MEAN WELL DDR-120A-12 120W DIN Rail Type DC-DC Converter Owner’s Manual

June 13, 2024
MEAN WELL

120W DIN Rail Type DC-DC Converter
DDR-120 series

User’s Manual

https://www.meanwell.com/Upload/PDF/DDR-120,240,480_EN.pdf

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - icon
1 MEAN WELL DDR 120A 12 120W DIN
Rail Type DC DC Converter - icon 2

DDR-120A-12 120W DIN Rail Type DC-DC Converter

Features

  • Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard Width only 32mm
  • 2:1 wide input range
  • -40~+70C wide working temperature
  • 150% peak load capability
  • DC output adjustable
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Protections: Short circuit / Overload / Over voltage / Input reverse polarity / Input under voltage protection
  • 4KVdc I/O isolation(Reinforced isolation)
  • 3 years warranty

Applications

  • Bus, tram, metro or railway system
  • Industrial control system
  • Semi-conductor fabrication equipment
  • Factory automation
  • Electro-mechanical
  • Wireless network
  • Telecom or datacom system

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

DDR-120 series is a120W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra slim width (32mm), 2:1 wide input voltage, fanless design, -40~+70 C wide operating temperature, 4KVdc I/O isolation, 150% peak load, adjustable output voltage and full protective functions.
This series of models has various input options: 9~18V/16.8~33.6V /33.6~67.2V /67.2~154V and various output options: 12V /24V/ 48V and can be used for industrial & railway control, security control, communication system and other fields. Suitable applications include DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…etc.

Model Encoding

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - model
encoding

SPECIFICATION

MODEL| DDR-120A-12| DDR-120A-24| DDR-120A-48| DDR-12013-12| DDR-120B-24| DDR-120B-48
---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 24V| 48V| 12V| 24V| 48V
RATED CURRENT| 8.3A| 4.2A| 2.1A| 10A| 5A| 2.5A
CURRENT RANGE| 0 – 8.3A| 0 – 4.2A| 0 – 2.1A| 0 – 10A| 0 – 5A| 0 – 2.5A
RATED POWER| 99.6W| 100.8W| 100.8W| 120W| 120W| 120W
PEAK CURRENT| 12.45A| 6.3A| 3.15A| 15A| 7.5A| 3.75A
PEAK POWER Notes| 150W (3sec.)| 180W (3sec.)
RIPPLE 8 NOISE (max.) Note.2| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p
VOLTAGE ADJ. RANGE| 9 – 14V| 24 – 28V| 48 – 56V| 9 – 14V| 24 – 28V| 48 – 56V
VOLTAGE TOLERANCE Not..3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms ©12Vdc| 500ms, 60ms @24Vdc
HOLD UP TIME (Typ.)| Please refer to page 7 Hold up Time( Load de-rating curve )
INPUT| VOLTAGE RANGE Note.4| 9 – 18Vdc| 9 – 18Vdc| 9 – I8Vdc| 16.8 – 33.6Vdc| 16.8 – 33.6Vdc| 16.8 – 33.6Vdc
EFFICIENCY (Typ.)| 89.%| 89.%| 89.%| 89%| 90.%| 91%
DC CURRENT (Typ.)| 11.2A ©12Vdc| 5.6A ©24Vdc
INRUSH CURRENT (Typ.)| 5A ©12Vdc| 5A @ 24Vdc
INTERRUPTION OF VOLTAGE SUPPLY| EN50155:2007-comply with 3ms© full load| EN50155:2007-compq with Siove! (6ms) @id bad. S2 level (10ms)ft 70% loac
EN50155:2017-comply with S1 level| EN50155:2017-comply with Si level
PROTECTION| OVERLOAD| Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105-135% rated output power with auto-recovery
OVER VOLTAGE| 14.4 – 16.8V| I 28.8 – 33.6V| I 57.6 – 67.2V| 1 14.4 – 16.8V| I 28.8 – 33.6V| I 57.6 – 67.2V
Protection type : Shut down o/p voltage, re power on to recover
REVERSE POLARITY| By internal MOSFET. no damage. recovers automatically after fault condition removed
UNDER VOLTAGE LOCKOUT| 1 2Vin (A – type) :Power ON?: 9V , OFFS:8.5V| I 24Vm (B – type) Power ON ;:-= 16.8V , OFF tt; 16.5V
EIMRONNENI| WORKING TEMP.| -40 -+7012 (Refer to terating Curve’)
WORKING HUMIDITY| 5 – 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85t , 5 – 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/t (0- 55°C )
VIBRATION| Component:10 – 500Hz. 5G 10minitcycle. 60min. each along X. Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE| 5000 meters
SAFETY & EMC
(Note 6)| SAFETY STANDARDS| IEC 62368-1, UL 62368-1, EAC TP TC 004. AS/NZS 62368.1 approved; Design refer to UL508
---|---|---
WITHSTAND VOLTAGE| 11P-0/P:4KVdc I/P-FG:2.5KVdc 0/P-FG:2.5KVdc
ISOLATION RESISTANCE| UP-0/P. UP-FG. 0/P-FG:>100M Ohms! 500Vdc / 25t / 70% RH
EMC EMISSION| Parameter| Standard| Test Level! Note
Conducted| BS EN/EN55032| Class B
Radiated| BS EN/EN55032| Class 8
Voltage Ricker| BS EN/EN61000-3-3| —
Harmonic Current| | —-
EMC IMMUNITY| BS EWEN55024 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level! Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3. 1KV/Line-Line level 3. 2KV/Line-Line-FG :criteria A
Conducted| BS EN/EN61000-4-6| Level 3,10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4. 30Alm ; criteria A
RAILWAY STANDARD| Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC (except for 9-18Vin)
OTHERS| MTBF| 1769.5K hrs min. Telcordia SR-332 (Bellcore) : 214.5K hrs min. MIL-HDBK-217F (25t )
DIMENSION| 32’125.21102mm (WWI))
PACKING| 510g; 28pcs/15.3Kg/1.22CUFT
NOTE| 1.All parameters NOT specially mentioned are measured at normal input (A:12Vdc , B:24Vdc) , rated load and 25t of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 ri f & 47 rt f parallel capacitor.
3.Tolerance : includes set up tolerance, line regulation and load regulation.
4.Derating may be needed under low input voltage. Please check the derating curve for more details.
5.3 seconds max., please refer to peak loading curves.
6.The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
7.The ambient temperature derating of 3.5t /1000m with fanless models and of 5t /1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer : For detailed information. please refer to https://www.meanwell.com/serviceDisclaimeraspx
MODEL| DDR-120C-12| DDR-120C-24| DDR-120C-48| DDR- 120D-12| DDR-120D-24| DDR-120D-48
---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 24V| 48V| 12V| 24V| 48V
RATED CURRENT| 10A| 5A| 2.5A| 10A| 5A| 2.5A
CURRENT RANGE| 0 – 10A| 0 – 5A| 0 – 2.5A| 0 – 10A| 0 – 5A| 0 – 2.5A
RATED POWER| 120W| 120W| 120W| 120W| 120W| 120W
PEAK CURRENT| 15A| 7.5A| 3.75A| 15A| 7.5A| 3.75A
PEAK POWER Note.5| 180W (3sec.)
RIPPLE & NOISE (max.) Note.2| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p
VOLTAGE ADJ. RANGE| 9 – 14V| 24 – 28V| 48 – 56V| 9 – 14V| 24 – 28V| 48 – 56V
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms @48Vdc| 500ms, 60ms @110Vdc
HOLD UP TIME (Typ.)| Please refer to page 7 Hold up Time( Load de-rating curve )
INPUT| VOLTAGE RANGE Note.4| 33.6 – 67.2Vdc| 33.6 – 67.2Vdc| 33.6 – 67.2Vdc| 67.2 – 154Vdc| 67.2 – 154Vdc| 67.2 – 154Vdc
EFFICIENCY (Typ.)| 90.%| 91%| 92%| 90.%| 91%| 92.%
DC CURRENT (Typ.)| 2.8A @48Vdc| 1.3A @110Vdc
INRUSH CURRENT (Typ.)| 5A@48Vdc| 5A@110Vdc
INTERRUPTION OF VOLTAGE SUPPLY| EN50155:2007-comply with SI level (6ms) @ full load, S2 level (10ms) @ 60% load| EN50155:2007-comply with S2 level (10ms) @ full load
EN50155:2017-comply with Si level| EN50155:2017-comply with 51 level
PROTECTION| OVERLOAD| Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105-135% rated output power with auto-recovery
OVER VOLTAGE| 14.4 – 16.8V| 1 28.8 – 33.6V| 157.6 – 67.2V| 1 14.4 -16.8V| I 28.8 – 33.6V| I 57.6 – 67.2V
Protection type : Shut down o/p voltage, re power on to recover
REVERSE POLARITY| By internal MOSFET, no damage, recovers automatically after fault condition removed
UNDER VOLTAGE LOCKOUT| 48Vin (C-type):Power ON?-33.6V , OFF–.33V| 1110Vin(D-type):Power ON≥t67.2V,OFF≥65V
ENVIRONMENT| WORKING TEMP.| -40 – +70°C (Refer to “Derating Curve”)
---|---|---
WORKING HUMIDITY| 5 – 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85t , 5 – 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/°C (0 – 55°C )
VIBRATION| Component:10 – 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE| 5000 meters
SAFETY & EMC
(Note 6)| SAFETY STANDARDS| IEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved; Design refer to UL508
WITHSTAND VOLTAGE| I/P-0/P:4KVdc I!P-FG:2.5KVdc 0/P-FG:2.5KVdc
ISOLATION RESISTANCE| UP-0/P, UP-FG, 0/P-FG:>100M Ohms! 500Vdc / 25t/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level I Note
Conducted| BS EN1EN55032| Class B
Radiated| BS EN1EN55032| Class B
Voltage Flicker| BS ENIEN61000-3-3|
Harmonic Current| |
EMC IMMUNITY| BS ENIEN55024 , BS EN1EN61000-6-2(BS EN1EN50082-2)
Parameter| Standard| Test Level I Note
ESD| BS ENIEN61000-4-2| Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated| BS ENIEN61000-4-3| Level 3, 10V/m ; criteria A
EFT I Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KVILine-Line-FG ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS ENIEN61000-4-8| Level 4, 30A/m ; criteria A
RAILWAY STANDARD| Compliance to BS EN1EN45545-2 for fire protection ; Meet BS EN/EN50155 l IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC
OTHERS| MTBF| 1769.5K hrs min. Telcordia SR-332 (Bellcore) ; 214.5K hrs min. MIL-HDBK-217F (25°C )
DIMENSION| 32’125.2’102mm (WH’D)
PACKING| 510g; 28pcs/15.3Kg/1.22CUFT

NOTE

  1. All parameters NOT specially mentioned are measured at normal input (C:48Vdc , D:110Vdc) , rated load and 25°C of ambient temperature.
  2. Ripple & noise are measured at 2OMHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 « f & 47 « f parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. Derating may be needed under low input voltage. Please check the derating curve for more details.
  5. 3 seconds max., please refer to peak loading curves.
  6. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
  7. The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft).
    ※ Product Liability Disclaimer : For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Block Diagram
1

Derating Curve

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Derating Curve
1

Output derating VS input voltage

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Output derating
1

Peak Loading

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Peak Loading
1

Input Fuse

There is a fuse connected in series to the positive input line, which is used to protect against abnormal surge. Fuse specifications of each model are shown as below.

Type Fuse Type Reference and Rating
A Time-Lag Conquer MST, 8A, 250V *2
B Time-Lag Conquer MST, 8A, 250V *1
C Time-Lag Conquer MST, 4A, 250V *1
D Time-Lag Conquer MST, 10A, 250V *2

Input Under-Voltage Protection

If input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when input voltage reaches above Vimin, please refer to the cruve below.

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Voltage
Protection 1

Input Reverse Polarity Protection

There is a MOSFET connected in series to the negative input line. If the input polarity is connected reversely, the MOSFET opens and there will be no output to protect the unit.

Input Range and Transient Ability

The series has a wide range input capability. With -30% / +40% of rated input voltage(except A Type), it can withstand that for 1 second.

Inrush Current

Inrush current is suppressed by a current limit circuit during the initial start-up, and then the circuit is bypassed by a MOSFET to reduce power consumption after accomplishing the start-up.

Hold-up Time

  • EN50155: 2007 version – D type is in compliance with S2 level (10ms), while A types are in compliance with S1 level (3ms) at full load output condition. To fulfil the requirements of S2 level (10ms), B types require de-rating their output load to 70%, C types require de-rating their output load to 60%, please refer to the curve diagrams below.

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Time
1 MEAN WELL DDR 120A 12 120W DIN
Rail Type DC DC Converter - Time 2

  • EN50155: 2017 version – Comply with S1 level (6ms)

Efficiency vs Load & Vin Curve

The efficiency vs load & Vin curves of each model are shown as below.

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Efficiency
1 MEAN WELL DDR 120A 12 120W
DIN Rail Type DC DC Converter - Efficiency 2

Immunity to Environmental Conditions

Test method Standard Test conditions Status
Cooling Test EN 50155 section 12.2.3 (Column 2, Class TX) EN 60068-2-1
Temperature: -40°C Dwell Time: 2 hrs/cycle No damage
Dry Heat Test EN 50155 section 12.2.4 (Column 2, Class TX)

EN 50155 section 12.2.4 (Column 3, Class TX & Column 4, Class TX) EN 60068-2-2| Temperature: 70°C 185°C Duration: 6 hrs / 10min| PASS
Damp Heat Test, Cyclic| EN 50155 section 12.2.5 EN 60068-2-30| Temperature: 25°C-55°C Humidity: 90%-100% RH Duration: 48 hrs| PASS
Vibration Test| EN 50155 section 12.2.11 EN 61373| Temperature: 19°C Humidity: 65%
Duration: 10 mins| PASS
Increased Vibration Test| 112. EN 50155 section 12.2.11 EN 61373| Temperature: 19°C Humidity: 65% Duration: 5 hrs| PASS
Shock Test| EN 50155 section 12.2.11 EN 61373| Temperature: 21 ± 3°C Humidity: 65 ± 5% Duration: 30ms*18| PASS
Low Temperature Storage Test| EN 50155 section 12.2.3 (Column 2, Class TX) EN 60068-2-1| Temperature: -40°C Dwell Time: 16 hrs| PASS
Salt Mist Test| EN 50155 section 12.2.10 (Class ST4)| Temperature: 35°C ±2°C Duration: 96 hrs| PASS

EN45545-2 Fire Test Conditions

Test Items Hazard Level
Items Standard
R22 Oxygen index test
EN ISO 4589-2:1996 PASS
Smoke density test EN 45545-2:2013
EN ISO 5659-2:2006 PASS
Smoke toxicity test EN 45545-2:2013
NF X?0-100:2006 PASS
R24 Oxygen index test
EN ISO 4589-2:1996 PASS
R25 Glow-wire test
EN 60695-2-11:2000 PASS
R26 Vertical flame test
EN 60695-11:2003 PASS

Mechanical Specification

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Mechanical
Specification 1

MEAN WELL DDR 120A 12 120W DIN Rail Type DC DC Converter - Mechanical
Specification 2

Installation Manual