SOLAX POWER SDM230 Series Wire Multifunction Din Rail Meter User Manual
- June 15, 2024
- SOLAX POWER
Table of Contents
SDM230 Series
Single Phase Two Wire
Multifunction Din Rail Meter
SDM230 Series Wire Multifunction Din Rail Meter
User Manual V1.6
Warnings
Important Safety Information is contained in the Maintenance section.
Familiarize yourself with this information before attempting installation or
other procedures.
Risk of Danger: These instructions contain important safety information. Read
them before starting installation or servicing of the equipment.
Caution: Risk of Electric Shock
Introduction
This document provides operating, maintenance and installation instructions of
SDM230 series made by Eastron Electronic Co., Ltd. The SDM230 series measure
and display the characteristics of single phase two wire (1p2w) network. The
SDM230 series covers 5 models:SDM230-Modbus,SDM230-Pulse,SDM230- Mbus,
SDM230-2T and SDM230-Std.
The bi-directional measurement makes the meter suitable for active and
reactive energy and power monitoring applications, and also perfect for solar
PV measurements. With RS485 Modbus and M-bus port, the meter is easy to remote
communication with other AMRI/SCADA systems.
Model| Measurements| Communi- cation| Pulse Outputs|
Multi Tariffs
---|---|---|---|---
SDM230- Modbus| U, I, P, Q, S, PF, Hz, Dmd, kWh, kVArh, Import, Export| RS485
Modbus| 1: confgurable
2: 1000imp/kwh| NO
SDM230- Mbus| U, I, P, Q, S, PF, Hz,Dmd, kWh, kVArh, Import, Export| M-bus
EN13757-3| 1:confgurable
2: 1000imp/kwh| NO
SDM230- Pulse| U, I, P, Q, S, PF, Hz, DNmO d, kWh, kVArh, Import, Export| | 1:
confgurable
2: 1000imp/kwh| NO
SDM230- 2T| U, I, P, Q, S, PF, Hz, Dmd, kWh, kVArh, Import, Export| RS485
Modbus| 1: confgurable
2: 1000imp/kwh| 2 Tariffs (time relay)
SDM230- Std| kWh, kVArh, Import, Export| RS485 Modbus| 1: conFgurable
2: 1000imp/kwh| NO
1.1 Key Characteristics
- Bi-directional measure and display
- Multi-function measurements
- Two Pulse outputs
- RS485 Modbus / M-bus
- 100A direct connection
- Two module size (35mm)
- Password protected set-up
- Backlighted LCD
- 2 tariff dual power source
1.2 Pulse output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 can be set to generate pulses to represent total /
import/export kWh or kVArh.
The pulse constant can be set to generate 1 pulse per:
0.001/0.01/0.1/1kWh/kVArh (default is 0.001 export kWh). Pulse width:
200/100/60ms Pulse output 2 is non-confgurable. It is fixed up with active kWh
(Imp). The constant is 1000imp/kWh.
1.3 RS485 Serial – Modbus RTU
RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit.Set-up screens are provided for setting up
the RS485 port.
1.4 Mbus for SDM230-Mbus
This unit has an M-BUS serial port with M-BUS protocol to provide a means of
remotely monitoring and controlling the unit set-up screens are provided for
setting up the M-bus port.
1.5 2T by time relay for SDM230-2T
The unit has a time relay inside which can monitor if there is external 230V
signal input. If there is 230V signal input, the meter switches Tariff 2
measurement, otherwise it will measure as Tariff 1.
Operation
2.1 LCD Display
NO. | Descriptions |
---|---|
1 | 7 digits used to display measured values |
2 | Total value |
3 | Tariff information |
4 | Import information, Export information |
5 | Max. Demand for Power or Current. |
6 | Pulse output 1and Pulse output2 |
7 | Measurement units |
8 | PF = power factor Hz = frequency |
9 | Bar display of Power |
10 | Communication indicatior |
13 | Lock symbol |
2.2 Initialization Display
| All display segments light up, display check.
---|---
| Software version (please check the real software version on the product as
the final).
| Modbus ID or Mbus Primary Address
| Mbus Secondary Address (High) (for SDM230-Mbus only)
| Mbus Secondary Address (Low) (for SDM230-Mbus only)
| Baud rate.
| Total kWh.
2.3 Scroll display by Buttons
After initialization and self-checking program, the meter display the measured
values. The default page is total kWh. If the user wants to check other
information, he needs to press the scroll button on the front panel.
The display order by scroll button :
*For SDM230-Modbus:
Total kWh→ Import kWh→Export kWh→ Resettable kWh→ Total kVArh→Import kVArh→
Export kVArh→Resettable kVArh → Max. Power Demand→ Voltage →Current→W→ Var →
VA→ Power Factor→Frequency →Pulse Constant→ Modbus ID → Baud Rate →Continuous
Running Time
Display No:1,4~7,10~24.
*For SDM230-Std:
Total kWh→ Import kWh→Export kWh→ Resettable kWh→Total kVArh→Import kVArh→
Export kVArh→ Resettable kVArh→ Pulse Constant→ Modbus ID→ Baud Rate
→Continuous Running Time Display No:1,4~7,10~12, 21~24.
1| | Total active energy Example:70.00kWh
---|---|---
2| | T1 active energy Example: 10.00kWh (for SDM230-2T only)
3| | T2 active energy Example: 10.00kWh (for SDM230-2T only)
4| | Import(input) active energy Example: 50.00kWh
5| | Export(output) active energy Example: 20.00kWh
6| | Resettable total energy
7| | Total reactive energy Example: 10.00kVArh
8| | T1 reactive energy Example: 2.00kVArh (for SDM230-2T only)
9| | T2 reactive energy
Example: 2.00kVArh (for SDM230-2T only)
10| | Import(input)reactive energy Example: 5.00kVArh
11| | Export(output)reactive energy
Example: 5.00kVArh
12| | Resettable total energy
13| | Max. power demand Example: 6938W
14| | Voltage
Example: 229.8V
15| | Current
Example: 30.156A
16| | Active power
Example: 4700W
17| | Reactive power
Example: 1030Var
18| | Apparent power
Example: 4811VA
19| | Power factor
Example: 1.000
20| | Frequency
Example: 49.99Hz
21| | Pulse 2 constant
Example: 1000
22| | Modbus address
Example: 001
Mbus primary address
Example:001
22-1| | High and Low bit of MBUS Secondary address (Default 00 00 00 01)
Example: if the Secondary address high bit is 0000, low bit is 0001,that means
the integral Secondary address is 00 00 00 01
(for SDM230-Mbus only)
23| | Baud rate
Example: 9600
24| | Continuous running time (since last time reset) Continuous running time
(since last time reset)
2.4 Set-up Mode
To get into Set-up Mode, the user needs to press the “Enter” button for 3
seconds.
| The setting is done correctly
---|---
| The entering information
is wrong. The operation fails.
1| | Password
To get into Set-up mode, it asks a password confirmation.
Default password: 1000
---|---|---
2| | Address
For Modbus:
Default ID is 001
Range: 001~247
For Mbus:
Primary address ID
Default ID is 001
Range:001~250
2-1| | Press the
“Enter” button, the first digit frash.Press the “Scroll” button to change the
value. After choosing the new address value, the user needs to press the
“Enter” button to confirm the setting.
2-2| | High bit of Mbus Secondary address(Default 00 00) (for SDM230-Mbus
only)
| Low bit of Mbus Secondary address(Default 00 01)
Example: if the Secondary address high bit is 0000,low bit is 0001,that means
the integral Secondary address is 00 00 00 01 (for SDM230-Mbus only)
2-3| Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the option.
After choosing the new value, the user needs to press the “Enter” button to
confirm the setting.
3| | Baud rate for Modbus
Default value: 2400bps
Range: 1200, 2400,
4800, 9600bps.
Baud rate for Mbus:
Default value: 2400bps
Range:300, 600,1200, 2400,
4800, 9600bps.
3-1| | Press the “Enter” button, the red digit flash.Press the “Scroll” button
to change the value. After choosing the new baud rate, the user needs to press
the “Enter” button to conflrm the setting.
4| | Parity
Default: None
Option:None, Even, Odd
4-1| | Press the “Enter” button, the red part flash. Press the “Scroll” button
to change the option. After choosing the new parity, the user needs to press
the “Enter” button to confirm the setting.
5| | Pulse Output 1
Default: kWh
Option:kWh / KVArh /
Imp. kWh / Exp.kWh /
Imp.kVArh / Exp.kVArh
5-1| | Press the
“Enter” button, the red part flash.Press the “Scroll” button to change the
option. After choosing the new pulse output option, the user needs to press
the “Enter” button to
confirm the setting.
6| | Pulse Constant
Default: 1000
Option: 1000 / 100 / 10 / 1
6-1| | Press the “Enter” button, the red part flash.Press the “Scroll” button
to change the option. After choosing the new pulse constant option, the user
needs to press the “Enter” button to confirm the setting.
7| | Pulse duration
Default: 100mS
Option: 200 / 100 / 60mS
7-1| | Press the “Enter” button, the red part flash.Press the “Scroll” button
to change the option. After choosing the new pulse duration option, the user
needs to press the “Enter” button to confirm the setting.
8| | Demand Integration Time
Default: 15 minutes
Option: off(0) / 5 / 10 /
15 / 30 / 60
8-1| | Press the “Enter” button, the ed part flash.Press the “Scroll” button
to change the option. After choosing the new DIT option, the user needs to
press the “Enter” button to confirm the setting.
9| | Automatic Scroll Time Interval
Default: 0 S
Option: 0 ~ 30S
9-1| | Press the “Enter” button, the red part flash.Press the “Scroll” button
to change the option. After choosing the new “Scrl” option, the user needs to
press the “Enter” button to confirm the setting.
10| | Backlit lasting time set-up
Default: 60 min
Option: 0(off)/ 5/ 10/ 20/ 30/ 60
Long press “Enter” button to enter set-up mode.
10-1| | Press the “Enter” button, the red part flash.Press the “Scroll” button
to change the option. After choosing the new “Scrl” option, the user needs to
press the “Enter” button to confirm the setting.
11| | Clear
Long press “Enter” to enter clear interface.
11-1| | Clear Max demand of active power Long press “Enter” button to confirm
the operation.
12| | Clear the resettable energy Long press the Enter button to confirm the
operation.
13| | Password
Default: 1000
13-1| | Press the “Enter” button, the red part flash.Press the “Scroll” button
to change the option. After choosing the new “Scrl” option, the user needs to
press the “Enter” button to confirm
the setting.
ATTENTION: Pulse output must be fed as shown in the wiring diagram below.
Scrupulously respect polarities and the connection mode.
Opto-coupler with potential-free SPST-NO Contact.
Contact range:5~27VDC Max. current
Input:27mA DC.
3.5 RS485 output for Modbus RTU
Not for SDM230-Pulse or SDM230-Mbus
The meter provides a RS485 port for remote communication.
Modbus RTU is the protocol applied. For Modbus RTU, the following RS485
communication parameters can be configured from the set-up menu.
Baud rate: 1200, 2400, 4800, 9600 bps
Parity: NONE/ODD/EVEN
Stop bits: 1 or 2
Modbus Address: 1 to 247
3.6 Mbus
For SDM230-Mbus only
The meter provides a Mbus Port for remote communication.
the meter adopts EN1434-3 Mbus communication protocol.
The communication parameters can be configured via the SET-UP mode.
Baudrate: 300,600,1200,2400,4800,9600 bps
Parity: NONE/ODD/EVEN
Stop bits: 1 or 2
Primary address: 001~250
Secondary address: 00000001~99999999
3.7 Mechanics
Din rail dimensions| 36x99x63 (WxHxD)
Per DIN 43880
---|---
Mounting| DIN rail 35mm
Sealing| IP51 (indoor)
Material| self-extinguishing UL94V-1
Dimensions
Installation and sealing
Wiring diagram
6.1 SDM230-V1 6.2 SDM230-V2
6.3 Definitions of other terminals![SOLAX POWER SDM230 Series Wire Multifunction Din Rail Meter
- Denitions of other terminals](https://manuals.plus/wp-
content/uploads/2023/12/SOLAX-POWER-SDM230-Series-Wire-Multifunction-Din-Rail-
Meter-Denitions-of-other-terminals.jpg) Declaration of Conformity(for the
MID approved version meter only)
We Zhejiang Eastron Electronic Co.,Ltd.
Declare under our sole responsibility as the manufacturer that the poly phase multifuntion electrical energy meter “SDM230 Series” correspond to the production model described in the EU-type examination certificate and to the requirements of the Directive 2014/32/EU EU type examination certificate number 0120/SGS0206.
Identification number of the NB0120
Zhejiang Eastron Electronic Co.,Ltd.
Add: No.1369 , Chengnan Rd. Jiaxing,
Zhejiang, China
Tel: 86 573 83698881/83698882
Fax: 86 573 83698883
Email: sales@eastrongroup.com
Web: www.eastrongroup.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>