FOX-ESS LV5200 Low Voltage Lithium Battery User Manual

June 13, 2024
FOX-ESS

FOX-ESS LV5200 Low Voltage Lithium Battery

Information

In order to prevent improper operation before use, please carefully read this manual. The user manual version is updated frequently, the latest version can be downloaded from the official website.

Table of Contents

1. Introduction
2. Symbols
3. Safety

Product Introduction

The document describes the installation, commissioning, maintenance, and troubleshooting of the following low-voltage battery listed below.

  • Battery Model: LV5200
  • Battery Chemistry: Lithium Iron Phosphate This manual is designed for qualified personnel only. The tasks described in this document should be performed by authorized and qualified technicians only. After installation, the installer must explain the user manual to the end user.

Product Symbols

Symbol Explanation
CE mark The inverter complies with the requirements of the applicable

CE guidelines. This mark indicates compound UK product safety
certification requirements.
Caution, risk of electric shock.| Do not place nor install near flammable or explosive
materials.
Install the product out of reach of children.|
Read the instruction manual before starting the installation and
operation.|
Do not dispose of the product with household wastes.| Recyclable.
Disconnect the equipment before carrying out maintenance or
repair.|
Observe precautions for handling electrostatic discharge
sensitive devices.|
PE conductor terminal|
Caution, risk of electric shock, energy storage timed
discharge.|

Product Safety

Any work on the batteries should be handled by authorized technicians. Therefore, technicians should familiarize themselves with the contents of this manual before any maintenance or installation is carried out on the system.

Product Information

Battery Module Specifications

Battery module| Nominal capacity (Ah)| Nominal voltage (Vdc)| Nominal energy (kWh)| Battery voltage range (Vdc)| Max. continuous discharging current (A)| Max. continuous charging current (A)| Recommended charging current (CC-CV) (A)| Charging cut-off current (constant current and constant
voltage) (A)| Peak charging current (30s) (A)| Peak discharging current (30s) (A)| Cycle life| Discharge capacity (Ah)| Energy density (wh / kg)| Ingress protection| Communication| Weight (kg)| Dimensions (WHD) [mm]| Protective class
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
LV5200| 100| 51.2| 5.12| 43.2 – 57.6| 100| 100| 100| 5| 105| 150| -20 – 50| 104| IP21| RS485/CAN| 49| 342207600| I

Battery Charge/discharge Curve

Battery charge Current protection Trigger
First level over the current 105A, Lasts 30s COC
Second level over current 125A, Lasts 1s COC2
Battery discharge
First level over the current 110A, Lasts 300s
Second level over current 125A, Lasts 30s
Third level over current 155A, Lasts 1s

Introduction

  • The document describes the installation, commissioning, maintenance, and troubleshooting of the following low-voltage battery listed below. LV5200
  • The battery chemistry of this product is Lithium Iron Phosphate.
  • This manual is designed for qualified personnel only.
  • The tasks described in this document should be performed by authorized and qualified technicians only.
  • After Installation, the Installer must explain the user manual to the end user.

Symbols

FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1
\(1\)FOX-ESS-LV5200-Low-Voltage-Lithium-
Battery-FIG-1 \(2\)

Safety

Any work on the Batteries should be handled by authorized technicians and hence it is understood that the technicians should familiarize themselves with the contents of this manual before any maintenance or installation is carried out on the system.

Handling

  • Do not expose battery to open flame.
  • Do not place the product under direct sunlight.
  • Do not place the product near flammable materials. It may lead to fire or explosion in case of an accident.
  • Store in a cool and dry place with ample ventilation.
  • Do not store the product near water sources.
  • Store the product on a flat surface.
  • Store the product out of reach of children and animals.
  • Do not damage the unit by dropping, deforming, impacting, cutting or penetrating with a sharp object. It may cause leakage of electrolytes or fire.
  • Do not touch any liquid spilled from the product. There is a risk of electric shock or damage to the skin.
  • Always handle the battery wearing insulated gloves.
  • Do not step on the product or place any foreign objects on it. This can result in damage.
  • Do not charge or discharge the damaged battery.
  • Do not store the battery near water sources.

Installation

  • Do not connect the LV5200 to inverter conductors or Photo-Voltaic conductors. This will damage the battery and may result in an explosion.
  • After unpacking, please check the product for damages and missing parts.
  • Make sure that the inverter and battery is completely turned off before commencing installation.
  • Do not interchange the positive and negative terminals of the battery.
  • Ensure that there is no short circuit of the terminals or with any external device.
  • Do not exceed the battery voltage rating of the inverter.
  • Do not connect the battery to any incompatible inverter.
  • Do not connect different battery types together.
  • Please ensure that all the batteries are grounded properly.
  • Do not open the battery to repair or disassemble. Only the manufacturer is allowed to carry out any such repairs.
  • In case of fire, use only a dry powder fire extinguisher. Liquid extinguishers should not be used.
  • Install the batteries only inside the approved manufacturer enclosure. Installing the battery anywhere outside is strictly forbidden.
  • Do not install the battery near water sources or places where the battery can get wet.
  • Install the battery away from children or pets.
  • Do not use the battery in a high static environment where the protection device might be damaged.
  • Do not install with other batteries or cells.
  • Batteries with different color labels cannot be connected in parallel.

Response to Emergency Situations
The battery can be used in single or multi in parallel. It is designed to prevent hazards or failures. However, manufacturer cannot guarantee their absolute safety. Under exposure to the internal materials of the battery the following recommendations should be carried out by the user.

  • If there has been inhalation, please leave the contaminated area immediately and seek medical attention.
  • If there has been contact with eyes, rinse the eyes with running water for 15 minutes and seek medical attention immediately.
  • If there has been contact with the skin, wash the contacted area with soap thoroughly and seek medical attention immediately.
  • If there has been ingestion, induce vomiting and seek medical attention.

Fire Situation
In situations where the battery is on fire, if it is safe to do so, disconnect the battery pack by turning of the switch to shut off the power to the system. Use an FM-200 or Co2 fire extinguisher for the battery and an ABC fire extinguisher for the other parts of the system. Under any fire situation, please evacuate the people from the building immediately before trying to extinguish it.
Water Situation
The battery modules are not water resistant. Hence care should be taken not to get it wet. If you find the battery completely or partially submerged in water do not try to open. Contact authorized personnel or manufacturers for further instructions.

Product Information

LV5200 photovoltaic energy storage system is a 48V energy storage system based on a lithium-ion ferrous phosphate battery. It is equipped with a customized battery management system (BMS), which is designed for energy storage applications of household photovoltaic power generation users. In the daytime, the surplus power of photovoltaic power generation can be stored in the battery. At night or when necessary, the stored energy can be provided to the electrical equipment, it can improve the use efficiency of photovoltaic power generation, peak-load shifting, and provide emergency standby power.

Battery Module Specifications

Specifications for Battery Note
Battery module LV5200
Nominal capacity (Ah) 100
Nominal voltage (Vdc) 51.2
Nominal energy (kWh) 5.12
Battery voltage range (Vdc) 43.2 – 57.6
Max. continuous discharging current (A) 100
Max. continuous charging current (A) 100
Recommended charging current (CC-CV) (A) 100

Charging cut off current

(constant current and constant voltage) (A)

| 5|
Peak charging current (30s) (A)| 105|
Peak discharging current (30s) (A)| 150|
Cycle life| ≥6000@25°C @90% DOD|
Storage temperature (°C)| -20 – 50|
Operating temperature range (°C)| Charge: 0 – 55

Discharge: -15 – 55

|
Discharge capacity (Ah)| 0°C±2 @ 1C @ 80%

25°C±2 @ 1C @ 100%

45°C±2 @ 1C @ 96%

|
Energy density (wh / kg)| 104|
Ingress protection| IP21|
Communication| RS485/CAN|
Weight (kg)| 49|
Dimensions (WHD) [mm]| 342207600|
Protective class| I|

Battery Charge/discharge Curve

Current protection

| | Trigger| Recover


Battery charge

| First COC| level| over| current| ≥105A, Lasts 30s| ≥60s: Recover
Second level over current COC2| ≥125A, Lasts 1s| ≥60s: Recover



Battery discharge

| First DOC| level| over| current| ≥110A, Lasts 300s| ≥60s: Recover
Second level over current DOC2| ≥125A, Lasts 30s| ≥60s: Recover
Third SC| level| over| current| ≥155A, Lasts 1s| ≥60s: Recover

Product Features

Battery System Features
The batteries have been fitted with multiple protection systems to ensure the safe operation of the system.
Some of the protection system includes:

  • Inverter interface protection: Over voltage, over current, external short circuit, reverse polarity, ground fault, over temp, in rush current.
  • Battery Protection: Internal short circuit, over voltage, over current, over temp, under voltage. The battery system contains the following Interface to allow it to connect and operate efficiently.

Battery interface:

Object Description Object Description
A POWER-1 H Start button
B LinkPort1 I Power switch
C Ground screw J CAN
D Add switch K RS485/CAN
E SOC LED L Ground screw
F Alarm LED M LinkPort0
G Running LED N POWER-2

Communication parallel interface (Link Port0, Link Port1, RS485) and communication interface to inverter (CAN/RS485)

  • LV5200 has two 485 communication units in series operation, one for master control and one for slave control.
  • Network interface description: Link Port0 is connected to the upper battery module, Link Port1 is connected to the lower battery module. CAN / RS485 is the communication interface to the inverter. The interface is defined as follows:

Pin configuration is as follows:
Link Port0

Pin Function definitions Function d eclaration
1 B RS485-B
2 A RS485-A
3 GND GND
4 NC NC
5 NC NC
6 GND GND
7 A RS485-A
8 B RS485-B

Link Port1

Pin Function definitions Function declaration
1 B RS485-B
2 A RS485-A
3 GND GND
4 NC NC
5 NC NC
6 GND GND
7 A RS485-A
8 B RS485-B

RS485

Pin Function definitions Function declaration
1 B RS485-B
2 A RS485-A
3 GND GND
4 NC NC
5 NC NC
6 GND GND
7 A RS485-A
8 B RS485-B

CAN

Pin| Function

definitions

| Function

declaration

---|---|---
1| NC| NC
2| GND| GND
3| NC| NC
4| CANH| CANH
5| CANL| CANL
6| NC| NC
7| NC| NC
8| NC| NC

Earth Terminal
This terminal is used to connect the battery to the earth for safety purposes.
Handle
The handle is used to carry or move the battery.
Power Terminal
A set of positive and negative terminals to connect the battery to the inverter. When you are unplugging the wires from the terminals, make sure you press the lock button and then pull it. When installing the plug, do not press the button and push the plug until you hear a click sound.
In addition to the above physical features, the battery has the following performance:

  1. 90% Depth of Discharge;
  2. Cycle life ≥6000 cycles.
Installation

Items in the package
Please check if following items are including with the package:FOX-ESS-
LV5200-Low-Voltage-Lithium-Battery-FIG-1 \(5\)

L: To match the different inverters, our accessory packs are differentiated, so please look at the wire markings on the white sleeves before wiring.FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1
\(6\)

RS485 (Inverter side) Pin definition:

Pin 1 2 3 4 5 6 7 8
Definition NC NC RS485-B 12V RS485-A NC NC GND

RS485 (Battery side) Pin definition:

Pin 1 2 3 4 5 6 7 8
Definition RS485-B RS485-A GND NC NC GND RS485-A RS485-B

FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1 \(7\)

One end is plugged into the inverter CAN port, the other end into the battery CAN port.

CAN (Inverter side) Pin definition:

Pin 1 2 3 4 5 6 7 8
Definition NC GND NC CANH CANL NC NC NC

CAN (Battery side) Pin definition:

Pin 1 2 3 4 5 6 7 8
Definition NC GND NC CANH CANL NC NC NC
  1. Use only the parts included with the battery pack to ensure proper installation. If anything is damaged or missing, please contact your distributor.
  2. Package 1 is provided separately, not including in battery package. Please contact your distributor if you do not have it. Also you will receive L-1 or L-2 in package 1 .
  3. Select an interface (CAN/RS485) based on the actual inverter interface type.
  4. If the definition of the communication port from your inverter to the battery is different from all of the above, please make your own communication cable.

ClearanceFOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1
\(8\)

Position Min size
Left 300mm
Right 300mm
Top 300mm
Bottom On the ground

Make sure to leave a space of at least 30 cm. A clearance of at least 30 cm must be Ieft around the battery pack for proper cooling.
Note: Make sure that the battery pack is always exposed to the ambient air. The battery pack is cooled by natural convection. If the battery pack is entirely or partially covered or shielded, it may cause the batter ypack to stop operating.

Tools

The following tools will be required to install the battery.FOX-ESS-LV5200
-Low-Voltage-Lithium-Battery-FIG-1 \(9\)

Installation Steps

MountingFOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1
\(10\)

  • STEP-1
    Measure and confirm that the bottom of the bracket is 285mm away from the ground, and mark the 5-hole positions on the bracket with a pen.

  • STEP-2
    Drill holes with electric drill, make sure the holes are deep enough (at least 50mm) for installation, and then tighten the expansion tubes.

  • STEP-3
    Install the expansion tubes in the holes, and tighten them. Then install the wall bracket by using the expansion screws.

  • STEP-4
    Hang the battery over the bracket, move the battery close to it, lower the battery, and make sure the 2 mounting bars on the back are fixed well with the 2 grooves on the bracket.

Wiring

  • STEP A
    Connect BAT + to POS +, BAT – to NEG – respectively. Connect the battery communication network cable to the lithium battery communication port of the inverter.

  • STEP B
    Plug the power plug into any output socket on the left or right of the battery. Connect the communication network cable to the CAN interface of the battery, connect the ground terminal of the battery with the ground wire, and lock the nut.FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1
\(13\)

    • Select an interface (CAN/RS485) based on the actual inverter interface type. Please choose L-1 or L-2.
    • Parallel multiple batteries, please refer to the following steps.
  • STEP C
    Plug the power line of the parallel battery into the remaining output socket, insert the communication line of the parallel battery into LinkPort1, and lock the ground nut.

  • STEP D
    Plug the power line of the parallel battery into the remaining output socket, insert the communication line of the parallel battery into LinkPort0, and lock the ground nut.

  • STEP E
    Repeat STEP C through STEP D to insert more batteries (up to 12 batteries).

System Start up

  • When connected to the inverter, turn on the battery first to ensure that the battery voltage output is normal, then turn on the inverter.
  • All installation and operation must comply with local electrical standards.
  • Check all power cables and communication cables carefully.

Turn on the POWER

  • switch Dial address selection: Definition of address switch for parallel batteries: When the battery pack is connected with multiple batteries in parallel, the address switch can be used to distinguish different pack addresses. The hardware address can be set by the address switch on the board. Addresses 1, 2, 3, and 4 represent the online number of batteries (only the host needs to be configured), 5, 6, 7, and 8 represent the slave address. The slave address needs to be continuous, and can support up to 12 batteries in parallel.
    Single battery address setting: 0001 0000
    Parallel batteries address setting: refer to the table below for the definition of address switch. For example, three batteries are in parallel, and the address switch example is as follows:
    Master dial: 0011 0000, slave 1 dial: 0000 0001, slave 2 dial: 0000 0010

Number of batteries| Master| Slave 1| Slave 2| Slave 3| Slave 4| Slave 5| Slave 6| Slave 7| Slave 8| Slave 9| Slave 10| Slave 11
---|---|---|---|---|---|---|---|---|---|---|---|---
1| 0001

0000

| | | | | | | | | | |
2| 0010

0000

| 0000

0001

| | | | | | | | | |
3| 0011

0000

| 0000

0001

| 0000

0010

| | | | | | | | |
4| 0100

0000

| 0000

0001

| 0000

0010

| 0000

0011

| | | | | | | |
5| 0101

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| | | | | | |
6| 0110

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| | | | | |
7| 0111

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| 0000

0110

| | | | |
8| 1000

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| 0000

0110

| 0000

0111

| | | |
9| 1001

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| 0000

0110

| 0000

0111

| 0000

1000

| | |
10| 1010

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| 0000

0110

| 0000

0111

| 0000

1000

| 0000

1001

| |
11| 1011

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| 0000

0110

| 0000

0111

| 0000

1000

| 0000

1001

| 0000

1010

|
12| 1100

0000

| 0000

0001

| 0000

0010

| 0000

0011

| 0000

0100

| 0000

0101

| 0000

0110

| 0000

0111

| 0000

1000

| 0000

1001

| 0000

1010

| 0000

1011

Note: “1”indicates that the Dip switch is “ON”, “0” indicates that the Dip switch is “OFF”. And it also indicates the position of the Dip switch. For example, “0001 0000” indicates that the 4th Dip switch is “ON”,the rest are all “OFF”.

  1. Please change the address switch in the right position accordingly base on the system battery quantity before power on battery.
  2. After pressing the power switch for 1s, all LEDs will be on and flashing, which indicates that the battery is started normally. After pressing the start button for 3s, the battery will turn on the discharge function.

Commissioning

There are seven LED indicators on the front of the battery packs to show its operating status.
Fault status indicated by indicator:

  • ● Off
  • ○ On
  • ◐ Flash
  1. The RUN indicator blinks and the ALARM indicator is off: The battery is running.FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1 \(17\) FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1 \(21\)
  2. RUN indicator Steady on: The device is powered off or the battery is faulty and cannot be charged or discharged.FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1 \(22\) FOX-ESS-LV5200-Low-Voltage-Lithium-Battery-FIG-1 \(23\)

Exclusion

The warranty shall not cover the defects caused by normal wear and tear, inadequate maintenance, handling, storage faulty repair, modifications to the battery or pack by a third party other than manufacturer or manufacturer agent, failure to observe the product specification provided herein or improper use or installation, including but not limited to the following.

  • Damage during transport or storage.
  • Incorrect Installation of battery into pack or maintenance.
  • Use of battery pr pack in inappropriate environment.
  • Improper, inadequate, or incorrect charge, discharge or production circuit other than stipulated herein.
  • Incorrect use or inappropriate use.
  • Insufficient ventilation.
  • Ignoring applicable safety warnings and instructions.
  • Altering or attempted repairs y unauthorized personnel.
  • In case of force majeure (ex: lightning, storm, flood, fire, earthquake, etc.).
  • There are no warranties implied or express other than those stipulated herein. the manufacturer shall not be liable for any consequential or indirect damages arising or in connection with the product specification, battery or pack.

Troubleshooting and Maintenance

Maintenance

  1. It is recommended that the battery storage time is not more than 6 months.
  2. It is required to charge the battery at least once every 6 months, for this charge maintenance make sure the SOC is charged to higher than 70%。 In the condition of 90% charging. It is recommended that the customers use a low-voltage inverter and fill the battery every half month, otherwise, the SOC will deviate.
  3. Every year after installation. The connection of the power connector, grounding point, power cable, and screw are suggested to be checked. Make sure there is no loose, no broken, no corrosion at the connection point. Check the installation environment such as dust, water, insects etc. Make sure it is suitable for the IP21 battery system.

Troubleshooting

When the red/green LED on the panel is flashing or normally on, it does not mean that the LV5200 is abnormal, it may be just an alarm or protection. Please check the ‘LED status indicators’ in Chapter 7 for the detailed faulty definition before any troubleshooting steps. In general, the alarm indication is normal without manual intervention. When the alarm-triggering state is removed, LV5200 will automatically return to normal use.
Problem determination based on the following points

  1. Whether the green light on the power switch is on;
  2. Whether the buzzer in BMS is on;
  3. Whether the battery system can be communicated with inverter;
  4. Whether the battery can be output voltage or not.

Preliminary determination steps

  1. The battery system cannot work, when DC is switched on and the POWER is on, the LED doesn’t light up or flash, please consider contacting the local distributor.
  2. The LED display of BMS is normal, but it cannot charge and discharge. Observe the display screen of the inverter and there is no SOC. Please check whether the RS485 communication between BMS to inverter is well connected. If the connection is good, please replace a RS485 communication cable. If the SOC is still not visible on the inverter display screen, please contact the local distributor.
  3. After the battery system is powered on, if you can see the alarm information on the LED and inverter display screen at the same time, please contact the local distributor.

The copyright of this manual belongs to FOXESS CO., LTD. Any corporation or individual should not plagiarize, partially or fully copy (including software, etc.), and no reproduction or distribution of it in any form or by any means is permitted. All rights reserved.

  • FOXESS CO., LTD.
  • Add: No.939, Jinhai Third Road, New Airport Industry Area, Longwan District, Wenzhou, Zhejiang
  • ng, China
  • Tel: 0510- 68092998
  • WWW.FOX-ESS.COM.
  • V1.0 10-500-10070-00

In order to prevent improper operation before use, please carefully read this manual. The user manual version is updated frequently, the latest version can be downloaded from the official website.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals