SEELEY KACV125D1S Invertair True Inverter Add On Cooling Unit Owner’s Manual
- June 15, 2024
- SEELEY
Table of Contents
- SEELEY KACV125D1S Invertair True Inverter Add On Cooling Unit Owner’s
- IMPORTANT
- MAIN COMPONENTS
- INTRODUCTION & SAFETY
- MAGIQTOUCH CONTROLLER® SETTINGS MENU
- OPERATION
- MAINTENANCE & SERVICE
- MAINTENANCE SCHEDULE
- CHECK BEFORE CALLING FOR SERVICE
- OPERATION TIPS
- TROUBLESHOOTING GUIDE
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SEELEY KACV125D1S Invertair True Inverter Add On Cooling Unit Owner’s
Manual
KACV125D1S / KCHV125D1B
KACV140D1S / KCHV140D1B
KACV160D1S / KCHV160D1B
IMPORTANT
As with any product that has moving parts or is subject to wear and tear, it is VERY IMPORTANT that you maintain your air conditioner and have it regularly serviced. Accordingly, it is a condition of warranty cover for your air conditioner that you comply with all of the maintenance and service requirements set out in this manual. Compliance with these requirements will prolong the life of your air conditioner. Furthermore, it is also a condition of warranty cover that the Maintenance Schedule in the manual is filled out (by signing and dating it in the places indicated) when the item is completed. ANY FAILURE TO CARRY OUT THE REQUIRED MAINTENANCE AND SERVICING, AND ANY FAILURE TO FILL OUT THE MAINTENANCE SCHEDULE, WILL VERY LIKELY VOID YOUR WARRANTY.
(For complete warranty terms, refer to the separate Warranty Booklet sold with
the product. Alternatively, visit
https://www.seeleyinternational.com/warranty/ to download the terms.
Warranty terms are subject to property access and industry safety standards.)
WARNING! Failure to install and commission the product in compliance with these instructions, or failure to do the job properly and competently, may void the customer’s warranty. Further, it could expose the Installer and/or the Retailer to serious liability.
MAIN COMPONENTS
Indoor and Outdoor unit operating temperature range:
INTRODUCTION & SAFETY
Congratulations on purchasing a new Braemar Invertair™ – True Inverter Add-On Cooling unit!
Please keep this Manual and the Warranty Booklet in a safe place, along with the original purchase documents, plus all relevant installation work performed. Please register the Warranty straight away, by following the steps set out in the Warranty Booklet.
The Braemar Invertair™ – True Inverter Add-On Cooling unit is a refrigerated
cooling only, split type air conditioning system, designed specifically for
connection to a Braemar “T
TQM Extra Air” Series gas ducted heating unit, using MaglQtouch Controller.
The installer must read the Installation Manual before installing the Braemar InvertairTM
True Inverter Add-On Cooling unit. The home owner/user should read the Owner’s Manual before operating the unit.
To ensure the warranty on the unit is continued and valid, the unit must be checked and serviced by the home owner/user as per the requirements in the Maintenance & Service section and the Maintenance Schedule. This will also prolong the life of your air conditioner.
The home owner/user should regularly check the Air Inlet side of the Outdoor unit (see the diagram on page 1) to ensure grass, leaf and other matter are not drawn into or onto the Inlet side of the Outdoor unit. Restriction to the air flow across the coil will reduce the system’s capacity, and result in high operation pressures and excessive operating costs
A return air filter MUST be installed by the installer at the return air grille. The air filter should be inspected and cleaned at least every two weeks during summer or other periods when the Braemar Invertair – True Inverter Add-On Cooling unit is used.
Note: the manufacturer recommends that low level return air grilles are installed
Important! THE AUSTRALIAN GREENHOUSE OFFICE HAS ISSUED VARIOUS REGULATIONS ON THE USE AND DISPOSAL OF REFRIGERANTS IN THE UNIT. FAILURE TO FOLLOW THESE REGULATIONS MAY HARM THE ENVIRONMENT AND COULD LEAD TO THE IMPOSITION OF SUBSTANTIAL FINES. WHERE SPECIFIED, ONLY QUALIFIED AND LICENSED TECHNICIANS SHOULD PERFORM WORK ON THIS UNIT, FAILING WHICH THE WARRANTY ON THE UNIT WILL BE VOID.
WARNING! This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
If the supply cord is damaged, it must be replaced by a Seeley service agent
or similarly qualified person in order to avoid a hazard.
Any unventilated area where the appliance is installed shall be so constructed
that should any refrigerant leak, it will not stagnate so as to create a fire
or explosion hazard
Ducted systems which have outlets in rooms of areas less than MINIMUM ROOM AREA shall not have continuously open flames (i.e. an operating gas appliance) or other potential ignition source (i.e. operating electric heater or hot surface).
Auxiliary devices which may be a potential ignition source shall not be installed in the duct work.
Examples of such potential ignition sources are hot surfaces with a temperature exceeding 7000C and electric switching devices. Only auxiliary devices approved by Seeley International or declared suitable with the refrigerant shall be installed in connecting ductwork.
MAGIQTOUCH CONTROLLER® SETTINGS MENU
Your MagIQtouch Controller contains a settings menu which gives you access to information about your Braemar Invertair™ – True Inverter Add-On Cooling unit and to extra functions including:
ABOUT APPLIANCE
Access information about the appliances installed in your system.
COOLER SELECTION
If you have both an Evaporative Cooler and Invertair™ True Inverter Add-On
Cooling unit installed, you can select which product to use for cooling mode.
MIN/MAX SET TEMPERATURE
You can change the minimum and maximum temperature displayed on your slider,
depending on what temperature range you prefer your system to work within.
ROOM FAN RUN-ON TIME
You can select whether to have the fan on Time” when the compressor stops.
Note! There are some settings that are just for trained service agents or
installers. You won’t be able to access any of these options without a pin
code.
Here’s a brief visual guide to get you started quickly!
Refer to the MagIQtouch Wall Control Owner’s Manual for detailed instructions.
STEP 1
Activate screen.
OPERATION
Your Braemar InvertairTM – True Inverter Add- On Cooling unit has been designed and built with reliable, quality components. To ensure many years of trouble free, dependable service please read the following pages very carefully, and please ensure that you follow all of the instructions.
Please refer to your Braemar Ducted Gas Heater Home Owner’s Manual for the setting and operation of your Braemar InvertairTM – True Inverter Add-On Cooling unit.
REFRIGERATED COOLING ZONING
TQ3 Series
The TQ3 Series of Braemar Ducted Gas Heaters are not designed for zoning, and
when operated all outlets will be open for heating. If a Braemar InvertairTM –
True Inverter Add-On Cooling unit is connected, then when it is operating all
outlets will be open for cooling. Accordingly, if you choose to have a zoning
control system fitted to your TQ3 Series Heater, then because it has not been
designed for zoning, you may be disappointed with the heating and the cooling
performance.
However, any issues will need to be referred back to the supplier and/or installer of the zoning control system.
CONNECTION TO OTHER DUCTED GAS HEATER BRANDS
The Braemar InvertairTM – True Inverter Add- On Cooling unit is not suitable
to be connected to other brands of ducted gas heaters.
MAINTENANCE & SERVICE
AIR FILTER
It is important to check and clean the air filter as per the Maintenance
Schedule below. A dirty air filter will not allow the correct amount of clean
air to pass through your air conditioner, resulting in poor performance and
increased running costs. You should ask the installer to show you where the
air filter is located.
To clean the air filter, it should be removed and then cleaned with a water hose using moderate pressure, spraying from the internal side. Make sure it is completely dry before refitting it. If it is very dirty and cannot be cleaned, the filter will need replacing. You should never operate the air conditioner without the air filter in place.
INDOOR COIL (Refer page 2)
The indoor coil does not have any moving parts, but it is advisable to have the drain and duct connections checked on an annual basis (as set out in the Maintenance Schedule below). Drains can become blocked by insects, and rats have been known to chew through the drain to get to the water in the pipe.
OUTDOOR UNIT (Refer page 2)
The Outdoor unit has either one or two fans, and draws air through the
appliance to expel the heat generated during the cooling cycle. We recommend
checking that plants haven’t grown into or around the air intake or outlet,
along with other debris that may build up over time, namely, leaves and the
like.
REFRIGERANT
The refrigerant is the life blood of your air conditioning unit. Not only does
the correct refrigerant charge provide you with reliable and economical
cooling, it also provides the cooling for the compressor. A lack of
refrigerant, due to a leak, will cause the compressor to overheat and expire
prematurely. You will notice a decline in cooling effect and an increase in
power consumption. Therefore, having a qualified, licensed technician service
your air conditioner will save you money in the long term.
PLEASE REFER TO THE NEXT PAGE FOR THE MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
Please NOTE! the Maintenance Schedule covers Year 1 to Year 5. To preserve your investment for many years afterwards, we strongly recommend that you continue to maintain and service the Braemar Invertair™ – True Inverter Add-On Cooling unit as per the items and frequency set out in the Schedule, and as indicated elsewhere in this manual.
CHECK BEFORE CALLING FOR SERVICE
Before calling Service, please check the following:
-
If a new installation, please contact the installer to ensure the installation has been completed and commissioned.
-
Your system MUST have a MagIQtouch Controller, if not, please refer back to your installer.
-
Does the display show any information?
a. If yes, go to Step 4.
b. If No, check power supply to Heater.
I. Repair power supply and set time and day.
II. Follow procedure in your Braemar Ducted Gas Heater Owner’s Manual on how to set up and operate your system.
III. After completing the above checks and rectifying any fault as required, if your appliance continues not to operate, please call Braemar Service. -
Is the MaglQtouch Controller set to “COOL” mode?
a. If Yes,
l. Is there air coming out of the outlets in your home?
ll. If No,
1. Ensure MaglQtouch Controller is set to COOL and the set point is below the room temperature.
2. Check and clean return air filter.
3. Check and open outlets and/or zones.
4. Check duct for disconnection or damage.
5. After the above have been checked and repaired as required, please call Braemar Service.
b. If Yes, continue below:
l. Check Circuit Breaker and/or Isolator to Invertair Outdoor unit, Invertair Indoor unit and Ducted Gas Heater. If electricity is available, the unit may be timing out on the inbuilt safety timer. Wait 5 minutes and re-check. ll. If fan is blowing on Outdoor unit, check large pipe’s temperature, this pipe should be cold to touch. If not cold, please have the installer check for refrigerant leaks before calling Braemar Service. -
Does the Invertair Add-On Cooling unit run for short periods of time?
1. If No, refer above
2. If Yes,
a. Check to ensure enough outlets are open.
b. Check and clean return air filter.
c. The InvertairTM True Inverter Add- On Cooling unit has special safety features built in to protect the system.
It will switch off the Add-On Cooling unit output signal when the supply air temperature drops below a pre-set minimum value and will restart after the supply air temperature rises by a pre-set value.
d. Call the installer to check you have the required number of outlets open.
e. Once the above have been checked and repaired as required, call Braemar Service.
Please NOTE!
It is important that you recognise whether the fault is with the Ducted Gas
Heater or if the fault is with the Braemar Invertair™ – True Inverter Add-On
Cooling unit. For prompt,
before calling the number below. 1300 650 644
When calling the Warranty Service number, please ensure you have your model and serial number available, along with date of purchase, and if possible a description of the problem.
OPERATION TIPS
The following events may occur during normal operation:
The following events may occur during normal operation
-
Protection of the air conditioner.
Compressor protection
• The compressor cannot restart for 3 minutes after it stops.
• The supply air drops below a pre-determined set point; this prevents the indoor coil from freezing. -
A white mist coming out from the Indoor unit.
• A white mist may generate due to a large temperature difference between air inlet and air outlet on COOL mode in an indoor environment that has a high relative humidity -
Low noise of the air conditioner.
• You may hear a low hissing sound when the compressor is running or has just stopped
running.
This sound is the sound of the refrigerant flowing or coming to a stop.
• You can also hear a low “squeak” sound when the compressor is running or has just stopped running.
This is caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.
4. Dust is blown out from the Indoor unit.
This is a normal condition when the air conditioner has not been used for a
long time or during first use of the unit.
5. A peculiar smell comes out from the Indoor unit.
This is caused by the Indoor unit giving off smells permeated from building
material, from furniture, smoke (for example if someone is cooking food), or
from the duct work.
6. FAN operation during COOL mode.
When indoor air temperature reaches the setting on the MaglQtouch Controller,
the compressor will stop operating and after approximately 60 seconds the
indoor fan will stop blowing air. When the room temperature rises back to the
set point, the indoor fan and the compressor will start again.
TROUBLESHOOTING GUIDE
Note!
Seeley International strives for continuous product improvements, therefore
specifications are subject to change without notice. Unit colour may vary
slightly from that depicted in this booklet. Installation and commissioning of
this system to the manufacturer’s specification, and compliance with industry
standards, and local, state and national regulatory codes, are the
responsibility of the installer.
Information in this booklet was true and correct at the time of publishing. E & OE.
Warranty Service Australia
1300 650 644
It is the policy of Seeley International to introduce continuous product
improvement.
Accordingly, specifications are subject to change without notice.
Please consult with your dealer to confirm the specifications of the model
selected.
Read More About This Manual & Download PDF:
References
- Seeley International - World Leading Air Conditioners
- Warranty/Maintenance Information - Seeley International
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>