PRELIMINARY WARNINGS

The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

  • WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians.
  • Specific documentation is available using the QR-CODE shown on page 1.
  • The module must be repaired and damaged parts replaced by the Manufacturer.
  • The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
  • Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

ABOUT COMPANY

  • SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY;
  • Tel. +39.049.8705359
  • Fax +39.049.8706287

CONTACT INFORMATION

  • Technical support:support@seneca.it
  • Product information:sales@seneca.it
  • This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies.
  • Stated data may be modified or supplemented for technical and/or sales purposes.

MODULE LAYOUT

  • Dimensions: LxHxD 17.5 x 102.5 x 111 mm;
  • Weight: 110 g;
  • Enclosure: PA6, black

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR Green ON The device is powered correctly
FAIL yellow Flashing Anomaly or fault
RX Red Flashing Receipt of packet completed
RX Red ON Anomaly / Check connection
TX Red Flashing Transmission of packet completed

TECHNICAL SPECIFICATIONS

SENECA Z-8AI Analog Input or Output Module-fig4

INPUTS

Voltage input :| Bipolar with F.S. programmable at +2Vdc and +10Vdc Input impedance >100kOhm
Current input :| Bipolar with F.S. Programmable at +20mA with 50Ohm internal shunt selectable via DIP-switch. Available power supply: 90 + 90mA at 13Vdc.
Number of channels:| 8
Input resolution:| 15 bit + sign.
Input protection:| ± 30Vdc or 25mA
Precision voltage and current:| Starting: 0.1 of full scale Linearity : 0.03% of scale. Zero: 0.05% of scale.

TC: 100 ppm, EMI: <1 %

Sampling time| 120 ms/channel or 60 ms/channel
Measurement update time (sampling rate: 10ms)| 1 channel enabled (update time for 1 channel)

4 channels enabled (update time for 4 channels)

8 channels enabled (update time for 8 channels)

CONFIGURATION OF FACTORY SETTINGS

SENECA Z-8AI Analog Input or Output Module-fig5

SETTING THE DIP-SWITCHES

The position of the DIP-switches defines the Mod bus communication parameters of the module: Address and Baud Rate The following table shows the Baud Rate and Address values according to the DIP-switch setting:

SENECA Z-8AI Analog Input or Output Module-fig6
Note:
When DIP switches 1 to 8 are OFF, the communication settings are taken from programming (EEPROM).
Note 2: The RS485 line must be terminated only at the ends of the communication line.

SENECA Z-8AI Analog Input or Output Module-fig7
The settings of the dip-switches must be compatible with the settings on the registers. The description of the registers is available in the USER MANUAL.

ELECTRICAL CONNECTIONS

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DINAL-17.5 accessory.

Back connector (IDC 10)
The illustration shows the meanings of the various IDC10 connector pins if signals are to be sent via them directly.

INPUTS

SENECA Z-8AI Analog Input or Output Module-fig9

  • A) Voltage input with sensor supply from the MODULE (13 Vdc)
  • B) Voltage input with sensor supply NOT coming from the MODULE
  • C) Current input with sensor supply NOT coming from the MODULE
  • D) Current input with sensor supply from the MODULE (13 Vdc)
  • E) Current input with sensor EXTERNAL power supply

ATTENTION

  • The upper power supply limits must not be exceeded, as this might cause serious damage to the module. Switch the module off before connecting inputs and outputs.
  • To meet the electromagnetic immunity requirements:
    • use shielded signal cables;
    • connect the shield to a preferential instrumentation earth system;
    • separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, etc…).
    • install a fuse with a MAX capacity of 2.5A near the module.