Bard IWSRL-B I-TEC Wall Sleeve for Recessed Louvers In Masonry Walls Instruction Manual
- June 5, 2024
- Bard
Table of Contents
IWSRL-B I-TEC Wall Sleeve for Recessed Louvers In Masonry Walls
Instruction Manual
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-747A
Supersedes: 2100-747
Date: 1-12-22
MIS-4156
GETTING OTHER INFORMATION AND PUBLICATIONS
The following publications can help when installing the wall sleeve. They can
usually be found at the local library or purchased directly from the
publisher. Be sure to consult the current edition of each standard.
The standard for the Installation of Air Conditioning and Ventilating Systems
…………………………………….ANSI/NFPA 90A
Standard for Warm Air Heating and Air Conditioning Systems …………ANSI/NFPA 90B
In addition, if may be helpful to consult the latest revision of the I-TEC
Installation Instructions manual 2100-549.
For more information, contact these publishers:
ACCA
Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: 202-483-9370
Fax: 202-234-4721| ANSI
American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: 212-642-4900
Fax: 212-302-1286
---|---
ASHRAE
American Society of Heating, Refrigeration
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: 404-636-8400
Fax: 404-321-5478| NFPA
National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: 800-344-3555
Fax: 617-984-7057
I-TEC WALL SLEEVE GENERAL INFORMATION
Shipping Damage
Upon receipt of equipment, the carton should be checked for external signs of
shipping damage. If damage is found, the receiving party must contact the last
carrier immediately, preferably in writing, requesting inspection by the
carrier’s agent.
General
The IWSRL-B Series Wall Sleeve is designed for use with the I-TEC Series heat
pump. The wall sleeve assembly consists of a large intake sleeve and a smaller
exhaust sleeve. Both sleeves are telescoping to adjust for different wall
depths. The wall sleeve is designed for use with 1″ to 4″ louver depths. As
shipped, the sleeve is ready for 1″ louver installation. See Figure 1 (page 4)
and Figure 2 (page 5).
Wall Sleeve Model No. | Wall Thickness | Standard Louver Depth |
---|---|---|
VASR L-B | 8 1? .5′ | 1″ |
These instructions explain the recommended method to install the wall sleeve.
The equipment covered in this manual is to be installed by trained service and
installation technicians.
These instructions and any instructions packaged with any separate equipment
required to make the entire air conditioning system should be carefully read
before beginning the installation.
While intended as a general recommended guide, these instructions do not
supersede any national and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is made.
Unpacking
- The smaller exhaust sleeve is attached to the weatherization plate with two (2) screws for shipping. Remove these screws (throw away) and set the exhaust sleeve assembly aside.
- Remove the inner telescoping sleeve (with the rubber gasket) from the larger inlet sleeve and set it aside.
- Remove the inlet sleeve, with the weatherization plate attached, from the carton and turn it over.
- Remove and save the four (4) screws attaching to the security plate.
FIGURE 1
IWSRL-B Wall Sleeve Dimensions
FIGURE 2
I-TEC and Wall Sleeve
INSTALLATION
Masonry Construction Walls
The IWSRL-B sleeve is meant to extend to the back of a recessed wall louver
that is fastened directly to the masonry or brick wall (see Figure 3). The
sleeve then extends to meet the back of the I-TEC unit. Sealant is used to
form a water-tight seal between all sleeve parts.
It is important to note that the louver must have a means of allowing water to
drain out of the sleeve area.
A slope is built into the bottom of the sleeve. The slope will allow any water
that enters the sleeve area to drain out through the louver.
Unit replacement applications may require user modification of the IWSRL-B.
Modifications may include provisions for water drainage and also the ability
to use existing wall louvers and openings.
Start the sleeve installation process by separating the two (2) pieces of the
outer telescoping sleeve assembly.
The inner portion of the sleeve assembly will not be used currently and can be
set off to the side. Next, remove the weatherization plate from the outer
telescoping sleeve assembly. The weatherization plate is attached to the outer
sleeve surface that will be flush with the back of the recessed louver.
Install the sleeve assembly into the wall opening with the outer sleeve
surface located where the back of the recessed wall louver will be. The outer
sleeve surface is meant to be attached to the back of the recessed wall
louver. Sealant must be used to join the outer sleeve and the louver to avoid
leakage while allowing water from the sleeve area to exit through the louver.
Insert the inner portion of the outer sleeve assembly and extend it to be ½”
beyond the inner wall surface.
The foam on the outer telescoping sleeve will be used to form a seal between
the outer telescoping sleeve assembly and the I-TEC unit.
FIGURE 3
Masonry Construction Installation
NOTE: If foamed insulation is used, the final location of the inner
sleeve must be determined since the foam insulation could lock the inner
sleeve into an incorrect location causing either an air leak between the
sleeve and back of the unit or preventing the unit from going as tight to the
wall or sill as desired. This must be done before the unit is placed and
before the inner portion of the intake, the sleeve is secured with screws to
the outer sleeve.
Insulating this space will prevent infiltration of any unwanted outside air
(see Figure 4).
If the I-TEC unit will be drained through the wall, the drain line must be
installed prior to setting the unit. Information for the drain installation is
provided in the installation manual supplied with the unit.
At this point, the following are options:
-
Install the weatherization plate if the I-TEC unit is not ready to be installed.
NOTE: The exhaust sleeve attaches to the I-TEC unit. Store it and any remaining mounting hardware in a safe location. -
Proceed with the attachment of the wall sleeve to the I-TEC unit.
FIGURE 4
Typical Installation
Attachment of Wall Sleeve to I-Tec Unit
Move the unit into place ensuring it is aligned side to side. Push it back
until the side panels are flush with the wall, or until the sides contact the
window sill—if that is the case. From the outside of the building, push the
inner sleeve inward until the foam gasket contacts the unit. Attach the sleeve
to the rear of the I-TEC using MIS-4159
the twelve (12) ¾” long self-tapping screws supplied with the sleeve. See
Figure 5 on page 8, Ref. B.
Tie the inner and outer sleeves together with the three (3) ¾” long self-
tapping screws on each side (Figure 5, Ref. A). Apply a bead of caulk to the
entire perimeter seam between the inner and outer sleeves (Figure 5, Ref. A).
The exhaust sleeve has three (3) screw slots in each side flange. Line these up with the screw engagement holes in the fan panel. Attach using six (6) ¾” long sheet metal screws supplied with the sleeve (Figure 5, Ref. C). Extend the sleeve out until it is flush with the louver attachment angles. Lock the sleeve in place using two (2) ½” long sheet metal screws on each side by shooting through the slot into a pre-punched hole (Figure 5, Ref. D).
FIGURE 5
Attachment of Wall Sleeve
Documents / Resources
| Bard
IWSRL-B I-TEC Wall Sleeve for Recessed Louvers In Masonry
Walls
[pdf] Instruction Manual
IWSRL-B, I-TEC Wall Sleeve for Recessed Louvers In Masonry Walls
---|---