect either through 12-pin main connector or to 3/16″ spade connector E34.
50V51-843 TYPICAL SYSTEM WIRING TABLE
50V51-843 TERMINAL| TERMINAL TYPE| SYSTEM COMPONENT
CONNECTION
---|---|---
TERMINAL
W1
W2
G
R
B/C
YLO
Y
DEHUM
O| | two-stage thermostat W1 terminal (or equivalent)
two-stage thermostat W2 terminal (or equivalent)
two-stage thermostat G terminal (or equivalent)
two-stage thermostat R terminal (or equivalent)
two-stage thermostat B/C terminal (or equivalent)
two-stage thermostat Y terminal (or equivalent)
two-stage thermostat Y2 terminal (or equivalent)
humidistat enable OUTPUT to circulator
H/P or cooling mode OUTPUT to circulator
MVH (Pin 1)
PS2 (Pin 2)
FP (Pin 3)
GND (Pin 4)
TH (Pin 5)
HLI (Pin 6)
MVL (Pin 7)
MV COM (Pin 8)
TR (Pin 9)
GND-2 terminals (Pin 10)
HLO (Pin 11)
PS1(Pin 12)| | gas valve SECOND STAGE
2nd stage pressure switch INPUT
flame sensor probe
MUST BE RELIABLY GROUNDED TO CHASSIS
24 VAC transformer (low voltage HIGH SIDE)
high limit INPUT
gas valve FIRST STAGE
gas valve COMMON
24 VAC transformer (low voltage COMMON SIDE)
MUST BE RELIABLY GROUNDED TO CHASSIS
high limit OUTPUT
1st stage pressure switch INPUT
IGN ( Pin 1)
IND HI (Pin 2)
IND LO (Pin 3)
IND N (Pin 4)
IGN N (Pin 5)| | ignitor HOT side
inducer HIGH SPEED HOT side
inducer LOW SPEED HOT side
inducer NEUTRAL side
ignitor NEUTRAL side
E2-1
E2-2
E2-3
E2-4
E2-5
E2-6
E2-7
E2-8
E2-9
E2-10
E2-2
E2-12
E2-13
E2-14
E2-15
E2-16| | 24 VAC COMMON
low heat speed select OUTPUT Circulator Blower
24 VAC COMMON
Delay tap OUTPUT to circulator
Cool tap OUTPUT to circulator
“YLO” OUTPUT to circulator
adjust tap OUTPUT to circulator
24 VAC COMMON
“O” OUTPUT to circulator
Humidistat/Y-Y2 OUTPUT to Circulator Blower
Heat tap OUTPUT to circulator
24 VAC OUTPUT to circulator
“W2” OUTPUT to circulator
“Y” OUTPUT to circulator
“G”/YLo OUTPUT to Circulator Blower
green CFM indicator
CIRC| spade terminal| circulator blower HOT terminal
LINE| spade terminal| input voltage (120 VAC) HOT side
XFMR| spade terminal| 24 VAC transformer line voltage HOT side
EAC (optional)| spade terminal| electronic air cleaner HOT side
HUM (optional)| spade terminal| humidifier HOT side
CIRC N| spade terminal| circulator blower NEUTRAL side
LINE N| spade terminal| input voltage (120 VAC) NEUTRAL side
XFMR N| spade terminal| 24 VAC transformer line voltage NEUTRAL side
HUM N (optional)| spade terminal| humidifier NEUTRAL side
EAC N (optional)| spade terminal| electronic air cleaner NEUTRAL side
FP / E34| spade terminal| flame sensor probe (Lennox)
NOTE: Spade terminals are 0.25″ x 0.032″
- maximum recommended flame probe wire length is 36 inches.
OPERATION
NORMAL OPERATION HEAT ON
When the thermostat calls for heat the module verifies the pressure switches
are open and energizes the inducer (high speed) and optional humidifier
contacts. When the low-pressure switch contacts close a 15-second pre-purge
begins. After 15 seconds the inducer switches to low speed and the 120 VAC
ignitor is energized. The ignitor warms up for 17 seconds and the gas valve is
energized on low fire. Flame must be detected within 4 seconds. If flame is
detected, a 45-second heat, fan on time delay begins. This allows the heat
exchanger to warm up before energizing the circulator on low speed and
(optional) Electronic Air Cleaner contact. When the thermostat (or module)
initiates second stage the inducer is energized at high speed.
This closes the second stage inducer pressure switch then energizes the second
stage on the gas valve and then the high heat circulator speed.
NORMAL OPERATION HEAT OFF
When the thermostat satisfies for second stage, the control will switch high-
speed inducer and high fire gas valve to low-speed inducer and low fire gas
valve. After the 30-second high heat fan delay the circulator will drop to low
speed. When the thermostat satisfies for first stage the gas valve de-
energizes and the inducer will run low speed for a 15-second post-purge. The
circulator runs until the heat off delay ends.
Note: If the module is configured for a single-stage thermostat and running on second stage when the call for heat ends, the circulator will drop to low speed after 30 seconds and continue until the heat-off delay ends.
COOL MODE
In a typical system, a call for cool is initiated by closing Y and G. This
energizes the compressor and the electronic air cleaner (optional). The
electronic air cleaner and the G and (Y or Ylo outputs to the Circulator motor
will energize after the 5 second cool on delay period. After the thermostat is
satisfied, the compressor is de-energized and the control starts a 60-second
cool circulator speed-off delay. After 60 seconds the circulator is de-
energized.
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the “ON” position, the electronic air
cleaner (optional) and the G circulator output to the circulator motor will be
energized. When the fan switch is returned to the AUTO position, the G
circulator output and the electronic air cleaner are de-energized.
TROUBLESHOOTING
SYSTEM LOCKOUT
When a system lockout occurs (1hour), the gas valve is de-energized, the low-
speed inducer blower is energized for the 60 seconds inter purge period and
the circulator is energized for selected heat off delay if it was previously
ON. The diagnostic indicator light will flash the fault that is present (refer
to diagnostic table).
To reset the control after system lockout, do one of the following:
System Reset
Remove 24 VAC power to the control for twenty (20) seconds or longer to reset
the control.
Thermostat Reset
Remove the call for heat from the thermostat for a period of between (1)
second and less 20 seconds. If flame is sensed with the gas valve de-
energized, interrupting the call for heat at the thermostat will not reset the
control.
Auto Restart
After one (1) hour of internal or external lockout, the control will
automatically reset itself and go into an auto-restart purge for 15 seconds.
DIAGNOSTIC FEATURES
The control continuously monitors its own operation and the operation of the
system. If a failure occurs the diagnostic indicator LED (DSI) will flash a
“RED” failure code. If a failure is internal to the control the “RED”
indicator will stay on continuously. In this case, the entire control should
be replaced as the control is not field-repairable. If the LED is continuously
OFF, there may be no power to the control or a failure within the control. If
the sensed failure is in the system (external to the control), the LED will
flash RED in the sequence listed in the Diagnostic Table. The LED will also
indicate “System Status” as per the Amber and Green LED signatures listed in
the Diagnostic Table. The LED will flash one RED flash at power-up.
CFM INDICATOR
The LED (DS2) CFM flashes when the blower motor is running. The flashing
indicates the motor CFM (cubic feet per minute) airflow designated by the
furnace manufacturer. Consult the furnace manufacturer for flash code detail.
FAULT CODE RETRIEVAL
To retrieve fault codes, push and release the “LAST ERROR” button for more
than 1/5 second and less than 5 seconds. (Control will indicate this period by
solid GREEN for 1/5 secs. to 5 secs.). The LED will flash up to five stored
fault codes, beginning with the most recent. If there are no fault codes in
memory, the LED will flash two green flashes. The control will flash the most
recent error first and the oldest error last (last in first out). There shall
be 2 seconds between codes. Solid LED error codes will not be displayed.
NOTE
These error codes may be different from furnace label or furnace manual.
TRI-COLOR (DSI LED) DIAGNOSTIC TABLE
Green
LED
Flash
| Amber
LED
Flash
| Red LED
Flash
| Error/Condition| Comments/Troubleshooting
---|---|---|---|---
| | 1| Flame sensed when no flame should be present| Verify the gas valve is
operating and shutting down properly. Flame in burner assemble should
extinguish promptly at the end of the cycle. Check orifices and gas pressure.
| | 2| Pressure switch stuck closed/ inducer error| Pressure switch stuck
closed. Check switch function, verify inducer is turning off.
| | 3| 1st-stage pressure switch stuck open/inducer error| Check pressure
switch function and tubing. Verify inducer is turning on the pulling
sufficient vacuum to engage switch.
| | 4| Open limit switch| Verify continuity through rollout switch circuit.
| | 5| Open rollout/open fuse detect| Verify continuity through rollout switch
circuit, check fuse.
| | 6| 1st-stage pressure switch cycle lockout| If the first stage pressure
switch cycles 5 times (open, closed) during one call for heat from the
thermostat the control will lockout. Check pressure switch for fluttering,
inconsistent closure or poor vacuum pressure.
| | 7| External lockout (retries exceeded)| Failure to sense flame is often
caused by carbon deposits on the flame sensor, a disconnected or shorted flame
sensor lead or a poorly grounded furnace. Carbon deposits can be cleaned with
emery cloth. Verify sensor is not contacting the burner and is located in a
good position to sense flame. Check sensor lead for shorting and verify
furnace is grounded properly.
| | 8| External lockout (ignition recycles exceeded where flame is established
and then lost)| Check items for exceeded retries listed above and verify valve
is not dropping out allowing flame to be established and then lost.
| | 9| Grounding or Reversed polarity| Verify the control and furnace are
properly grounded. Check and reverse polarity (primary) if incorrect.
| | 10| Module gas valve contacts energized with no call for heat| Verify
valve is not receiving voltage from a short. If a valve wiring is correct and
condition persists, replace module.
| | 11| Limit switch open – possible blower failure overheating limit|
Possible blower failure restricted airflow through appliance or ductwork.
Verify continuity through limit switch circuit and correct overheating cause.
| | 12| Module Ignitor contact failure| Fault code indicates the module
ignitor contacts are not functioning properly. Replace module.
| | Solid| Module – internal fault condition| Module contacts for gas valve
not operating or processor fault. Reset control. if condition persists replace
module.
| | 3 double| 2nd-stage Pressure Switch Stuck Open/Inducer Error| Check
pressure switch function and tubing. Verify inducer is turning on and pulling
sufficient vacuum to engage switch.
| 1| | Normal Operation with call for first stage heat| Normal operation –
first stage
| 2| | Normal Operation with call for second stage heat| Normal operation –
first stage
| 3| | W2 present with no W1| Second stage call for heat on thermostat circuit
with no call for first stage. Verify DIP switches are set for two stage
thermostat and check the thermostat first stage circuit. Configured for a
multi-stage thermostat the Module will not initiate heating unless first stage
call from the thermostat is received.
| 4| | Y present with no G call| Module will allow cooling to operate with
only a “Y signal from the thermostat but will also trigger this code. Verify
thermostat is energizing both “Y” and “G” on call for cool. Check “G” terminal
connections.
| Rapid| | Low flame sense current| Low flame sense current is often caused by
carbon deposits on the flame sensor, a poorly grounded furnace, or a
misaligned flame sense probe. Carbon deposits can be cleaned with emery cloth.
Check for improving furnace and module ground. Verify sensor is located in or
very near flame as specified by the appliance manufacturer.
1| | | Standby or Call for Cool| Normal operation. Waiting for call from the
thermostat or receiving thermostat call for cool.
NOTES
___
TECHNICAL SUPPORT: 1-888-725-9797