Bard CRV-F5 Wall Mount Ventilation Instruction Manual

June 13, 2024
Bard

Bard CRV-F5 Wall Mount Ventilation

Bard-CRV-F5-Wall-Mount-Ventilation-PRODUCT

Product Information

  • Product Name : Partial Flow Commercial Room Ventilator
  • Model : CRV-F5
  • Manufacturer : Bard Manufacturing Company, Inc.
  • Compatible with Bard Wall Mount Air Conditioner and Heat Pump Models : W3SAC, W4SAC, W5SAC, W42AC, W48AC, W60AC, W72AC, W42HC, W48HC, W60HC, C36HY, C42HY, C48HY, C60HY
  • Manual : 2100-751A
  • Supersedes : 2100-751
  • Date : 3-28-23 – Page: 1 of 23

Product Usage Instructions

  1. Unpacking
    • Upon receiving the equipment, compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
  2. General
    • The ventilator should only be installed by a trained heating and air conditioning technician.
    • These instructions are intended as a guide for the technician installing the ventilator package and not for the mechanically inclined owner to install the package.
  3. Ventilator Kit
    • The ventilator housing is shipped in one carton along with the following components
    • CRV-F5 ventilator
    • 7003-084 mist filters (2)
    • 7003-083 exhaust bug screen (1)
    • 539-405 intake sealing frames (2)
    • 3000-1622 wire assembly (1)
    • 1913-002-0808 8-1/2 foam strips (2)
    • 1913-002-0708 7-1/2 foam strips (4)
    • 1913-013-2708 foam gasket (1)
    • 543-223 lower block off plates (2)
    • 1012-086 screws (12)
    • 539-414 exhaust damper assembly (1)
    • 2100-751A installation instructions (1)

Please follow the installation instructions provided in the manual for proper installation and usage of the CRV-F5 ventilator. For specific information on blade adjustment, control system notes, and sequence of operation, refer to the corresponding sections in the manual.

Commercial Room Ventilator Model Nomenclature

Unpacking

  • Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
  • Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage (check parts list below). Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.

General

  • The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step-by-step procedure with which the mechanically inclined owner can install the package.
  • The ventilator housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions.

Ventilator kit includes

  1. (1) CRV-F5 ventilator
  2. (2) 7003-084 mist filters
  3. (1) 7003-083 exhaust bug screen
  4. (2) 539-405 intake sealing frames
  5. (1) 3000-1622 wire assembly
  6. (2) 1913-002-0808 8-1/2″ foam strips
  7. (4) 1913-002-0708 7-1/2″ foam strips
  8. (1) 1913-013-2708 foam gasket
  9. (2) 543-223 lower block off plates
  10. (12) 1012-086 screws
  11. (1) 539-414 exhaust damper assembly (1) 2100-751A installation instructions

Commercial Room Ventilator Features

  • Exhaust air damper – built in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings.
  • Actuator motor – 24 volt, power open, spring return with built in torque limiting switch.

Description
The CRV-F5 ventilator is designed to be used with the specific models with “letter” revision codes as designated on the front page of this installation instructions manual. The factory-installed vent
is denoted by the letter “M” in the unit model nomenclature.
The ventilator is an electromechanical vent system designed to provide fresh air to meet indoor air quality standards.

Models
When installed in the models listed on the front page, the CRV-F5 provides built-in exhaust provisions. When the damper blade opens to bring fresh air in, the damper also opens an exhaust relief. The exhaust air will flow into the condenser section of the unit. The condenser fan will help draw exhaust air out when it is operating with compressor in cooling or heat pump mode.

Basic Installation

WARNING
Electrical shock hazard.
Disconnect remote electrical power supply or supplies before servicing.
Failure to do so could result in electric shock or death.

WARNING
Exposed moving parts.
Disconnect electrical power before servicing.
Failure to do so could result in severe injury or amputation.

CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.

Disconnect all power to unit (see Figure 1).

  • Remove both side grilles (see FIgure 2).

  • Remove upper blower door and outer control panel cover (see Figure 3).

  • Remove blank off plates on both sides (behind side grilles) and discard (see Figure 4).

  • Remove exhaust blank off plate through return or through side intake openings (see Figure 5).

  • Install 1913-013-2708 gasket 5/8″ from bend as shown in Figure 6. Then install exhaust blade assembly using 10 screws (see Figure 7).

  • Remove both air filters and the low voltage inner control panel cover (see Figure 8).

  • FIGURE 8

      • Remove Air Filters and
  • Low Voltage Inner Control Panel Cover

  • Connect 3000-1622 wire assembly (see Figure 9). Snap the 4 pin connector into the opening next to the low voltage box and plug the 12 pin male connector into the female plug in the low voltage box.

  • Before installing vent, remove CRV from packaging and verify there is no damage. Install the vent from the side as shown in Figure 10. CRV can be installed from either side.

  • Set CRV on the exhaust partition (see Figure 5 on page 5) and slide in until flush with the side of the wall mount.

  • When the CRV is fully installed, the control plug should be centered in the plug access opening on the front panel of the CRV as shown in Figure 11.

  • From the front, through the filter opening, plug the CRV power plug into the control panel plug (see Figure 12).

  • IMPORTANT: Sharp edges—PPE required.

  • The CRV exhaust blade is fixed in the shipping position by the actuator blade stop (see Figure 13 top and side views). Proceed with caution as the actuator is spring loaded. Remove the blade stop to release the blade.

  • Set blade stop (see Figure 14) using airflow charts found on pages 9 thru 12.

  • With the exhaust damper blade fully closed, re-install the actuator blade stop. To adjust fresh air amount, loosen the screw on the actuator blade stop and slide the stop to the desired setting. Use the notches in the blade stop and marks on the actuator blade position label to correlate with the airflow settings. Tighten the screw.

  • Install the 539-405 intake sealing frame and the 543-223 lower block off plates (both sides) as shown in Figure 15. Install two (2) 1913-002-0708 7-1/2″ foam gaskets below the intake sealing frame (both sides).

  • Bend the two (2) sheet metal tabs in the condenser partition up to hold the bottom of the mist eliminator in place.

  • Install 7003-084 mist filters on both sides (see Figure 16). Then re-install the side grilles removed earlier.

  • Remove the front lower (condenser) grille and bend the two (2) sheet metal tabs in the condenser partition up to hold the bottom of the bug screen in place. Install two (2) 1913-002-0808 8-1/2″ foam gaskets to sides of cabinet (see Figure 17). Install the 7003-083 exhaust bug screen. Re-install grille.

  • Restore power to unit. The “A” terminal can now be energized to test blade operation. When blade testing is complete, disconnect power.

  • Install both filters, then re-install the inner control panel cover, outer control panel cover and upper blower door.

  • Restore power to unit.

Control System Notes

This ventilation package is capable of being set to meet the current ASHRAE specifications for minimum occupied airflow rates.

On/Off Operation
Energizing the A terminal in the low voltage connection box during occupied conditions will drive the fresh air damper to the fixed position selected as shown in Figure 14 on page 7.

Blade Adjustment for Desired Ventilator Air
The amount of ventilation air supplied by the commercial room ventilator is dependant on four factors.

  1. Return air duct static pressure drop.
  2. Supply air duct static pressure drop.
  3. Indoor blower motor speed.
  4. Damper blade open position setting.

Refer to the appropriate graph on pages 9, 10, 11 or 12 to determine the blade setting necessary to achieve the ventilation air required. Bard-CRV-F5-Wall-
Mount-Ventilation- \(19\) Bard-CRV-F5-Wall-Mount-
Ventilation- \(20\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(21\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(22\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(23\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(24\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(25\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(26\) Bard-CRV-F5-Wall-Mount-Ventilation-
\(27\)Bard-CRV-F5-Wall-Mount-Ventilation-
\(28\)

GRAPH 6
C36H AND C42H CRV-F5 Ventilation DeliveryBard-CRV-F5-Wall-Mount-Ventilation-
\(29\)Bard-CRV-F5-Wall-Mount-Ventilation-
\(30\)

GRAPH 7
C48H AND C60H CRV-F5 Ventilation Delivery

Bard-CRV-F5-Wall-Mount-Ventilation- \(31\)Bard-
CRV-F5-Wall-Mount-Ventilation- \(32\) FIGURE 18
Programmable Thermostat Connections for CRV with Single Stage Air Conditioners

Bard-CRV-F5-Wall-Mount-Ventilation- \(33\)

  1. Factory installed jumper. Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.
  2. Wire not needed below 15KW.
  3. Wire required for dehumidification models only.
  4. Do not connect “A” from thermostat if optional CO2 controller is used
  5. 10 VDC modulating C02 control signal for modulating ventilation 5 control (optional for ECON only – see vent instruction manuals)
  6. Change model configuration from heat pump to heat/cool. Must be configured to programmable and fan set to be programmed fan for the “A” output to function during scheduled occupied periods. Must be configured for multi-
  7. stage for Y1 output to be active 1st stage cooling. For dehumidification, must be configured for “No Economizer” for YO/D to be active for humidity control.
  8. Install jumper for 1 stage electric heat on units with more than 10KW
  9. Do not add these wires if setting up for modulating control. See note 5.
  10. Factory installed jumper. Remove jumper to activate Balanced Climate™ mode. 9 A 2-stage thermostat is recommended for Balanced Climate mode.Y1 Y2 jumper not present if economizer is factory installed. Units with economizers have balanced climate jumper in economizer, refer to economizer manual.

FIGURE 19
Programmable Thermostat Connections for CRV with 2-Stage Air Conditioners

Bard-CRV-F5-Wall-Mount-Ventilation- \(34\)

  1. Factory installed jumper. Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.
  2. Wire not needed below 15KW.
  3. Wire required for dehumidification models only.
  4. Do not connect “A” from thermostat if optional CO2 controller is used
  5. 10 VDC modulating C02 control signal for modulating ventilation 5 control (optional for ECON only – see vent instruction manuals)
  6. Change model configuration from heat pump to heat/cool. Must be configured to programmable and fan set to be programmed fan for the “A” output to function during scheduled occupied periods. Must be configured for multi-
  7. stage for Y1 output to be active 1st stage cooling. For dehumidification, must be configured for “No Economizer” for YO/D to be active for humidity control.
  8. Install jumper for 1 stage electric heat on units with more than 10KW
  9. Do not add these wires if setting up for modulating control. See note 5.
  10. Factory installed jumper. Remove jumper to activate Balanced Climate™ mode. A 3-stage thermostat is recommended for Balanced Climate mode. Must not be

FIGURE 20
Programmable Thermostat Connections for CRV with Heat Pumps

Bard-CRV-F5-Wall-Mount-Ventilation- \(35\)

  1. Factory installed jumper. Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.
  2.  Wire not needed below 15KW.
  3. Wire required for dehumidification models only.
  4. Do not connect “A” from thermostat if optional CO2 controller is used 0-10 VDC modulating C02 control signal for modulating ventilation control (optional for ECON only – see vent instruction manuals)
  5. Ensure model configuration is heat pump and not heat/cool. Must be configured to programmable and fan set to be programmed fan for the “A” output to function during scheduled occupied periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For dehumidification, must be configured for “No Economizer” for YO/D to be active for humidity control.
  6. Do not add these wires if setting up for modulating control.
  7. Factory installed jumper. Remove jumper to activate Balanced Climate TM Mode.
  8. A 2-stage thermostat is recommended for balanced climate mode. Y1 Y2 jumper
    not present if economizer is factory installed. Units with economizers have balanced
    climate jumper in economizer, refer to economizer manual. The jumper is factory removed in the unit and on jade for CHY models. Completestat not compatible with CHY models.

FIGURE 21
Non-Programmable Thermostat Connections for CRV with Single Stage Air Conditioners

Bard-CRV-F5-Wall-Mount-Ventilation- \(36\)

  1. Factory installed jumper. Remove jumper and connect 6 0 to N.C fire alarm circuit if emergency shutdown required.
  2. 2A Wire not needed below 15KW.
  3. 2B Install Jumper for 1 stage electric heat on units with more than 10KW.
  4. Wire required for dehumidification models only.
  5. For vent operation, add jumper if optional CO2 controller is not used. Vent will run while blower is energized.
  6. For ECON & CRV-V an additional wire change is required See install Manual.
  7. Do not add these wires if setting up for modulating control. See note 6.
  8. -10 VDC Modulating CO2 control signal for modulating ventilation control (Optional for ECON Only) – See vent installation manual.
  9. Jumper needs added.
  10. Thermostat will not work with units equipped with economizers.
  11. Factory installed jumper. Remove jumper to activate Balanced Climate™ Mode. A 2-stage thermostat is recommended for Balanced Climate mode. Y1 Y2 jumper not present if economizer is factory installed. Units with economizers have balanced climate jumper in economizer, refer to economizer manual.

FIGURE 22
Non-Programmable Thermostat Connections for CRV with 2-Stage Air Conditioners

Bard-CRV-F5-Wall-Mount-Ventilation- \(37\)

  1. Factory installed jumper. Remove jumper and connect 6 0 to N.C fire alarm circuit if emergency shutdown required.
  2. 2A Wire not needed below 15KW.
  3. 2B Install Jumper for 1 stage electric heat on units with more than 10KW.
  4. Wire required for dehumidification models only.
  5. For vent operation, add jumper if optional CO2 controller is not used. Vent will run while blower is energized.
  6. For ECON & CRV-V an additional wire change is required See install Manual.
  7. Do not add these wires if setting up for modulating control. See note 6.
  8. VDC Modulating CO2 control signal for modulating ventilation control (Optional for ECON Only) – See vent installation manual.
  9. Jumper needs added.
  10. Thermostat will not work with units equipped with economizers.
  11. Factory installed jumper. Remove jumper to activate Balanced Climate™ Mode. A 3-stage thermostat is recommended for Balanced Climate mode. Must not be removed if Econ is installed.

FIGURE 23
Non-Programmable Thermostat Connections for CRV with Heat Pumps

Bard-CRV-F5-Wall-Mount-Ventilation- \(38\)

  1. Factory installed jumper. Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.
  2. Wire not needed below 15KW.
  3. Wire required for dehumidification models only.
  4. For vent operation, add jumper if optional CO2 controller is not used. Vent will run while blower is energized.
  5. For ECON & CRV-V, an additional wire change is required.
  6. See install manual
  7. Do not add these wires if setting up for modulating control. See note 6.
  8. 0-10 VDC Modulating CO2 control signal for modulating ventilation control
  9. (Optional for ECON Only) – See vent installation manual.
  10. Jumper needs added.
  11. Thermostat will not work with units equipped with economizers. T4 pro not compatible with C**HY models
  12. Factory installed jumper. Remove jumper to activate Balanced Climate™ Mode.
  13. A 2-stage thermostat is recommended for Balanced Climate mode. Y1 Y2 jumper not present if economizer is factory installed. Units with economizers have balanced climate jumper in economizer, refer to economizer manual.
  14. The jumper is  factory removed in the unit and on jade for C**HY models

FIGURE 24
CRV-F* Wiring Diagram

Bard-CRV-F5-Wall-Mount-Ventilation- \(39\)

Sequence of Operation
On/Off ventilation options energize when the “A” low voltage strip terminal is energized signaling occupancy, and de-energize when “A” terminal is no longer receiving a 24VAC signal. The “G” low voltage strip terminal is used to operate the indoor blower for unit airflow.
The M On/Off CRV vent option is a damper blade operated by a 24VAC motor that when energized opens to a pre-adjusted setting. The airflow amount being brought in will be dependent on the blower speed during unit operation.

TABLE 1
WAC and WHC Unit Operation with M Ventilation Option

Bard-CRV-F5-Wall-Mount-Ventilation- \(40\) BC and B Climate − Balanced Climate

  1. Fan speed is selectable through the blower speed control terminal block. LO (default), MED or HI speeds can be used.
  2. Dehumidification operation is disabled when a call for heating or cooling occurs. Unit runs at Balanced Climate speed during dehumidification operation.

TABLE 2
W*SAC Unit Operation with M Ventilation Option

Bard-CRV-F5-Wall-Mount-Ventilation- \(41\)

BC and B Climate − Balanced Climate

  1. Fan speed is selectable through the blower speed control terminal block. LO (default), MED or HI speeds can be used.
  2. Dehumidification operation is disabled when a call for heating or cooling occurs. Unit runs at Balanced Climate speed during dehumidification operation.

TABLE 3
C**HY Unit Operation with M Ventilation Option

Bard-CRV-F5-Wall-Mount-Ventilation- \(42\)

FIGURE 25
Call for Ventilation With or Without Compressor Operation

Bard-CRV-F5-Wall-Mount-Ventilation- \(43\)

FIGURE 26
Call for Compressor or Fan Only with Ventilation Off

Bard-CRV-F5-Wall-Mount-Ventilation- \(44\)

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals