SEELEY INTERNATIONAL CW-80 Multi Magic Supply Duct Sensor User Manual

June 1, 2024
SEELEY INTERNATIONAL

SEELEY-INTERNATIONAL-logo

SEELEY INTERNATIONAL CW-80 Multi Magic Supply Duct Sensor

IMPORTANT!
READ THIS FIRST BEFORE COMMENCING INSTALLATION

This sensor measures the air temperature and relative humidity inside ducts. It is intended for use with a compatible CW-80 or CW-H cooler.

Input Range

  • Temperature: 0-10V = 0-50o C / 32-122o F
  • Relative Humidity: 0-10V = 0-100%

Recommended Cable Specification
The sensor requires 24VDC power and 2 signal wires.

  • Instrumentation Cable with 4x 0.5mm2 (AWG 20) conductors;
  • Always route communication cables at least 300mm (12”) away from high-voltage cables and high-power machines.
  • Crossover high-power cables at right angles. 24VDC power can be supplied by the cooler (as shown) or a separate power supply (not included).

Cooler Input Terminals
Compatible CW-80 or CW-H coolers have a series of sensor input channels, configured in pairs and labelled S1/S2, S3/S4 (CW-H and CW-80) and S5/S6 (CW-80 only). Always set up the first channel (S1, S3 or S5) for temperature, and the second channel (S2, S4 or S6) for relative humidity.

EXAMPLE CW-80 FITMENT

SEELEY-INTERNATIONAL-CW-80-Multi-Magic-Supply-Duct-Sensor-fig-
\(1\)

EXAMPLE CW-H FITMENT

SEELEY-INTERNATIONAL-CW-80-Multi-Magic-Supply-Duct-Sensor-fig-
\(2\)

CONNECTING

After installation, use the LEFT/RIGHT buttons to navigate to the SENSORS screen on the cooler PLC screen. Highlight the first sensor input channel for the connected sensor (S1, S3 or S5). Press OK and use the DOWN button to select SPLY-T. Press OK to confirm. SPLY-H will automatically be selected for the second sensor input channel (S2, S4 or S6). Check the Temperature and R/H values on the cooler PLC screen are present and correct. Units can be changed between o C and o F in the PLC settings.

Warranty Service Australia
For outside Australia contact your local dealer. seeleyinternational.com  It is the policy of Seeley International to introduce continual product improvement. Accordingly, specifications are subject to change without notice. Please consult with your dealer to confirm the specifications of the model selected.