Carrier 50FCQ-04 Electric Heat Puron Refrigerant Owner’s Manual

June 16, 2024
Carrier

Carrier 50FCQ-04 Electric Heat Puron Refrigerant

  • JOB NAME:………………………………… LOCATION:……………………………………………….
  • BUYER:…………………….. BUYER PO #:…………………… CARRIER #:……………………..
  • UNIT NUMBER:………………………………. MODEL NUMBER:………………………………..
  • PERFORMANCE DATA CERTIFIED BY:……………………………………………………………

DESCRIPTION

50FCQ units are standard-efficiency, single-packaged heat pump units with Ecoblue™ Technology that are pre-wired and pre-charged with Puron® refrigerant. Electric heat is available as a field-installed accessory. The units are fully factory-tested and agency-certified. These units have field convertible supply and return openings and are intended for installation on a roof curb accessory (ordered separately), or for slab mounting (for horizontal duct connections). Units may be ordered with various factory-installed options. Field-installed accessories are also available.

FEATURES

Standard Base Unit

  • Puron (R-410A) HFC refrigerant
  • SEERs up to 14.3 and SEER2s up to 13.4
  • IEERs up to 15.0 and heating HSPFs up to 8.2
  • HSPFs up to 8.2 (COPs to 3.8)
  • ASHRAE 90.1 compliant and Energy Star qualified
  • Rated by AHRI Standards 210/240 (3-5 ton sizes) and 340/360 (6-ton sizes)
  • Designed by Underwriters Laboratories Std 1995
  • Listed by UL and UL-Canada
  • Non-corrosive composite sloping design; side or centre drain condensate pan. Meets ASHRAE Standard 62
  • Single-stage cooling capacity control on 3-5 tons while 6 ton models have two-stage cooling capacity control
  • Standard cooling operating range up to 115°F (46°C) and down to 40°F (4°C). Low Ambient allows cooling operation down to –20°F (–29°C)
  • Convertible from vertical to horizontal airflow for slab mounting
  • Two-inch disposable return air filters
  • Thru-the-bottom power entry capability
  • Single-point electric connections on field-installed electric heat units
  • 24-volt control circuit protected with resettable circuit breaker and 75-VA transformer
  • Direct Drive – EcoBlue ™ Technology indoor fan system uses a Vane Axial fan design and electronically commutated motor.
  • Enclosed condenser motors with permanently lubricated bearings
  • State-of-the-art defrost control board, easily configured for defrost cycles of 30, 60, 90, or 120 minutes
  • New Unit Control Board with intuitive quick fan adjustment
  • Loss of charge, high-pressure, and freeze protection switches
  • Full perimeter base rail with built-in rigging adapters and fork truck slots

Cabinet

  • Access panels with easy grip handles and replaceable no-strip screw collar
  • Pre-painted exterior panels and primer-coated interior panels tested to 500 hours of salt spray protection
  • Fully insulated cabinet
  • Tool-less filter access door

Refrigerant System

  • Acutrol™ refrigerant metering system on 04-06 models, TXV on 07 size models
  • Liquid line filter drier
  • Scroll compressors with internal line-break overload protection
  • Indoor and outdoor coils constructed of aluminium fins mechanically bonded to seamless copper tubes
  • Removable gauge line plugs for reading refrigerant pressure with unit panels in place
  • Four-way reversing valve operation
  • Suction line accumulator standard – prevents excessive liquid floodback of refrigerant to the compressor even during the start of the defrost cycle

Warranty

Standard Limited Parts Warranty

  • 5-year electric heater (field-installed)
  • 3-year SystemVu Controller
  • 5-year compressor
  • 1-year parts

PERFORMANCE DATA

  • Unit Operating Weight __ lb
  • Curb Weight __ lb

COOLING

  • Net Total Capacity __ Btuh
  • Net Sensible Capacity ___ Btuh
  • Compressor Power Input ___ kW
  • at Outdoor Air Temperature __ °F
  • Indoor Entering: db __ °F / wb __ °F
  • Airflow CFM External Static Pressure in. wg

HEATING (ELECTRIC)

  • Power Input to Unit ____ kW
  • Integrated Capacity ___ Btuh
  • Indoor Operating Air Temperature ___ °F db
  • Outdoor Air Temperature ___ °F (Winter Design)
  • Rating at 70% R.H. Outdoors ___ kW Heater Selected
  • __ Heat/Cool Ratio
  • Electrical Capacity Required ___ Btuh

ELECTRICAL DATA

  • Power Supply to Unit ____
  • Volts _____
  • Phase _____ Hz
  • Maximum Circuit Amps __
  • Maximum Overcurrent Protection (Fuse Only) _____

SUBMITTAL DATA

  • Job Name _____
  • Architect __
  • Engineer _____
  • Contractor _____
  • Unit Designation ____

FACTORY-INSTALLED OPTIONS

Economizer with DRY BULB Sensing and Barometric Relief 1

  • Standard Leak Air Dampers — Models with W7212 controller provide standard non-diagnostic control (EconoMi$er® IV system).
  • Models with W7220 controller meet California Title 24 (Section 120.2) for Fault Detection and Diagnostic (FDD) requirements (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (Section 120.2) Fault Detection and Diagnostic (FDD) requirements (EconoMi$er 2 system).

Economizer with ENTHALPY Sensing and Barometric Relief 1

  • Standard Leak Air Dampers — Models with W7212 controller provide standard non-diagnostic control (EconoMi$er® IV system).
  • Models with W7220 controller meet California Title 24 (Section 120.2) Fault Detection and Diagnostic (FDD) requirements (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (Section 120.2) Fault Detection and Diagnostic (FDD) requirements (EconoMi$er 2 system).

Economizer with DRY BULB Sensing and Barometric Relief 1

  • ULTRA LOW LEAK Air Dampers — Models with W7220 controller meet California
  • Title 24 section 120.2 Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, have returned, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty. (EconoMi$er 2 system).

Economizer with ENTHALPY Sensing and Barometric Relief 1

  • ULTRA LOW LEAK Air Dampers — Models with W7220 controller meet California
  • Title 4 section 120.2 Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, have returned, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty. (EconoMi$er 2 system).

SystemVu Controls

  • Large full text – multi-line display
  • USB Flash Port for data transfer
  • Built-in i-Vu®, CCN and BACnet
  • Refrigerant pressure from the display
  • Quick LED Status – Run, Alert, Fault
  • Conventional stat or sensor capabilities
  • Historical component runtime and starts
  • Supply Air Tempering
  • Equipment / System Touch Compatibility
  • Demand Limiting and ZS Sensor Compatibility

RTU Open multi-protocol controller communicates to LonWorks®2, MODBUS®2, BACnet™2, and Johnson N2 protocols

  • Through-the-base connectors for electric conduit
  • Non-fused disconnect (80A max)
  • Powered 115-volt convenience outlet
  • Non-powered 115-volt convenience outlet
  • High static evaporator fan motor
  • Return air smoke detector
  • Supply air smoke detector
  • Smoke detectors — return and supply air
  • Pre-coated Al/Cu condenser coil
  • E-coated Al/Cu condenser coil
  • E-coated Al/Cu condenser and evaporator coil
  • Cu/Cu condenser coil
  • Cu/Cu condenser coil and evaporator coil
  • Condenser hail guard – louvred style1
  • CO2 sensor
  • Hinged access doors
  • Condensate overflow switch

Optional Warranties

  • Complete unit parts only, up to 5 years
  • Complete unit parts and labour, up to 5 years

Many other optional warranties are available. See the Commercial Start-Up and Optional Extended Warranty Price pages for further information.

FIELD-INSTALLED ACCESSORIES

Economizer with DRY BULB Sensing and Barometric Relief 1

  • Standard Leak Air Dampers — Models with W7212 controller provide standard non-diagnostic control (EconoMi$er® IV system).
  • Models with W7220 controller meet California Title 24 (Section 120.2) for Fault Detection and Diagnostic (FDD) requirements (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (Section 120.2) Fault Detection and Diagnostic (FDD) requirements (EconoMi$er 2 system).

Economizer with ENTHALPY Sensing and Barometric Relief 1

  • Standard Leak Air Dampers — Models with W7212 controller provide standard non-diagnostic control (EconoMi$er® IV system).
  • Models with W7220 controller meet California Title 24 (Section 120.2) Fault Detection and Diagnostic (FDD) requirements (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (Section 120.2) Fault Detection and Diagnostic (FDD) requirements (EconoMi$er 2 system).

Economizer with DRY BULB Sensing and Barometric Relief 1

  • ULTRA LOW LEAK Air Dampers — Models with W7220 controller meet California
  • Title 24 section 120.2 Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty (EconoMi$er X system).
  • Models with RTU Open controller meet California Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, have returned, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty. (EconoMi$er 2 system).

Economizer with ENTHALPY Sensing and Barometric Relief 1

ULTRA LOW LEAK Air Dampers — Models with W7220 controller meet California Title 4 section 120.2 Fault Detection and Diagnostic (FDD) requirements, have a return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty (EconoMi$er X system).
Models with RTU Open controller meet California Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, have returned, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements – plus 5-year limited parts warranty. (EconoMi$er 2 system).

  • Power exhaust – vertical or horizontal
  • Electric heat
  • Single point kit
  • Two-position motorized outdoor air damper
  • Manual outdoor air damper 25%
  • Manual outdoor air damper 50%
  • Roof curb – 14 inch (356 mm) tall
  • Roof curb – 24 inch (610 mm) tall
  • Thru-the-bottom utility connection kit
  • Time Guard II compressor anti-cycle control
  • Outdoor coil hail guard – louvred style
  • Programmable setback thermostat
  • Phase monitor (loss of phase/phase reversal)
  • Condensate overflow switch

Economizer Sensors

  • Single dry bulb control
  • Differential dry-bulb control
  • Single enthalpy control
  • Differential enthalpy control
  • CO2 — wall mounted
  • CO2 — duct mounted

DIMENSION

CERTIFIED DIMENSION PRINT

Carrier-50FCQ-04-Electric-Heat-Puron-Refrigerant-FIG-2Carrier-50FCQ-04-Electric-Heat-Puron-Refrigerant-
FIG-3 Carrier-50FCQ-04-Electric-Heat-
Puron-Refrigerant-FIG-4

ROOF CURB DETAILS

Carrier-50FCQ-04-Electric-Heat-Puron-Refrigerant-FIG-5

NOTES

  1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
  2. INSULATED PANELS: 25.4 [1″] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
  3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
  4. ROOFCURB: 18 GAGE STEEL.
  5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
  6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
  7. DIRECTION OF AIR FLOW.
  8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.

CONTACT

  • Manufacturer reserves the right to discontinue or change at any time, specifications or designs without notice and without incurring obligations.
  • Printed in U.S.A. Form 50FCQ-4-7-02SB Rev.
  • B Pg 10 10-23 Replaces: 50FCQ-4-7-01SB.