Leviton AFTR1-W Smartlock Pro Receptacle Outlet User Manaul
- June 14, 2024
- Leviton
Table of Contents
Leviton AFTR1-W Smartlock Pro Receptacle Outlet
What is a Outlet Branch Circuit AFCI?
An Outlet Branch Circuit AFCI is different from conventional receptacles. It is intended to provide protection to branch circuit wiring, cord sets, and power-supply cords connected to it against the unwanted affects of arcing. In the event of an arc fault, an AFCI will trip and quickly stop the flow of electricity to mitigate the effects of the arcing that may have posed a risk of fire ignition if the arcing persisted.
Definition of an arcing fault:
An arcing fault is an unintentional arcing condition in a circuit. Arcing
occurs as a normal condition in some motors or when a switch opens. An example
of unintentional arcing would be arcing that occurs due to severed power-
supply cord conductors. An Outlet Branch AFCI does not protect against circuit
overloads, short-circuits or against shock hazards.
NOTE:
Leviton’s AFCI’s contain a lockout feature that will prevent RESET if:
- There is no power being supplied to the AFCI.
- The AFCI is miswired due to reversal of the LINE and LOAD leads.
- The AFCI cannot pass its internal test, indicating that it may not be able to provide protection in the event of an arc fault.
The AFCI’s features
Should you install it?
Installing a GFCI receptacle can be more complicated than installing a
conventional receptacle.
Make sure that you:
- Understand basic wiring principles and techniques
- Can interpret wiring diagrams
- Have circuit wiring experience
- Are prepared to take a few minutes to test your work, making sure that you have wired the GFCI receptacle correctly
LINE vs. LOAD
A cable consists of 2 or 3 wires
LINE cable:
Delivers power from the service panel (breaker panel or fuse box) to the GFCI.
If there is only one cable entering the electrical box, it is the LINE cable.
This cable should be connected to the GFCI’s LINE terminals only.
LOAD cable:
Delivers power from the GFCI to another receptacle in the circuit. This cable
should be connected to the GFCI’s LOAD terminals only. The LOAD terminals are
under the yellow sticker. Do NOT remove the sticker at this time
Turn the power OFF
Plug an electrical device, such as a lamp or radio, into the receptacle on
which you are working. Turn the lamp or radio ON. Then, go to the service
panel. Find the breaker or fuse that protects that receptacle. Place the
breaker in the OFF position or completely remove the fuse. The lamp or radio
must turn OFF.
Next, plug in and turn ON the lamp or radio at the receptacle’s other outlet to make sure the power is OFF at both outlets. If the power is not OFF, stop work and call an electrician to complete the installation.
Identify cables/wires
Important:
DO NOT install the GFCI receptacle in an electrical box containing (a) more
than four (4) wires (not including the grounding wires) or (b) cables with
more than two (2) wires (not including the grounding wire) Contact a qualified
electrician if either (a) or (b) are true.
- If you are replacing an old receptacle, pull it out of the electrical box without disconnecting the wires.
- If you see one cable (2-3 wires), it is the LINE cable. The receptacle is probably in position C (see diagram to the right).
- Remove the receptacle and go to step 7A.
- If you see two cables (4-6 wires), the receptacle is probably in position A or B (see diagram to the right). Follow steps a-e of the procedure to the right
Procedure : box with two (2) cables (4-6 wires):
- Detach one cable’s white wire and hot wires from the receptacle and cap each one separately with a wire connector.
- Make sure that they are from the same cable.
- Re-install the receptacle in the electrical box, attach faceplate, then turn the power ON at the service panel.
- Determine if power is flowing to the receptacle. If so, the capped wires are the LOAD wires. If not, the capped wires are the LINE wires.
- Turn the power OFF at the service panel, label the LINE and LOAD wires, then remove the receptacle.
- Go to step 7B.
Placement in circuit:
The GFCI’s place in the circuit determines if it protects other receptacles in
the circuit.
Sample circuit:
- Placing the GFCI in position A will also provide protection to “load side” receptacles B and C. On the other hand, placing the GFCI in position C will not provide protection to receptacles A or B.
- Remember that receptacles A, B, and C can be in different rooms.
Connect the wires
Connect the wires (choose A or B)… only after reading other side completely
A: One Cable (2 or 3 wires) entering the box
Connect the LINE cable wires to the LINE terminals:
- The white wire connects to the WHITE terminal (Silver)
- The black wire connects to the HOT terminal (Brass or Black)
Connect the grounding wire (only if there is a grounding wire):
- For a box with no grounding terminal (diagram not shown): Connect the LINE cable’s bare copper (or GREEN) wire directly to the grounding terminal on the GFCI receptacle.
- For a box with a grounding terminal (diagram shown above): Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the GFCI. Also connect a similar wire to the grounding terminal on the box. Connect the ends of these wires to the LINE cable’s bare copper (or GREEN) wire using a wire connector. If these wires are already in place, check the connections.
Complete the installation:
- Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT terminals. Screw the receptacle to the box and attach the faceplate.
- Go to step 8.
B: Two cables (4 or 6 wires) entering the box
Connect the LINE cable wires to the LINE terminals:
- The white wire connects to the WHITE terminal (Silver)
- The black wire connects to the HOT terminal (Brass or Black)
Connect the LOAD cable wires to the LOAD terminals:
- Remove the YELLOW sticker to reveal the LOAD terminals
- The white wire connects to the WHITE terminal (Silver)
- The black wire connects to the HOT terminal (Brass or Black)
Connect the grounding wires (only if there is a grounding wire):
- Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the GFCI. If the box has a grounding terminal, also connect a similar wire to the grounding terminal on the box.
- Connect the ends of these wires to the LINE or LOAD cable’s bare copper (or GREEN) wire using a wire connector. If these wires are already in place, check the connections.
Complete the installation:
- Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT terminals. Screw the receptacle to the box and attach the faceplate.
- Go to step 8
Test your work
Why perform this test?
- If you miswired the GFCI it may not prevent personal injury or death due to a ground fault (electrical shock).
- If you mistakenly connect the LINE wires to the LOAD terminals, the GFCI will not reset and will not provide power to either the GFCI receptacle face or any receptacles fed from the GFCI.
Procedure:
- This GFCI is shipped from the factory in the tripped condition and cannot be reset until it is wired correctly and power is supplied to the device. Plug a lamp or radio into the GFCI (and leave it plugged in).
- Turn the power ON at the service panel. Ensure that the GFCI is still in the tripped condition by pressing the TEST button. If the lamp or radio is OFF, and the GFCI will not reset, go to the Troubleshooting section as the Line and Load connections are reversed.
- Press the RESET button fully and release. If the Status Indicator Light turns Green and the lamp or radio is ON, the GFCI has been installed correctly. If the Status Indicator Light turns or continuously blinks Red, or the GFCI cannot be reset, go to the Self-Test Operation section.
- If you installed your GFCI using step 7B, plug a lamp or radio into surrounding receptacles to see which one(s), in addition to the GFCI, lose power when you press the GFCI TEST button.
- Place a “GFCIPROTECTED OUTLET” sticker on every receptacle that lost power, then press the RESET button to reset the GFCI. DO NOT plug life saving devices into any of the receptacles that lost power.
- Press the TEST button (then RESET button) every month to assure proper operation. If the Status Indicator Light does not turn Green when the RESET button is depressed and then released, or the GFCI cannot be reset, it must be replaced.
TROUBLESHOOTING
Turn the power OFF and check the wire connections against the appropriate wiring diagram in step 7A or 7B. Make sure that there are no loose wires or loose connections. If the Status Indicator Light is not ON and the device is unable to reset this could be a result of no power available. Start the test from the beginning of step 8 if you rewired any connections to the GFCI.
SELF-TEST OPERATION
- A Self-Test GFCI receptacle has all the features of a conventional GFCI receptacle. In addition, this receptacle tests itself periodically to confirm the GFCI electronics are functional. The Status Indicator Light will be solid green when the GFCI is powered from Line side and working correctly.
- Self-Test Indications: If the Status Indicator Light is solid or flashing RED a problem may exist. Press the TEST button to trip the GFCI. If unable to Reset, replace the GFCI. NOTE: The status indicator may flash Red at power “ON” and Reset.
WARRANTY
LIMITED 2 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of
anyone else that this product
at the time of its sale by Leviton is free of defects in materials and
workmanship under normal and proper use for two years from the purchase date.
Leviton’s only obligation is to correct such defects by repair or replacement,
at its option. For details visit www.leviton.com or call
1-800-824-3005. This warranty excludes
and there is disclaimed liability for labor for removal of this product or
reinstallation. This warranty is void if this product is installed improperly
or in an improper environment, overloaded, misused, opened, abused, or altered
in any manner, or is not used under normal operating conditions or not in
accordance with any labels or instructions. There are no other or implied
warranties of any kind, including merchantability and fitness for a particular
purpose, but if any implied warranty is required by the applicable
jurisdiction, the duration of any such implied warranty, including
merchantability and fitness for a particular purpose, is limited to two years.
Leviton is not liable for incidental, indirect, special, or consequential
damages, including without limitation, damage to, or loss of use of, any
equipment, lost sales or profits or delay or failure to perform this warranty
obligation. The remedies provided herein are the exclusive remedies under this
warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call
- 1-800-824-3005 (U.S.A. Only)
- 1 800 405-5320 (Canada Only)
- www.leviton.com
FCC
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
IC STATEMENT
This device complies with Industry Canada licence-exempt RSS standard(s).
Operation is subject to the following two conditions:
- this device may not cause interference, and
- this device must accept any interference, including interference that may cause undesired operation of the device.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should
contact Leviton in writing at Leviton Manufacturing of Canada Ltd to the
attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire
(Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
FAQs
What is the Leviton GUSB1-W Smart Lock Wall Charger Outlet?
The Leviton GUSB1-W is a Smart Lock Wall Charger Outlet that combines the functionality of a USB charger with a smart lock, offering both charging capabilities and enhanced security features.
How does the USB charging feature work?
The USB charging feature of the Leviton GUSB1-W allows users to conveniently charge their devices directly from the wall outlet, eliminating the need for separate chargers or adapters.
Is the Leviton GUSB1-W compatible with common USB devices?
Yes, the Leviton GUSB1-W is designed to be compatible with a wide range of common USB devices, including smartphones, tablets, and other electronic gadgets.
Does the smart lock feature include keyless entry?
Yes, the Leviton GUSB1-W typically features keyless entry, allowing users to unlock the connected space using a PIN code or through a connected smart home system.
Can multiple user codes be programmed into the smart lock?
Yes, the smart lock function of the Leviton GUSB1-W often allows users to program multiple user codes, providing access to different individuals without the need for physical keys.
Is the Leviton GUSB1-W compatible with popular smart home platforms?
The Leviton GUSB1-W is designed to be compatible with various popular smart home platforms, enabling users to integrate it into their existing smart home systems for enhanced control and automation.
What security features are included in the smart lock?
The smart lock function of the Leviton GUSB1-W may include features such as auto-locking, tamper alerts, and other security measures to enhance the safety of the connected space.
Does the Leviton GUSB1-W require a hub for smart functionality?
Some models of the Leviton GUSB1-W may require a hub for full smart functionality, while others can operate independently. Users should check the product specifications for clarification.
What type of USB ports does the Leviton GUSB1-W have?
The Leviton GUSB1-W typically features standard USB Type-A ports, providing compatibility with a wide range of USB cables and devices.
Can the Leviton GUSB1-W be installed in existing electrical boxes?
Yes, the Leviton GUSB1-W is designed for installation in existing electrical boxes, making it a convenient upgrade for homes and offices.
Is there a warranty for the Leviton GUSB1-W Smart Lock Wall Charger Outlet?
The Leviton GUSB1-W may come with a limited warranty. Users are advised to check the product documentation or contact the manufacturer for warranty details.
Does the USB charger function work independently of the smart lock?
Yes, the USB charger function of the Leviton GUSB1-W can typically be used independently of the smart lock, allowing users to charge their devices without engaging the locking mechanism.
Video-Introduction
Download This PDF Link: Leviton AFTR1-W Smartlock Pro Receptacle Outlet User Manaul
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>