FOX-ESS LV5200 Solar Battery User Manual
- June 5, 2024
- FOX-ESS
Table of Contents
FOX-ESS LV5200 Solar Battery User Manual
In order to prevent improper operation before use, please carefully read this manual.
1. Introduction
The document describes the installation, commissioning, maintenance and
troubleshooting of the following low voltage battery listed below.
LV5200
The battery chemistry of this product is Lithium Iron Phosphate. This manual
is designed for qualified personnel only. The tasks described in this document
should be performed by authorized and qualified technicians only.
After Installation the Installer must explain the user manual to the end user.
2. Symbols
3. Safety
Any work on the Batteries should be handled by authorized technicians and hence it is understood that the technicians should familiarize themselves with the contents of this manual before any maintenance or installation is carried out on the system.
3.1 Handling
- Do not expose battery to open flame.
- Do not place the product under direct sunlight.
- Do not place the product near flammable materials. It may lead to fire or explosion in case of accident.
- Store in a cool and dry place with ample ventilation.
- Do not store the product near water sources.
- Store the product on a flat surface.
- Store the product out of reach of children and animals.
- Do not damage the unit by dropping, deforming, impacting, cutting or penetrating with a sharp object. It may cause leakage of electrolyte or fire.
- Do not touch any liquid spilled from the product. There is a risk of electric shock or damage to skin.
- Always handle the battery wearing the insulated gloves.
- Do not step on the product or place any foreign objects on it.
- This can result in damage.
- Do not charge or discharge damaged battery.
- Do not store the battery near water sources.
3.2 Installation
- Do not connect the LV5200 to inverter conductors or Photo-
- Voltaic conductors. This will damage the battery and may result in explosion.
- After unpacking, please check the product for damages and missing parts.
- Make sure that the inverter and battery is completely turned off before commencing installation.
- Do not interchange the positive and negative terminals of the battery.
- Ensure that there is no short circuit of the terminals or with any external device.
- Do not exceed the battery voltage rating of the inverter.
- Do not connect the battery to any incompatible inverter.
- Do not connect different battery types together.
- Please ensure that all the batteries are grounded properly.
- Do not open the battery to repair or disassemble. Only manufacturer is allowed to carry out any such repairs.
- In case of fire, use only dry powder fire extinguisher. Liquid extinguishers should not be used.
- Install the batteries only inside approved manufacturer enclosure. Installing the battery anywhere outside is strictly forbidden.
- Do not install the battery near water sources or places where the battery can get wet.
- Install the battery away from children or pets.
- Do not use battery in high static environment where the protection device might be damaged.
- Do not install with other batteries or cells.
3.3 Response to Emergency Situations
The battery can be used in single or multi in parallel. It is designed to
prevent hazards or failures.
However, manufacturer cannot guarantee their absolute safety.
Under exposure to the internal materials of the battery the following
recommendations should be carried out by the user.
- If there has been inhalation, please leave the contaminated area immediately and seek medical attention.
- If there has been contact with eyes, rinse the eyes with running water for 15 minutes and seek medical attention immediately.
- If there has been contact with the skin, wash the contacted area with soap thoroughly and seek medical attention immediately.
- If there has been ingestion, induce vomiting and seek medical attention.
Fire Situation
In situations where the battery is on fire, if it is safe to do so, disconnect
the battery pack by turning of the switch to shut off the power to the system.
Use FM-200 or Co2 fire extinguisher for the battery and an ABC fire
extinguisher for the other parts of the system. Under any fire situation,
please evacuate the people from the building immediately before trying to
extinguish it.
Water Situation
The battery modules are not water resistant. Hence care should be taken not to
get it wet. If you find the battery completely or partially submerged in water
do not try to open. Contact authorized personnel or manufacturer for further
instructions.
3.4 Warning Labels
Warning labels are attached on the battery pack.
4. Product Information
L V5200 photovoltaic energy storage system is a 48V energy storage system based on lithium-ion ferrous phosphate battery. It is equipped with a customized battery management system (BMS), which is designed for energy storage applications of household photovoltaic power generation users. In the daytime, the surplus power of photovoltaic power generation can be stored in the battery. At night or when necessary, the stored energy can be provided to the electrical equipment, it can improve the use efficiency of photovoltaic power generation, peak-load shifting, and provide emergency standby power.
4.1 Battery Module Specifications
4.2 Battery Charge/discharge Curve
5. Product Features
5.1 Battery System Features
The batteries have been fitted with multiple protection systems to ensure the safe operation of the system. Some of the protection system includes:
- Inverter interface protection: Over voltage, over current, external short circuit, reverse polarity, ground fault, over temp, in rush current.
- Battery Protection: Internal short circuit, over voltage, over current, over temp, under voltage.
The battery system contains the following Interface to allow it to connect and operate efficiently.
Battery interface:
Running LED
This LED is used to indicate if the battery is operating effectively. A green
light on this LED means the battery is ON and operating normally.
Alarm LED
This LED is used to indicate if the battery is operating failure. A red light
on this LED means the battery is operating abnormally.
Communication parallel interface (Link Porto, Link Port1, RS485) and
communication interface to inverter (CAN/RS485)
L V5200 has two 485 communication units in series operation, one for master
control and one for slave control.
Network interface description: Link Port0 is connected to the upper battery module, Link Port1 is connected to the lower battery module. CAN / RS485 is the communication interface to the inverter. The interface is defined as follows:
Earth Terminal
This terminal is used to connect the battery to the earth for safety purposes.
Handle
The handle is used to carry or move the battery.
Power Terminal
A set of positive and negative terminals to connect the battery to the
inverter. When you are unplugging the wires from the terminals, make sure you
press the lock button and then pull it. When installing the plug, do not press
the button and push the plug until you hear a click sound. In addition to the
above physical features, the battery has the following performance:
- 90% Depth of Discharge;
- Cycle life ~6000 cycles.
6. Installation
6.1 Items in the package
Please check if following items are including with the package:
Note:
- Please use only the components included with the battery pack to ensure proper installation. In the event of a component being damaged or missing, contact your distributor or reseller.
- Object I and J are provided separately and are not included in the battery package. Please contact your distributor or reseller for availability.
6.2 Clearance
Make sure to leave a space of at least 30 cm. A clearance of at least 30 cm must be left around the battery pack for proper cooling.
Note: Make sure that the battery pack is always exposed to the ambient air. The battery pack is cooled by natural convection. If the battery pack is entirely or partially covered or shielded, it may cause the battery pack to stop operating.
6.3 Tools
The following tools will be required to install the battery.
6.4 Installation Steps
- Mounting
STEP-1
Measure and confirm that the bottom of the bracket is 285mm away from the
ground, and mark the 5-hole positions on the bracket with a pen.
STEP-2
Drill holes with electric drill, make sure the holes are deep enough (at least
50mm) for installation, and then tighten the expansion tubes.
STEP-3
Install the expansion tubes in the holes, and tighten them. Then install the
wall bracket by using the expansion screws.
STEP-4
Hang the battery over the bracket, move the battery close to it, lower the
battery, and make sure the 2 mounting bars on the back are fixed well with the
2 grooves on the bracket.
- Wiring
STEP A
Connect BAT+ to POS +, BAT – to NEG – respectively. Connect the battery
communication network cable to the lithium battery communication port of the
inverter.
STEP B
Plug the power plug into any output socket on the left or right of the
battery. Connect the communication network cable to the CAN interface of the
battery, connect the ground terminal of the battery with the ground wire, and
lock the nut.
Note: Parallel multiple batteries, please refer to the following steps.
STEP C
Plug the power line of the parallel battery into the remaining output socket,
insert the communication line of the parallel battery into LinkPort1, and lock
the ground nut.
STEP D
Plug the power line of the parallel battery into the remaining output socket,
insert the communication line of the parallel battery into Link Port0, and
lock the ground nut.
STEP E
Repeat STEP C through STEP D to insert more batteries (up to 12 batteries).
6.5 System Start up
- When connected with inverter, the inverter should be turned on first to avoid the current pulse of the inverter increasing to the battery pack.
- All installation and operation must comply with local electrical standards.
- Check all power cables and communication cables carefully.
- Turn on the POWER switch
Dial address selection
Definition of address switch for parallel batteries: When the battery pack is
connected with multiple batteries in parallel, the address switch can be used
to distinguish different pack addresses. The hardware address can be set by
the address switch on the board. Addresses 1, 2, 3, and 4 represent the online
number of batteries (only the host needs to be configured), 5, 6, 7, and 8
represent the slave address. The slave address needs to be continuous, and can
support up to 12 batteries in parallel.
Single battery address setting: 0001 0000
Parallel batteries address setting: refer to the table below for the
definition of address switch. For example, three batteries are in parallel,
and the address switch example is as follows: Master dial: 0011 0000, slave 1
dial: 0000 0001, slave 2 dial: 0000 0010
- Please change the address switch in the right position accordingly base on the system battery quantity before power on battery.
- After pressing the power switch for 1s, all LEDs will be on and flashing, which indicates that the battery is started normally. After pressing the start button for 3s, the battery will turn on the discharge function.
- After the communication with the inverter is disconnected for 1 Os, the battery will turn off the output. If it does not recover after 48 hours, the battery will be shut down.
7 Commissioning
There are seven LED indicators on the front of the battery packs to show its
operating status.
– Running LED indication
After start up, the running indicator light flashes, which indicates that the
equipment is in normal operation.
– Alarm LED indication
When the battery is in normal operation, the alarm LED is off, and after the
fault occurs, the alarm LED is always on.
– SOC LED indication
Fault status indicated by indicator:
8 Exclusion
The warranty shall not cover the defects caused by normal wear and tear,
inadequate maintenance, handling, storage faulty repair, modifications to the
battery or pack by a third party other than
manufacturer or manufacturer agent, failure to observe the product
specification provided herein or improper use or installation, including but
not limited to the following.
- Damage during transport or storage.
- Incorrect Installation of battery into pack or maintenance.
- Use of battery pr pack in inappropriate environment.
- Improper, inadequate, or incorrect charge, discharge or production circuit other than stipulated herein.
- Incorrect use or inappropriate use.
- Insufficient ventilation.
- Ignoring applicable safety warnings and instructions.
- Altering or attempted repairs y unauthorized personnel.
- In case of force majeure (ex: lightning, storm, flood, fire, earthquake, etc.).
- There are no warranties-implied or express-other than those stipulated herein. manufacturer shall not be liable for any consequential or indirect damages arising or in connection with the product specification, battery or pack.
9 Troubleshooting and Maintenance
9.1 Maintenance
-
Regularly check whether the service environment of the battery meets the requirements, and the installation position should be far away from the heat source.
-
In case of one of the following situations, it needs to be charged in time:
– The battery is often under charged;
– The battery has been out of use or stored for more than 3 months. -
Regularly check whether the battery and its supporting terminals, connecting cables and indicator lights are normal.
9.2 Troubleshooting
When the red/ green LED on the panel is flashing or normally on, it does not mean that the LV5200 is abnormal, it may be just an alarm or protection. Please check the ‘LED status indicators’ in chapter 7 for the detailed faulty definition before any trouble-shooting steps. In general, the alarm indication is normal without manual intervention. When the alarm triggering state is removed, LV5200 will automatically return to normal use.
– Problem determination based on the following points
- Whether the green light on the power switch is on;
- Whether the buzzer in BMS is on;
- Whether the battery system can be communicated with inverter;
- Whether the battery can be output voltage or not.
– Preliminary determination steps
- Battery system cannot work, when DC switch on and POWER on, the LED doesn’t light up or flash, please consider contact the local distributor.
- The LED display of BMS is normal, but it cannot charge and discharge. Observe the display screen of inverter and there is no SOC. Please check whether the RS485 communication between BMS to inverter is well connected. If the connection is good, please replace a RS485 communication cable. If the SOC is still not visible on the inverter display screen, please contact the local distributor.
- After the battery system is powered on, if you can see the alarm information on the LED and inverter display screen at the same time, please contact the local distributor.
The copyright of this manual belongs to FOXESS Co., Ltd Wuxi Branch. Any
corporation or individual should not plagiarize, partially or fully copy
(including software, etc.), and no
reproduction or distribution of it in any form or by any means is permitted.
All rights reserved.
FOXESS Co., Ltd Wuxi Branch
Add: No.11, Lijiang Road, Xinwu District, Wuxi
City, Jiangsu Province, China
Tel: 0510- 68092998
WWW.FOX-ESS.COM.