PANDUIT SBCT250 Tin Plated and Copper Split Bolt Connectors Instruction Manual
- June 14, 2024
- PANDUIT
Table of Contents
PANDUIT SBCT250 Tin Plated and Copper Split Bolt Connectors
Tin Plated and Copper Split Bolt Connectors
INSTALLATION INSTRUCTIONS
PART NUMBERS
- SBC8
- SBC6S
- SBC6SL
- SBC4S
- SBC4SL
- SBC3
- SBC2
- SBC1/0
- SBC2/0
- SBC3/0
- SBC250
- SBC350
- SBC500
- SBCT8
- SBCT6
- SBCT3
- SBCT2
- SBCT1/0
- SBCT2/0
- SBCT3/0
- SBCT250
- SBCT350
- SBCT500
NOTE:
SBCT8 THRU SBCT2/0 ARE UL LISTED FOR USE WITH BOTH ALUMINUM AND COPPER
CONDUCTORS
NOTE:
SBCT3/0 AND LARGER ARE
UL LISTED FOR USE WITH COPPER CONDUCTORS THEY CAN STILL BE USED ON ALUMINUM
CONDUCTORS,HOWEVER THEY ARE NOTE UL LISTED FOR THAT APPLICATION
- SBC8L
- SBC2L
- SBC750
- SBC1000
- SBCT750*
- SBCT1000*
NOTE:
CAN BE USED ON ALUMINUM CONDUCTOR,HOWEVER THEY ARE NOT UL LISTED FOR THAT
APPLICATION
NOTE:
OVER 500 kcmil NOT UL OR CSA LISTED FOR GROUNDING OR BONDING
COPPER CONDUCTOR
PART NUMBER
| COPPER CONDUCTOR| ****
REQUIRED TORQUE (IN-LB)
---|---|---
MAXIMUM RUN TO MAXIMUM TAP| MINIMUM RUN TO MINIMUM TAP| MAXIMUM RUN TO MINIMUM
TAP| MINIMUM EQUAL
RUN| TAP| RUN| TAP| RUN| TAP| RUN| TAP
SBC8| 8 STR
8 SOL
| 8 STR
8 SOL
| 10 STR
10 SOL
| 16 STR
16 SOL
| 8 STR
8 SOL
| 16 STR
16 SOL
| 10 STR
10 SOL
| 10 STR
10 SOL
| 80
SBCT8| 6 SOL| 6 SOL| 8 STR
8 SOL
| 14 STR
14 SOL
| 6 STR
6 SOL
| 14 STR
14 SOL
| 8 STR
8 SOL
| 8 STR
8 SOL
| 165
SBC6S| 6 SOL| 6 SOL| 8 STR
8 SOL
| 16 STR
16 SOL
| 6 SOL| 16 SOL| 8 STR
8 SOL
| 8 STR
8 SOL
| 165
SBC6SL
SBCT6| 6 STR
6 SOL
| 6 STR
6 SOL
| 8 STR
8 SOL
| 10 STR
10 SOL
| 6 STR
6 SOL
| 10 STR
10 SOL
| 8 STR
8 SOL
| 8 STR
8 SOL
| 165
SBC4S| 6 STR
6 SOL
| 6 STR
6 SOL
| 8 STR
8 SOL
| 14 STR
14 SOL
| 6 STR
6 SOL
| 14 STR
14 SOL
| 8 STR
8 SOL
| 8 STR
8 SOL
| 165
SBC4SL
SBC3| 4 STR
4 SOL
| 4 STR
4 SOL
| 6 STR
6 SOL
| 14 STR
14 SOL
| 4 STR
4 SOL
| 14 STR
14 SOL
| 8 STR
8 SOL
| 8 STR
8 SOL
| 275
SBCT3| 4 STR
4 SOL
| 4 STR
4 SOL
| 6 STR
6 SOL
| 10 STR
10 SOL
| 4 STR
4 SOL
| 10 STR
10 SOL
| 8 STR
8 SOL
| 8 STR
8 SOL
| 275
SBC2| 2 STR
2 SOL
| 2 STR
2 SOL
| 6 STR
6 SOL
| 14 STR
14 SOL
| 2 STR
2 SOL
| 14 STR
14 SOL
| 6 STR
6 SOL
| 6 STR
6 SOL
| 275
SBCT2| 2 STR
2 SOL
| 2 STR
2 SOL
| 6 STR
6 SOL
| 14 STR
14 SOL
| 2 STR
2 SOL
| 14 STR
14 SOL
| 6 STR
6 SOL
| 6 STR
6 SOL
| 275
SBC1/0| 1/0 STR
1/0 SOL
| 1/0 STR
1/0 SOL
| 2 STR
2 SOL
| 14 STR
14 SOL
| 1/0 STR
1/0 SOL
| 14 STR
14 SOL
| 4 STR
4 SOL
| 4 STR
4 SOL
| 385
SBCT1/0| 1/0 STR
1/0 SOL
| 1/0 STR
1/0 SOL
| 2 STR
2 SOL
| 10 STR
10 SOL
| 1/0 STR
1/0 SOL
| 10 STR
10 SOL
| 4 STR
4 SOL
| 4 STR
4 SOL
| 385
SBC2/0| 2/0 STR
2/0 SOL
| 2/0 STR
2/0 SOL
| 1 STR
1 SOL
| 14 STR
14 SOL
| 2/0 STR
2/0 SOL
| 14 STR
14 SOL
| 2 STR
2 SOL
| 2 STR
2 SOL
| 385
SBCT2/0| 2/0 STR
2/0 SOL
| 2/0 STR
2/0 SOL
| 1 STR
1 SOL
| 8 STR
8 SOL
| 2/0 STR
2/0 SOL
| 8 STR
8 SOL
| 2 STR
2 SOL
| 2 STR
2 SOL
| 385
SBC3/0| 3/0 STR
3/0 SOL
| 3/0 STR
3/0 SOL
| 2/0 STR| 8 STR| 3/0 STR
3/0 SOL
| 8 STR
8 SOL
| 1 STR
1 SOL
| 1 STR
1 SOL
| 500
SBCT3/0| 3/0 STR
3/0 SOL
| 3/0 STR
3/0 SOL
| 2/0 STR
2/0 SOL
| 8 STR
8 SOL
| 3/0 STR
3/0 SOL
| 8 STR
8 SOL
| 1 STR
1 SOL
| 1 STR
1 SOL
| 500
SBC250| 250 STR| 250 STR| 4/0 STR
4/0 SOL
| 8 STR
8 SOL
| 250 STR| 8 STR| 1 STR
1 SOL
| 1 STR
1 SOL
| 650
SBCT250
SBC350| 350 STR| 350 STR| 350 STR
350 SOL
| 1/0 STR
1/0 SOL
| 350 STR| 1/0 STR| 2/0 STR
2/0 SOL
| 2/0 STR
2/0 SOL
| 650
SBCT350| 350 STR| 350 STR| 350 STR| 1/0 STR| 350 STR| 1/0 STR| 2/0 STR
2/0 SOL
| 2/0 STR
2/0 SOL
| 650
SBC500| 500 STR| 500 STR| 500 STR
500 SOL
| 2/0 STR
2/0 SOL
| 500 STR| 2/0 STR| 300 STR| 300 STR| 825
SBCT500| 500 STR| 500 STR| 400 STR| 2/0 STR| 500 STR| 2/0 STR| 300 STR| 300
STR| 825
PART NUMBER
| COPPER CONDUCTORS| MAX CONDUCTOR| ****
REQUIRED TORQUE (IN-LB)
---|---|---|---
RANGE OF EQUAL RUN & TAP| ****
MIN TAP WITH ONE MAX MAIN
| COPPERWELD
MIN.| MAX.| STR.| TYPE A
SBC8L| 16 STR| 8 STR| 16 STR| —| —| 80
SBC2L| 6 SOL| 2 STR| 14 STR| 3 No. 7| 3A| 275
SBC750| 350 kcmil| 750 kcmil| 8 SOL| 19 No. 5| —| 1000
SBCT750| 250 kcmil| 750 kcmil| 2/0 STR| 19 No. 5| —| 1000
SBC1000| 500 kcmil| 1000 kcmil| 8 SOL| —| —| 1100
SBCT1000| 350 kcmil| 1000 kcmil| 4/0 STR| —| —| 1100
For Technical Support: www.panduit.com/resources/install_maintain.asp
E-mail: cs@panduit.com
Fax: 708-444-6993
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>