White-Rodgers M30 Thermostat Instruction Manual
- June 5, 2024
- WHITE RODGERS
Table of Contents
White-Rodgers M30 Thermostat
YOUR THERMOSTAT REPLACES
Description
Standard Heating & Cooling Systems – 4 or 5 wires| No
Standard Heat Only Systems| Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces| Yes
Standard Central Air Conditioning| No
Gas or Oil Heat| Yes
Electric Furnace| Yes
Hydronic (Hot Water) Zone Heat – 2 Wires| Yes
Hydronic (Hot Water) Zone Heat – 3 Wires| No
Heat Pump| No
Baseboard Electric Heating or Line Voltage (120 or 240 Volt)| No
PREPARATIONS
Assemble tools required as shown below.
Failure to follow and read all instructions carefully before installing or operating this control could cause personal injury and/or property damage
THERMOSTAT FEATURES
REMOVING OLD THERMOSTAT
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electrical power to the system at the main fuse or circuit breaker until installation is complete.Before removing wires from old thermostat’s switching subbase, label each wire with the terminal designation it was removed from.
- Remove Old Thermostat : A standard heat thermostat consists of two basic parts:
- The cover, which may be either a snap-on or hinge type.
- The base, which is removed by unscrewing the mounting screws that hold it on the wall or adaptor plate.
Make a note here of the anticipator setting on the old thermostat for future
reference and use in step 5.
The heat anticipator pointer, if adjustable, will be set at one of a series of
numbers representing the current rating of the primary control in your
furnace. The number will be one of the following: .2, .4, .8, etc. or 0.2,
0.4, 0.8, etc.
If no heat anticipator/indication is showing, do not be concerned; move on to
the next step.
REMOVING OLD THERMOSTAT
CONTINUED FROM THE FIRST PAGE
ATTENTION
- This product does not contain mercury. However, this product may replace a unit that contains mercury.
- Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, take up the spilled mercury and place into a container which can be sealed.
- If a cell becomes damaged, the unit should be discarded.
- Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container. Refer to www.Thermostat-recycle.org for location to send the product containing mercury.
MOUNTING AND WIRING
WARNING
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard. Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage the thermostat and could cause personal injury and/or property damage. Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
- A. Mount base and adaptor plate: Mount base to wall using screws provided (see Fig. 1).
- B. Attach wires: Attach one wire to R and the other wire to W on base.
SET HEAT ANTICIPATOR
Set the anticipator to match the setting of your old thermostat you noted in Step 3, or, the anticipator should be set to match the current rat-ing stamped on your main heating control. The heat anticipator is adjustable from 0.15 to 1.2 amps. Adjust the anticipator by rotating the contact arm (see fig. 2). The anticipator setting is indicated by the numbers on the base that the pointer points to. If you are unsure where to set the anticipator contact the heater manufacturer for a recommended setting. Move the pointer counterclockwise to lengthen heating system cycles; move clockwise to shorten heating cycles. Adjustments should not be greater than 1/2 marking at a time. Snap-on Cover: Carefully align the cover with the base and snap the cover onto the base.
NEW THERMOSTAT OPERATION
After power is turned on, slide temperature lever to desired setting. To turn heat off, slide lever all the way to the left until it clicks.
SPECIFICATIONS
ELECTRICAL DATA
- Switch Rating ……………………24 VAC (30 VAC max.)
- Heating ……………………………..0.15 to 1.2 Amps
- Switch Action ……………………Snap Action
Anticipator Rating
- Heating ……………………………..Adjustable from 0.15 to 1.2 Amps
THERMAL DATA
- Temperature Range ……………50°F to 90°F (10°C to 32°C)
- Operating Humidity Range …0 – 90% noncondensing
TROUBLESHOOTING
Symptom | Possible Cause | Corrective Action |
---|---|---|
No Heat | 1. Blown fuse or tripped circuit breaker. |
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel loose or not properly installed.
4. Pilot light not lit.
5. Broken or melted anticipator wire.
6. Loose connection to thermostat or system.
7. Thermostat or heating system re- quires replacement or service.
| Replace fuse or reset breaker. Turn switch to ON.
Replace door panel in proper position to engage safety interlock or door switch.
Re-light pilot.
Excessive current or dead short in system. Have a qualified service person check the system.
Verify thermostat and system wires are securely attached.
Your furnace manufacturer or service person can describe how to test the heating system to verify it is operating correctly. If the heating
system is capable of operation and the no heat condition persists, replace the thermostat.
Intermittent Heat| 1. Furnace Lock-Out Condition| Many furnaces have
safety devices that shut the system down when a lock-out condition oc- curs.
If the heat works intermittently contact the furnace manufacturer or local
service person for assistance.
Heat Runs Constantly.| 1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat system.
| Check each wire connection to the thermostat to verify it is neatly looped
under the terminals. No extra wire should stick out from under the terminals.
Furnace Cycles Too Fast or Too Slow Narrow or wide temperature swing|
See Step 5, Adjusting the Anticipator.| The anticipation setting is the only
adjustment that effects the heating cycle rate. If an ac- ceptable cycle rate
is not achieved using the anticipator contact a local service person for ad-
ditional suggestions. The location of the thermo- stat, size of the Heat/Cool
System and current draw can influence the cycle rate.
Thermostat Setting and Thermostat Thermometer Disagree| 1. Thermostat
thermometer setting requires adjustment.
2. Thermostat setting lever requires calibration.
| The thermometer can be adjusted by using a standard slotted screwdriver.
Turn the thermom- eter pointer screw located inside the front cover to change
the setting. For calibrating the setting lever contact a local heating and
cooling service person.
Adjusting Thermometer| 3. Thermostat thermometer disagrees with other
room thermometers.| The thermometer on the thermostat is accurate- ly
calibrated at our factory but you can adjust it by using a standard slotted
screwdriver. Turn the thermometer pointer screw located inside the front cover
to change the setting.
FOR CALIFORNIA RESIDENTS
Warning: This product contains a chemical known to the state of California to
cause cancer and birth defects and other reproductive harm.