Bard WETV-A5 Wall Mounted Energy Recovery Ventilator Instruction Manual

June 2, 2024
Bard

INSTALLATION INSTRUCTIONS
Manual 2100-470D
Wall Mount
Energy Recovery Ventilator
with Exhaust
Models:
WERV-A5 WERV-C5

For Use with Bard 3-1/2 Through 5 Ton
Wall Mount Air Conditioners and Heat Pumps

Model Nomenclature

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-

Electrical Specifications

Model Voltage Amps Control Voltage
WERV-A5 230/208 2.2 24V
WERV-C5 460 1.2 24V

Description

The wall mount energy recovery ventilator was designed to provide energy efficient, cost effective ventilation to meet I.A.Q. (indoor air quality) requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools, classrooms, lounges, conference rooms, beauty salons and others. It provides a constant supply of fresh air for control of airborne pollutants including CO2, smoke, radon, formaldehyde, excess moisture, virus and bacteria.
The ventilator incorporates rotary heat exchanger technology to remove both heat and moisture. It is designed as a single package which can be easily factory or field installed for new installations or retrofit to the Bard WA and WH series wall mounted units. The package consists of a unique rotary energy recovery cassette that can be easily removed for cleaning or maintenance. The WERV-*5 has two 13″ diameter heat transfer wheels for efficient heat transfer. The heat transfer wheels use a permanently bonded dry desiccant coating for total heat recovery.
Ventilation is accomplished with two blower/motor assemblies each consisting of a drive motor and dual blowers for maximum ventilation at low sound levels. The intake and exhaust blowers can be operated at the same speed (airflow rate) or different speeds to allow flexibility in maintaining desired building pressurization conditions. Factory shipped on medium intake and low exhaust. See Figure 8A to change speeds. The rotating energy wheels provide the heat transfer effectively during both summer and winter conditions. Provides required ventilation to meet the requirements of ASHRAE 62.1 standard.

NOTE: During operation below 5°F outdoor temperature, freezing of moisture in the heat transfer wheel can occur. Consult the factory if this possibility exists.
General Information
NOTE: This manual covers both factory and field installed WERV assemblies. For factory installed WERV, skip information pertaining to installation of the WERV system.
The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step-by-step procedure, with which the mechanically-inclined owner can install the package. The ventilator housing is shipped in one carton, which contains the following:

  1.  Energy recovery ventilator
  2. Service door
  3. Rain hood and mist eliminator
  4. Installation instructions

Unpacking
Upon receipt of the equipment, be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
Inspect the carton housing of each ventilator as it is received and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.

Performance and Application Data

– WERV-*5 Summer Cooling Performance (Indoor Design Conditions 75°DB/62°WB)

Winter Heating Performance
(Indoor Design Conditions 70°F DB)

Ambient OD Ventilation Rate
400 CFM 75% Eff. 325 CFM 76% Eff.
DB/°F WVL
65 2430
60 4860
55 7290
50 9720
45 12150
40 14580
35 17010
30 19440
25 21870
20 24300
15 26730

LEGEND:
VLT = V entilation Load – Total
VLS = V entilation Load – Sensible
VLL = V entilation Load – Latent
HRT = Heat Recover – Total
HRS = Heat Recovery – Sensible
HRL = Heat Recovery – Latent
WVL = W inter Ventilation Load
WHR = W inter Heat Recovery
NOTE: All performance data is based on operating intake and exhaust blower on the same speed.

Basic Installation (Field Installation)

  1. Unpack the ventilator assembly, which includes the integral ventilator with attached electrical harness and miscellaneous hardware.
    WARNING
    Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to OFF. Model| For Use with the Following Units| Electrical
    ---|---|---
    WERV-A5| WA38-A, -B WA42-A, -B WA48-A, -B WA49-A, -B WA60-A, -B WA61-A, -B| SH38-A, -B SH43-A, -B SH49-A, -B SH61-A, -B WH42-A, -B WH48-A, -B WH60-A, -B| 230/208
    1 or 3 Phase
    WERV-C5| WA38
    -C WA42-C WA48-C WA49-C WA60-C WA61-C| SH38-C SH43-C SH49-C SH61-C WH42-C WH48-C WH60-C| 460
    3 Phase

**CAUTION**
Be sure the correct model and voltage energy recovery ventilator is used with the correct air conditioner or heat pump to ensure correct voltage compatibility.

  1. Remove exhaust blower assembly from back of ventilator and discard shipping plate (see Figure 1).

  2. Remove the existing exterior blower access and  service access panels on the Bard wall mount unit. Save the blower access panel and discard service access panel (see Figure 2).

  3. Remove and save existing unit return air filter. Remove and discard the exhaust cover plate and remove center screw from condenser grill (see Figure 3).

  4. Install exhaust blower assembly in exhaust opening and secure with four (4) screws. Position 4-pin connector so it is accessible (see Figure 4).

  5. Install ventilator into the unit to the left side clearing the right filter bracket. Once the ventilator is fully inserted, slide the ventilator to the right until it is tight against the back of the control panel (see Figure 5).
    IMPORTANT: Position front lip of ventilator under front grille and on top of condenser partition (see Figure 5 inset). This is important to ensure proper drainage  of any water entering damper assembly.

  6. Remove access panel and plug in exhaust blower (see Figure 5). Replace access panel.

  7. Open control panel to gain access to unit low voltage terminal block. (Ensure all power is OFF prior to opening the control panel.)

  8. Route electrical harness leads through the 7/8″ bushing in control panel into low voltage box (see Figure 5).

  9. Connect black lead with fork terminal to terminal strip terminal C, orange lead to terminal G and brown/white lead to F or O1 depending if heat pump or air conditioner (see Figure 6 and wiring diagram).
    NOTE: These 24 volt control wires control the starting and stopping of the energy recovery  ventilator and can be independentlycontrolled by an energy management control or timer. See Control Wiring on page 14 for suggested control schemes.

  10. Remove female plug of high voltage wiring harness from the heat recover assembly and snap into unit control panel. Wire to terminal block. (See Figure 6 and wiring diagram.)

  11. Plug male plug from female at side of control panel (see Figures 5).

  12. Close control panel cover.

  13. Replace filter and one (1) screw in condenser grille (see Figure 3).

  14. Ventilator checkout:
    A. Resupply power to unit.
    B. Energize the evaporator blower by switching thermostat to the manual fan position with Heat/Cool in OFF position.
    C. Ventilator heat transfer wheels should rotate slowly (49 RPM). Intake and exhaust blowers should run (see Figure 8).
    D. De-energize the evaporator blower. Energy recovery wheels and fresh air and exhaust air blowers should stop.
    E. This completes ventilator checkout.

  15. See Recommended Control Sequences on page 14 for permanent connection of the orange control wire that was connected to G for checkout.

  16. Re-install the blower access panel at top of unit and secure with sheet metal screws (see Figure 2).

  17. Replace the lower service access panel with the new panel provided. Attach air intake hood with screws provided (see Figure 7). Be sure to insert the top flange of the air intake hood into and through the slot in the service door and between the door and insulation to prevent bowing of the door.

  18. Apply Certification label, included with installation instructions, next to unit serial plate.

  19. Ventilator is now ready for operation.

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig1

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig2

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig3

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig4

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig5

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig6

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig7

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig8

Basic Installation (Factory Installed Versions)

  1. Remove blower access door and service door.
    Remove filter located above air circulation blower. Install filter.

  2. Remove and install air intake hood. Refer to Item 16 of Basic Installation (Field Installation).

  3. Refer to Control Wiring for suggested control schemes for the WERV.

  4. After wiring, replace all panels.
    Control Wiring
    The WERV comes from the factory with the low voltage control wires not wired into the wall mount low voltage terminal strip. Care must be taken when deciding how to control the operation of the ventilator. When designing the control circuit for the ventilator, the following requirements must be met.

Control Requirements

  1. Indoor blower motor must be run whenever the WERV is run.
  2. Select the correct motor speed tap in the WERV. Using Table 1, determine the motor speed needed to get the desired amount of ventilation air needed. For instance, do not use the high speed tap on a WERV-A5 if only 200 CFM of ventilation air is needed; use the low speed tap. Using the high speed tap would serve no useful purpose and significantly affect the overall efficiency of the air conditioning system. System operating cost would also increase.
  3. Run the WERV only during periods when the conditioned space is occupied. Running the WERV during unoccupied periods wastes energy, decreases the expected life of the WERV and can result in a large moisture buildup in the structure. The WERV removes 60 to 70% of the moisture in the incoming air, not 100% of it. Running the WERV when the structure is unoccupied allows moisture to build up in the structure because there is little or no cooling load. Thus, the air conditioner is not running enough to remove the excess moisture being brought in. Use a control system that in some way can control the system based on occupancy.

IMPORTANT **
Operating the WERV during unoccupied periods can result in a build up of moisture in the structure.

Recommended Control Sequences
Several possible control scenarios are listed below:

  1. Use a programmable electronic thermostat with auxiliary terminal to control the WERV based on daily programmed occupancy periods. Bard markets and recommends the White-Rodgers 1F93-380 (Bard P/N 8403-049) programmable electronic thermostat for air conditioner applications, and the White-Rodgers 1F93-380 (Bard P/N 8403-049) programmable electronic thermostat for heat pump applications (see Figure 9).
  2. Use a motion sensor in conjunction with a mechanical thermostat to determine occupancy in the structure. Bard markets the CS2000A1 for this use (see Figures 10 and 11).
  3. Use a DDC control system based on a room occupancy schedule to control the WERV.
  4. Tie the operation of the WERV into the light switch. The lights in a room are usually on only when occupied.
  5. Use a manual timer that the occupants turn to energize the WERV for a specific number of hours.
  6. Use a programmable mechanical timer to energize the WERV and indoor blower during occupied periods of the day.

Ventilation Airflow

The WERV-A5 and WERV-C5 are equipped with a 3-speed motor to provide the capability of adjusting the ventilation rates to the requirements of the specific application by simply changing motor speeds.

TABLE 1

Ventilation Air (CFM)


Model

| High Speed (Black)| Medium Speed (Blue)| Low Speed (Red)
WERV-A5 WERV-C5| 450| 375| 300

The units are set from the factory with the exhaust blower on the low speed and the intake blower on medium speed. Moving the speed taps located in the control panel can change the blower speed of the intake and exhaust (see Figure 8A).

WARNING
Open disconnect to shut all power OFF before doing this. Failure to do so could result in injury or death due to electrical shock.

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig9

Energy Recovery Ventilator Maintenance

General Information
The ability to clean exposed surfaces within air moving systems is an important design consideration for the maintenance of system performance and air quality. The need for periodic cleaning will be a function of operating schedule, climate and contaminants in the indoor air being exhausted and in the outdoor air being supplied to the building. All components exposed to the airstream, including energy recovery wheels, may require cleaning in most applications.
Rotary counterflow heat exchanges (heat wheels) with laminar airflow are “self-cleaning” with respect to dry particles. Smaller particles pass through; larger particles land on the surface and are blown clear as the flow direction is reversed. For this reason, the primary need for cleaning is to remove films of oil-based aerosols that have condensed on energy transfer surfaces. Buildup of material over time may eventually reduce airflow. Most importantly, in the case of desiccant-coated (enthalpy) wheels, such films can close off micron- sized pores at the surface of the desiccant material, reducing the efficiency, with which the desiccant can absorb and desorb moisture.
Frequency
In a reasonably clean indoor environment such as a school, office building or home, experience shows that reductions of airflow or loss of sensible (temperature) effectiveness may not occur for 10 or more years. However, experience also shows that measurable changes in latent energy (water vapor) transfer can occur in shorter periods of time in commercial, institutional and residential applications experiencing moderate occupant smoking or with cooking facilities. In applications experiencing unusually high levels of occupant smoking, such as smoking lounges, nightclubs, bars and restaurants, washing of energy transfer surfaces, as frequently as every 6 months,
may be necessary to maintain latent transfer efficiency. Similar washing cycles may also be appropriate for industrial applications involving the ventilation of high levels of smoke or oil-based aerosols such as those found in welding or machining operations, for example. In these applications, latent efficiency losses of as much as 40% or more may develop over a period of 1 to 3 years.
Cleanability and Performance
In order to maintain energy recovery ventilation systems, energy transfer surfaces must be accessible for washing to remove oils, grease, tars and dirt that can impede performance or generate odors. Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water molecules. The continued ability of an enthalpy wheel to transfer latent energy depends upon the permanence of the bond between the desiccant and the energy transfer surfaces. Bard wheels feature silica gel desiccant permanently bonded to the heat exchange surface without adhesives; the desiccant will not be lost in the washing process. Proper cleaning of the Bard energy recovery  wheel will restore latent effectiveness to near original performance.
Maintenance Procedures
NOTE: Local conditions can vary and affect the  required time between routine maintenance procedures; therefore, all sites (or specific units at a site) may not have the same schedule to maintain acceptable performance. The following timetables are recommended and can be altered based on local experience.
Quarterly Maintenance

  1. Inspect mist eliminator/prefilter and clean if necessary. This filter is located in the fresh air intake hood on the front of the unit. This is an aluminum mesh filter and can be cleaned with water and any detergent not harmful to aluminum.

  2. Inspect wall mount unit filter and clean or replace as necessary. This filter is located either in the unit, in a return air filter grille assembly, or both. If in the unit it can be accessed by removing the lower service door on the front of the unit. If in a return air filter grille, by hinging the grille open to gain access.

  3. Inspect energy recovery ventilator for proper wheel rotation and dirt buildup. This can be done in conjunction with Item 2 above. Energize the energy recovery ventilator after inspecting the filter and observe for proper rotation and/or dirt buildup.

  4. Recommended energy recovery wheel cleaning procedures follow: Disconnect all power to unit. Remove the lower service door of the wall mount unit to gain access to the energy recovery ventilator.

  5. Remove the front access panel on the ventilator. Unplug amp connectors to cassette motors. Slide energy recovery cassette out of ventilator.

  6. Use a shop vacuum with brush attachment to clean both sides of the energy recovery wheels.

  7. Reverse shop vacuum to use as a blower and blow out any residual dry debris from the wheel.
    NOTE: Discoloration and staining of the wheel does not affect its performance. Only excessive buildup of foreign material needs to be removed.

  8. If any belt chirping or squealing noise is present, apply a small amount of LPS-1 or equivalent dry film lubricant to the belt.

Annual Maintenance

  1. Inspect and conduct the same procedures as outlined under Quarterly Maintenance.

  2. To maintain peak latent (moisture) removal capacity, it is recommended that the energy recovery wheels be sprayed with a diluted nonacid based evaporator coil cleaner or alkaline detergent solution such as 409.
    NOTE: Do not use acid-based cleaners, aromatic solvents, temperatures in excess of 170°F or steam. Damage to the wheel may result.
    Do not disassemble and immerse the entire heat wheel in a soaking solution, as bearing and other damage may result.

  3. Rinse wheel thoroughly after application of the cleaning solution and allow to drain before reinstalling.

  4. No re-lubrication is required to heat wheel bearings of the drive motor or to the intake and exhaust blower motors.

  5. If any belt chirping or squealing noise is present, apply a small amount of LPS-1 or equivalent dry film lubricant to the belt.

Bard WETV A5 Wall Mounted Energy Recovery Ventilator-
fig11

Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Manual : 2100-470D
Supersedes: 2100-470C
Date: 11-18-22