MEAN WELL NCP-3200 Series 2 In 1 Rack Mounted Switching Power Supply Owner’s Manual
- June 14, 2024
- MEAN WELL
Table of Contents
MEAN WELL NCP-3200 Series 2 In 1 Rack Mounted Switching Power Supply
Dimension
- L W H
- 325.8 107 41 (1U) mm
- 12.82 4.21 1.61 (1U) inch
Features
- Universal AC input / Full range
- Power supply or charger mode selectable by PMBus, CANBus or SBP-001 (only for 24V/48V models)
- Built-in 2/3 stage charging curves and programmable curve (only for 24V/48V models)
- High efficiency up to 94.5%
- Built-in programmable output voltage and output current
- Built-in OR-ing FET or Diode, support hot swap (hot plug)
- Active current sharing up to 10 rack shelves and the maximum power supply that can be connected in parallel is 40 units
- Support PMBus/CANBus protocol
- Built-in intelligent fan speed control
- Protections: Short circuit / Overload / Over voltage /Over temperature
- Design refers to SEMI F47 standard specification
- 5 years warranty
Applications
- Industrial automation
- Distributed power architecture system
- Wireless/telecommunication solution
- Redundant power system
- Large-scale DC UPS or emergency backup system
- Electric scooter or vehicle charger station
- Wastewater treatment system
- Electrolysis system
GTIN CODE
- MW Search: https://www.meanwell.com/serviceGTIN.aspx.
Description
- NCP-3200 is a 3.2KW dual-purpose(Switching Power Supply and charger) rack-mounted AC/DC power supply with a 1U low profile design and high power density of up to 37W/inch. This series operates at 90~264VAC input voltage and offers the models with the DC output mostly demanded by the industry.
- Each model is cooled by the built-in DC fan with fan speed control and working for the temperature up to 70°C. NCP-3200 provides vast design flexibility by equipping with PMBus and CANbus, two international communication protocols that can be selected for industrial control and power supply control, and can also be used directly with intelligent controller CMU2. Active current sharing up to 10 rack shelves (DHP-1UT-B) and the maximum power supply that can be connected in parallel is 40 units, remote ON/OFF control, auxiliary power, alarm signal, and others.
Model Encoding / Order Information
Note 1: 19″ rack shelf, DHP-1UT-B(HV), available. Details available on
http://www.meanwell.com/
Note 2: Control/Monitor unit, CMU2, available. Details available on
http://www.meanwell.com/
Type | Communication Protocol | Note |
---|---|---|
Blan | PMBus protocol | In Stock |
CAN | CANBus protocol | In Stock |
SPECIFICATION FOR POWER SUPPLY MODE (Default)
MODEL | NCP-3200-24 | NCP-3200-48 |
---|
OUTPUT
| DC VOLTAGE (factory default)| 24V| 48V
RATED CURRENT (factory default)| 133A| 67A
CURRENT RANGE| 0 ~ 133A| 0 ~ 67A
RATED POWER (max.)| 3192W| 3216W
RIPPLE & NOISE (max.) **Note.2,3| 300mVp-p| 480mVp-p
VOLTAGE ADJ. RANGE| 23.5 ~ 30V| 47.5 ~ 58.8V
VOLTAGE TOLERANCE Note.4| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%
LOAD REGULATION| ±0.5%| ±0.5%
SETUP, RISE TIME| 1500ms, 60ms/230VAC at full load
HOLD UP TIME (Typ.)**| 16ms / 230VAC at 70% load 8ms / 230VAC
at full load
INPUT
| VOLTAGE RANGE Note.6| 90 ~ 264VAC 127 ~ 400VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| 0.97/230VAC at full load
EFFICIENCY (Typ.) Note.7| 93.5%| 94.5%
AC CURRENT (Typ.) Note.6| 17A/230VAC
INRUSH CURRENT (Typ.)| COLD START 55A/230VAC
LEAKAGE CURRENT| <2mA / 230VAC
PROTECTION
|
OVERLOAD
| 105 ~ 115% rated current
Protection type: Constant current limiting, shut down O/P voltage after 5 sec.
After the O/P voltage falls, re-power on to recover
OVERVOLTAGE
| 31.5 ~ 37.5V| 63 ~ 75V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION
| OUTPUT VOLTAGE
PROGRAMMABLE(PV)
| Adjustment of the output voltage is allowable to 50 ~ 125% of nominal
output voltage Please refer to the Function Manual in the following pages
CONSTANT CURRENT LEVEL PROGRAMMABLE(PC)| Adjustment of the constant
current level is allowable to 20 ~ 100% of rated current Please refer to the
Function Manual in the following pages
REMOTE ON-OFF CONTROL| By electrical signal or dry contact Power ON:
short Power OFF: open. Please refer to the Function Manual in the following
pages
REMOTE SENSE| Compensate voltage drop on the load wiring up to 0.5V.
Please refer to the Function Manual in the following pages
CURRENT SHARING| Active current sharing up to 10 rack shelves(DHP-1UT-B)
and the maximum number of supply units that can be connected in parallel is 40
AUXILIARY POWER| 5V @ 0.3A, tolerance ±10%, ripple 150mVp-p, 12V @ 0.8A,
tolerance ±10%, ripple 450mVp-p
ALARM SIGNAL| Isolated TTL signal output for T-Alarm, AC-OK and DC-OK.
Please refer to the Function Manual in the following pages
ENVIRONMENT
| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, and Z
axes
SAFETY & EMC
(Note 10)
| SAFETY STANDARDS| UL62368-1, CSA C22.2 No. 62368-1, TUV BS
EN/EN62368-1, EAC TP TC 004 approved ; Design refer to AS/NZS62368.1
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY
| BS EN/EN55024, BS EN/EN61000-6-2; Design refer to SEMI F47 at 200VAC
Parameter| Standard| Test Level / Note
END| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-4-5| 2KV/Line-Line 4KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
95% interruptions 250 periods
OTHERS
| MTBF| 510.5K hrs min. Telcordia SR-332 (Bellcore); 45.8K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 325.810741mm (LWH)
PACKING| 2.3Kg;4pcs/10.2Kg/1.09CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Under variable load application or parallel operation ripple of the output voltage may be higher than the SPEC at light load conditions. It will go back to normal ripple level once the output load is more than 5%.
4. Tolerance: includes set up tolerance, line regulation and load regulation.
5. RCM is on a voluntary basis and meets relevant IEC or AS/NZS standards complying with AS/NES 4417.1.
6. Derating may be needed under low input voltages. Please check the derating curve for more details.
7. The efficiency is measured at 75% load.
8. If use PV signal to adjust Vo, under certain operating conditions, the ripple noise of Vo might slightly go over the rating defined in this specification.
9. Output will shut down after O/P voltage is below < 80% of Vset for 5 sec, re-power on to recover.
10. The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
11. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
MODEL | NCP-3200-380 |
---|
OUTPUT
| DC VOLTAGE (factory default)| 380V
CURRENT (factory default)| 8.4A
CURRENT RANGE| 0 ~ 9.6A
RATED POWER (max.)| 3206.4W
FULL POWER VOLTAGE RANGE| 334 ~ 400V
RIPPLE & NOISE (max.) **Note.2,3| 4000mVp-p
VOLTAGE ADJ. RANGE| 260 ~ 400V
VOLTAGE TOLERANCE Note.4| ±1.0%
LINE REGULATION| ±0.5%
LOAD REGULATION| ±0.5%
SETUP, RISE TIME| 1500ms, 60ms/230VAC at full load
HOLD UP TIME (Typ.)**| 16ms / 230VAC at 70% load 8ms / 230VAC
at full load
INPUT
| VOLTAGE RANGE Note.6| 90 ~ 264VAC 127 ~ 400VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| 0.97/230VAC at full load
EFFICIENCY (Typ.) Note.7| 94%
AC CURRENT (Typ.) Note.6| 17A/230VAC
INRUSH CURRENT (Typ.)| COLD START 55A/230VAC
LEAKAGE CURRENT| <2mA / 230VAC
PROTECTION
|
OVERLOAD
| 105 ~ 115% rated current
Protection type: Constant current limiting, shut down O/P voltage after 5 sec.
After the O/P voltage falls, re-power on to recover
OVERVOLTAGE
| 420 ~ 480V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION
| OUTPUT VOLTAGE
PROGRAMMABLE(PV)
| Adjustment of the output voltage is allowable to 50 ~ 120% of nominal
output voltage Please refer to the Function Manual in the following pages
CONSTANT CURRENT LEVEL PROGRAMMABLE(PC)| Adjustment of the constant
current level is allowable to 20 ~ 100% of the rated current Please refer to
the Function Manual on the following pages
REMOTE ON-OFF CONTROL| By electrical signal or dry contact Power ON:
short Power OFF: open. Please refer to the Function Manual in the following
pages
CURRENT SHARING| Active current sharing up to 10 rack shelves(DHP-1UT-
BHV) and the maximum number of supply units that can be connected in parallel
is 40
AUXILIARY POWER| 5V @ 0.3A, tolerance ±10%, ripple 150mVp-p, 12V @ 0.8A,
tolerance ±10%, ripple 450mVp-p
ALARM SIGNAL| Isolated TTL signal output for T-Alarm, AC-OK and DC-OK.
Please refer to the Function Manual in the following pages
ENVIRONMENT
| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, and Z
axes
SAFETY & EMC
(Note 10)
| SAFETY STANDARDS| UL62368-1, CSA C22.2 No. 62368-1, TUV BS
EN/EN62368-1, EAC TP TC 004 approved ; Design refer to AS/NZS62368.1
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY
| BS EN/EN55024, BS EN/EN61000-6-2; Design refer to SEMI F47 at 200VAC
Parameter| Standard| Test Level / Note
END| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-4-5| 2KV/Line-Line 4KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
95% interruptions 250 periods
OTHERS
| MTBF| 510.5K hrs min. Telcordia SR-332 (Bellcore); 45.8K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 325.810741mm (LWH)
PACKING| 2.3Kg;4pcs/10.2Kg/1.09CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Under variable load application or parallel operation ripple of the output voltage may be higher than the SPEC at light load conditions. It will go back to normal ripple level once the output load is more than 5%.
4. Tolerance: includes set up tolerance, line regulation and load regulation.
5. RCM is on a voluntary basis and meets relevant IEC or AS/NZS standards complying with AS/NES 4417.1.
6. Derating may be needed under low input voltages. Please check the derating curve for more details.
7. The efficiency is measured at 75% load.
8. If use PV signal to adjust Vo, under certain operating conditions, the ripple noise of Vo might slightly go over the rating defined in this specification.
9. Output will shut down after O/P voltage is below < 80% of Vset for 5 sec, re-power on to recover.
10. The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
11. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
SPECIFICATION FOR CHARGER MODE (Selectable by PMBus, CANBus or SBP-001)
MODEL | NCP-3200-24 | NCP-3200-48 |
---|
OUTPUT
| BOOST CHARGE VOLTAGE(Vboost)(default)| 28.8V| 57.6V
FLOAT CHARGE VOLTAGE(Vfloat)(default)| 27.6V| 55.2V
CONSTANT CURRENT(CC)(default)| 110A| 55A
RECOMMENDED BATTERY
CAPACITY(AMP HOURS) Note.3
| ****
330 ~ 1000Ah
| ****
180 ~ 550Ah
LEAKAGE CURRENT FROM BATTERY(Typ.)| ****
<1.5mA
INPUT
| VOLTAGE RANGE Note.4| 90 ~ 264VAC 127 ~ 400VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| 0.97/230VAC at full load
EFFICIENCY (Typ.)| 93%| 94%
AC CURRENT (Typ.) Note.4| 17A/230VAC
INRUSH CURRENT (Typ.)| COLD START 55A/230VAC
LEAKAGE CURRENT| <2mA / 230VAC
PROTECTION
| ****
OVERVOLTAGE
| 31.5 ~ 37.5V| 63 ~ 75V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION
| REMOTE ON-OFF CONTROL| By electrical signal or dry contact Power ON:
short Power OFF: open. Please refer to the Function Manual in the following
pages
CURRENT SHARING| Active current sharing up to 10 rack shelves(DHP-1UT-B)
and the maximum number of supply units that can be connected in parallel is 40
AUXILIARY POWER| 5V @ 0.3A, tolerance ±10%, ripple 150mVp-p, 12V @ 0.8A,
tolerance ±10%, ripple 450mVp-p
ALARM SIGNAL| Isolated TTL signal output for T-Alarm, AC-OK and DC-OK.
Please refer to the Function Manual on the following pages
ENVIRONMENT
| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, and Z
axes
SAFETY & EMC
(Note 6)
| SAFETY STANDARDS| UL62368-1, CSA C22.2 No. 62368-1, TUV BS
EN/EN62368-1, EAC TP TC 004 approved ; Design refer to AS/NZS62368.1
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY
| BS EN/EN55024, BS EN/EN61000-6-2
Parameter| Standard| Test Level / Note
END| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-4-5| 2KV/Line-Line 4KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
95% interruptions 250 periods
OTHERS
| MTBF| 510.5K hrs min. Telcordia SR-332 (Bellcore); 45.8K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 325.810741mm (LWH)
PACKING| 2.3Kg;4pcs/10.2Kg/1.09CUFT
NOTE| 1. Modification for charger specification may be required for
different battery specifications. Please contact the battery vendor and MEAN
WELL for details.
2. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
3. This is MEAN WELL’s suggested range. Please consult your battery manufacturer for their suggestions about the maximum charging current limitation.
4. Derating may be needed under low input voltages. Please check the derating curve for more details.
5. RCM is on a voluntary basis and meets relevant IEC or AS/NZS standards complying with AS/NES 4417.1.
6. The charger is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on
a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
BLOCK DIAGRAM
STATIC CHARACTERISTICS
DERATING LOADS vs INPUT VOLTAGE
MODEL
INPUT
| 24V| 48V| 380V
---|---|---|---
180~264VAC
| 3192W
133A
| 3216W
67A
| 3192W
8.4A
90VAC
| 1596W
66.5A
| 1608W
33.5A
| 1596W
4.2A
DERATING CURVE
EFFICIENCY vs LOAD (48V MODEL)
FUNCTION MANUAL
Charging Curve (Charger mode only available for 24V/48V models)
- By default, the unit operates in power supply mode, and it can be configured to charger mode by PMBus, CANBus or SBP-001.
- By factory default, this charger performs the default curve which can be programmed via PMBus and CANBus.
- To accommodate the parameters of the charging curve, SBP-001, the smart battery charging programmer designed by MEAN WELL, and a personal computer are needed. Please contact MEAN WELL for details.
State | NCP-3200-24 | NCP-3200-48 |
---|---|---|
Constant Current |
110A
|
55A
Vboost| 28.8V| 57.6V
- Suitable for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries (lithium iron and lithium manganese).
State | NCP-3200-24 | NCP-3200-48 |
---|---|---|
Constant Current |
110A
|
55A
Vboost| 28.8V| 57.6V
Vfloat| 27.6V| 55.2V
- Suitable for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries (lithium iron and lithium manganese).
- Embedded 2-stage charging curves
MODEL | Description | CC(default) | Vboost |
---|
24V
| Default, programmable|
110A
| 28.8
Pre-defined, gel battery| 28
Pre-defined, flooded battery| 28.4
Pre-defined, AGM battery| 29
48V
| Default, programmable|
55A
| 57.6
Pre-defined, gel battery| 56
Pre-defined, flooded battery| 56.8
Pre-defined, AGM battery| 58
Embedded 3-stage charging curves
MODEL | Description | CC(default) | Vboost | Vfloat |
---|
24V
| Default, programmable|
110A
| 28.8| 27.6
Pre-defined, gel battery| 28| 27.2
Pre-defined, flooded battery| 28.4| 26.8
Pre-defined, AGM battery| 29| 27
48V
| Default, programmable|
55A
| 57.6| 55.2
Pre-defined, gel battery| 56| 54.4
Pre-defined, flooded battery| 56.8| 53.6
Pre-defined, AGM battery| 58| 54
Front Panel LED Indicators
Voltage Drop Compensation
- Remote Sense (For 24V/48V models under power supply mode only)
- The Remote Sense compensates for voltage drop on the load wiring up to 0.5V
Local Sense (For 24V/48V models under power supply mode only)
- The +S and and-S have to be connected to the +V(signal), and -V(signal), respectively, as the following diagram, in order to get the correct output voltage if Remote Sense is not used.
Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
- In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 50~125% (24/48V models) or 50~120% (380V model) of the nominal voltage by applying EXTERNAL VOLTAGE.
Constant Current Level Programming (or, PC / remote current programming / dynamic current trim)
-
The constant current level can be trimmed to 20~100% of the rated current by applying EXTERNAL VOLTAGE.
-
If setting the output current to a much lower level, as output status turns to the constant current mode, it might cause a higher current ripple under such conditions.
-
The 100% output current is 133/67/9.6A.
-
Notice the output power does not overrate power (max.)
Remote ON-OFF Control
- The power supply can be turned ON/OFF individually or along with other units by using the “Remote ON-OFF” function.
Between Remote ON-OFF and +5V-AUX | Power Supply Status |
---|---|
Switch Short | ON |
Switch Open | OFF |
PMBus Communication Interface
NCP-3200 supports PMBus Rev. 1.1 with a maximum 100KHz bus speed, allowing
information reading, status monitoring, output trimming, etc. For details,
please refer to the Function Manual.
CANBus Communication Interface
NCP-3200 supports CAN 2.0B with a maximum 250KHz bus speed, allowing
information reading, status monitoring, output trimming, etc. For details,
please refer to the User’s Manual.
Alarm Signal Output
- There are 3 alarm signals, DC-OK, AC-OK and T-ALARM, in TTL signal form, on CN1. These signals are isolated from the output. The maximum sink current is 10mA.
DC-OK signal | Power Supply Mode Status | Charger Mode Status |
---|---|---|
“High” > 3.5~5.5V | Vout ≦ 77%±5% | Vout ≦ 66%±5% |
“Low” < -0.5~0.5V | Vout ≧ 80%±5% | Vout ≧ 67%±5% |
AC-OK signal | Power Supply and Charger Mode Status | |
--- | --- | |
“High” > 3.5~5.5V | Input voltage ≧ 87Vrms | |
“Low” < -0.5~0.5V | Input voltage ≦ 75Vrms | |
T-ALARM signal | Power Supply and Charger Mode Status | |
--- | --- | |
“High” > 3.5~5.5V | OFF(OTP or Fan Fail) | |
“Low” < -0.5~0.5V | ON(Normal Work) |
Parallel Operation
- For parallel operation, please refer to the function manual of the DHP-1UT-B(HV) rack system.
- Read the installation manual before using this device. For the NCP-3200-380 high output voltage model, the correct rack system DHP-1UT-BHV should be used.
- Failure to do so will cause permanent damage.
19″ Rack shelf | DHP-1UT-B | DHP-1UT-B | DHP-1UT-BHV |
---|---|---|---|
Power supply or battery charger unit | NCP-3200-24*4 | NCP-3200-48*4 |
NCP-3200-380*4
MECHANICAL SPECIFICATION
Input / Output Connector Pin No. Assignment(CN1) : C27309-10749-Y
(Any questions about the Mating connector, please contact MEANWELL’S sales
representative.)
Pin No. | Function | Description |
---|---|---|
1,2 | -V | Negative output terminal. |
3,4 | +V | Positive output terminal. |
5 | +12V-AUX | Auxiliary voltage output, 10.8~13.2V, referenced to _GND-AUX (pin |
7)_.
The maximum load current is 0.8A. This output has the built-in “Oring diodes” and is not controlled by the Remote ON/OFF control.
6| +5V-AUX| Auxiliary voltage output,4.5~5.5V, reference to GND_AUX(pin7). The
maximum load current is 0.3A. The output has the built-in “Oring diodes” and
is not controlled by the Remote ON/OFF control.
7| GND-AUX| Auxiliary voltage output GND. The signal return is isolated from
the output terminals (+V & -V).
8
| ____
AC-OK
| High (3.5 ~ 5.5V): When the input voltage is ≧87Vrms. Low (-0.5 ~ 0.5V): When the input voltage is ≦75Vrms.
The maximum sourcing current is 10mA and only for output. (Note.2)
9
|
T-ALARM
| High (3.5 ~ 5.5V): When the internal temperature exceeds the limit of the temperature alarm, or when the fan fails. Low (-0.5 ~ 0.5V): When the internal temperature is normal, and when the fan normally works.
The maximum sourcing current is 10mA and only for output(Note.2)
10,24| NC| Standard model: Retain for future use
11
| SCL| For PMBus model: Serial Clock used in the PMBus interface. (Note.2)
CANCEL| For CANBus model: Data line used in CANBus interface. (Note.2)
12
| SDA| For PMBus model: Serial Data used in the PMBus interface. (Note.2)
CANH| For CANBus model: Data line used in CANBus interface. (Note.2)
13| Remote ON-OFF| The unit can turn the output ON/OFF by electrical signal or
dry contact between Remote ON/OFF and +5V-AUX. (Note.2) Short (4.5 ~ 5.5V)
: Power ON ; Open (-0.5 ~ 0.5V) : Power OFF ; The maximum input voltage is
5.5V.
14
|
____ DC-OK
| For power supply mode
High (3.5 ~ 5.5V): When the Vout ≦77%±5%. Low (-0.5 ~ 0.5V): When the Vout ≧80%±5%.
The maximum sourcing current is 10mA and only for output. (Note.2)
For charger mode
High (3.5 ~ 5.5V): When the Vout ≦66%±5%.
Low (-0.5 ~ 0.5V): When the Vout ≧67%±5%. The maximum sourcing current is 10mA and only for output. (Note.2)
DC OK is associated with battery low protection.
15,16| DA, DB| Differential digital signal for parallel control. (Note.1)
17| PC| Connection for constant current-level programming. (Note.1)
18,19,20,21| A2,A3,A4,A5| PMBus / CANBus interface address lines(for Rack
system). (Note.1)
22,23| A0,A1| PMBus / CANBus interface address lines for Rack-mountable front-
end rectifier. (Note.1)
25| PV| Connection for output voltage programming. (Note.1)
26| -V (Signal)| Negative output voltage signal.
It is for local sense, and certain function references; it cannot be connected directly to the load.
27
| -S| Negative sensing for remote sense.(For 24V/48V models under power supply
mode only)
NC| Not available for NCP-3200-380
28
| +S| Positive sensing for remote sensing. (For 24V/48V models under power
supply mode only)
NC| Not available for NCP-3200-380
29
| +V (Signal)| Positive output voltage signal. (For 24V/48V models under power supply mode only)
It is for local sense; it cannot be connected directly to the load.
NC| Not available for NCP-3200-380
30| FG| AC Ground connection.
32| AC/L| AC Line connection.
31| AC/N| AC Neutral connection.
Note 1: Non-isolated signal, referenced to [-V(signal)].
Note 2: Isolated signal, referenced to GND-AUX.
https://www.meanwell.com/serviceGTIN.aspx.