ECOSENSE Trov-L50 Graze Instruction Manual

June 4, 2024
ECOSENSE

ECOSENSE Trov-L50 Graze

ECOSENSE Trov-L50 Graze

Read the following instructions before operating the luminaire.

EcoSense Lighting fixtures must be installed by a qualified electrician.

EcoSense Lighting, Inc. is not responsible if its fixtures are not installed in accordance with all national and local safety standards.

INCLUDED

TROV Installation Guide

  • Angle lock Clips in bags of 10 will ship in separate boxes for each L50 order. Use one clip for 12 in and two clips for 48 in fixtures
  • Every lighting fixture includes firmware that facilitates electronic dimming control

ADDITIONAL ITEMS NEEDED

  • Power Cables: Order one power cable per run at the length needed

OPTIONAL ITEMS

  • Power Cables for joining runs: Power cables can also be used to connect power between fixtures that are separated from 1 to 10 feet as long as maximum run lengths are not exceeded
  • Mounting Options: Mounting track with Clips (FOR INTERIOR USE ONLY); L-Brackets. (See Spec sheets and Installation Guides for more details)

PLAN THE INSTALLATION

Verify the Electrical Plan

| 2W/LF| 4W/LF| 6W/LF| 8W/LF| 10W/LF| 12W/LF
---|---|---|---|---|---|---
Volts| Max Run all 1’| Max Run all 4’| Max Run all 1’| Max Run all 4’| Max Run all 1’| Max Run all 4’| Max Run all 1’| Max Run all 4’| Max Run all 1’| Max Run all 4’| Max Run all 1’| Max Run all 4’
120| 214| 214| 186| 186| 152| 152| 114| 114| 91| 91| 76| 76
220| 374| 392| 340| 340| 277| 277| 209| 209| 95| 167| 95| 139
277| 374| 494| 374| 428| 349| 349| 263| 263| 95| 190| 95| 175

ECOSENSE Trov-L50 Graze 1

INSTALL THE FIXTURES

Select Mounting Option

Choose method best suited for mounting surface and installation application.

ECOSENSE Trov-L50 Graze 2

INSTALLATION USING FLIP-TO-FLAT™ MOUNTING SYSTEM

ECOSENSE Trov-L50 Graze 3

OPTIONAL INSTALL WITH TRACK MOUNT

ECOSENSE Trov-L50 Graze 4OPTIONAL INSTALL WITH L-BRACKET

ECOSENSE Trov-L50 Graze 5

OPTIONAL INSTALL WITH ANGLE LOCK

ECOSENSE Trov-L50 Graze 6

INSTALLATION CONSIDERATIONS

  • POWER CONSUMPTION
  • OPERATING TEMPERATURE
  • OPERATING VOLTAGE
  • WEIGHT
  • DIMENSIONS

ECOSENSE Trov-L50 Graze 7

Connect Fixtures and Power

Attach the power cable to either the flexible connector or the fixed connector on the fixture. Cut the connector off at the other end of the power cable, strip the wires, and connect to the building power. Attach one of the terminators to the last fixture in the run.

Caution, risk of electric shock

  • The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
  • Read and understand the installation instructions before attempting to install or use the fixture.
  • Only use fixtures with voltage for which it is rated. Do not exceed the specified voltage and current input.
  • Do not use fixture if the housing, lens, or power cable are damaged.
  • Fixtures have line voltage risk of shock and no user serviceable parts. Do not attempt to open.
  • Do not hot swap. Ensure that power is off before connecting or disconnecting fixtures in the series
  • Ensure that main power supply is off before installing or wiring a fixture.
  • Hazardous live parts shall not be accessible after installation, and it is the installer’s responsibility to ensure that the installation/connections are in compliance with national and local electrical codes and regulations
  • The wire connection method shall be determined by local electrical codes and regulations, typically using either wire nuts or screw terminal blocks.
  • Possibly hazardous optical radiation emitted from this product.
  • Polycarbonate Chemical Warning: Please contact an EcoSense sales representative for a complete list of chemicals that can cause damage to polycarbonate lenses and silicone gaskets. EcoSense must not be held responsible for damage to, or failure of, fixtures where any of these, or chemicals of similar nature and makeup, are applied intentionally or inadvertently to EcoSense’s fixtures.
  • Earth leakage Statement: Please contact an EcoSense factory representative for full information on the earth leakage properties of EcoSpec fixtures when installed according to all local electrical codes and proper installation techniques
  • EcoSense Inrush Current Statement: Please contact an EcoSense Lighting sales representative for a complete list of Inrush Current Peak (A) at specific product Voltage, and Inrush Current Duration/Width (ms), for each EcoSense product.
  • The external flexible cable of this luminaire cannot be replaced; if the cord is damaged, the luminaire shall be destroyed.
  • The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
  • This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
  • This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
  • This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.

If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or experienced radio/TV technician for help.

Modifications

Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

ECOSENSE LIGHTING INC. 837 NORTH SPRING STREET SUITE 103 LOS ANGELES, CA 90012

  • P • 310.496.6255
  • F • 310 . 496 . 6256
  • T • 855.632.6736

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE. VISIT ECOSENSELIGHTING.COM FOR THE MOST CURRENT SPECIFICATIONS.
© 2019 ECOSENSE LIGHTING INC. ALL RIGHTS RESERVED. ECOSENSE, THE ECOSENSE LOGO, RISE, TROV, SLIM COVE AND ECOSPEC ARE REGISTERED TRADEMARKS OF ECOSENSE LIGHTING INC. FREEDOM TO CREATE™

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ECOSENSE User Manuals

Related Manuals