Product Usage Instructions
Wiring Connection
EPS Box-TP simplifies the connection process for users. Follow the wiring
diagram provided in the user manual to connect the ON-GRID side to the power
grid, the EPS port to the energy storage machine, and the LOAD port to the
home load.
Note: Ensure that the neutral cables of the on-grid side and backup side are connected for the backup function to work.
Preparation
Package Contents
Before installation, check that the package contains the following items:
- A – Expansion Screws
- B – Expansion Tubes
- C – Cushion Blocks
- D – Self-Tapping Screws
- E – AC Connectors
Tools Required
Make sure you have the following tools ready before starting the installation:
- Diagonal Plier
- Screwdriver
- Rubber Hammer
- Driller
- Marker Pen
Mounting
Step 1: Install the four cushion blocks on EPS Box-TP using the self-
tapping screws.
FAQ (Frequently Asked Questions)
-
Q: What should I do if the backup function is not working?
A: Ensure that the neutral cables of the on-grid side and backup side are connected together as per safety requirements. -
Q: Can I use EPS Box-TP with any type of equipment?
A: EPS Box-TP is compatible with equipment that has a backup function. Make sure to follow local wiring regulations for specific countries.
Introduction
EPS Box-TP integrates two contactors which provides simple connection for users. It is compatible with equipment with backup function. Configured with EPS Box, customers just need to connect 3 wires between inverter and EPS Box. It can simplify the operation and improve security.
Overview:
Objeto | Descripción |
---|---|
1 | LOAD |
2 | EPS |
3 | ON-GRID |
Wiring Diagram
Note: the following is the wiring diagram of EPS BOX TP. It is necessary
to connect the ON-GRID side of EPS BOX TP to the power grid, connect the EPS
port to the EPS port of the energy storage machine, and connect the LOAD port
to the load at home. The function of TP is to select the power of the load
port from the GRID or the EPS port of the energy storage machine.
Note: According to Australian safety requirements, the neutral cables of
the on-grid side and backup side must be connected together. Otherwise, the
backup function will not work.
This diagram is an example for an application that neutral connects with the PE in a distribution box. For countries such as Australia, New Zealand, South Africa, etc, please follow local wiring regulations.
This diagram is an example for an application in which neutral is separated
from the PE in the distribution box.
For countries such as China, Germany, the Czech Republic, Italy, etc, please
follow local wiring regulations. Need internal or external eps box, connect PE
and the off-grid N line.
Preparation
Package Contents
Before installation, make sure that nothing inside the package is damaged. The
following items should be inside the package.
Number | Items | Quantity |
---|---|---|
A | Expansion Screws | 4 |
B | Expansion Tubes | 4 |
C | Cushion Blocks | 4 |
D | Self-Tapping Screws | 4 |
E | AC Connectors | 3 |
Tools
Before you start, get the following tools ready.
Mounting
- Step 1: Install the four cushion blocks on EPS Box -TP with self-tapping screws.
- Step 2: Use EPS Box-TP with cushion blocks as a template to mark the four holes’ position on the wall with a marker pen.
- Step 3: Drill holes with 6 driller carefully, make sure the holes are deep enough for installation. Install the expansion tubes through cushion blocks into the holes and tighten them.
- Step 4: Install the expansion screws with a screwdriver to fix the EPS Box-TP.
Wiring Connection
Step1: Grid String Connection
EPS Box-TP is designed for a three-phase grid. Per voltage range is
220/230/240V; frequency is 50/60Hz. Other technical requests should comply
with the requirements of the local public grid.
Model(kw) | 5.0 | 6.0 | 8.0 | 10.0 | 12.0 |
---|---|---|---|---|---|
Cable (Load) | 6.0mm 2 | 6.0mm 2 | 6.0mm 2 | 6.0mm 2 |
6.0mm 2
Cable (ON-GRID)| 4.0mm 2| 4.0mm 2| 4.0mm 2| 4.0mm
2| 4.0mm 2
Cable (EPS)| 4.0mm 2| 4.0mm 2| 4.0mm 2| 4.0mm 2|
4.0mm 2
Micro- Breaker| 32A| 32A| 32A| 32A| 32A
Step 2: Grid Wiring
- Check the grid voltage and compare with the permitted voltage range (refer to technical data).
- Disconnect the circuit breaker from all the phases and secure against re-connection.
- Trim the wires:
- Trim all the wires to 52.5mm and the PE wire to 55mm.
- Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
Note: Please refer to local cable type and color for the actual installation
A. EPS Wiring
Set the parts on the cable.
Crimp wires, screw twisting torque 0.8+/-0.1N m.
Put the sealing body and yarn trapper into the main body, screw the lock nut into the main body, and the torque is (2.5 + /- 0.5N m).
Insert the male end into the female end. For the rotation direction of the lock, please refer to the LOCK mark on the assembly.
B. ON-GRID Wiring
Separate the ON-GRID plug into three parts as below.
- Hold middle part of the female insert, rotate the back shell to loosen it, detach it from female inset.
- Remove the cable nut (with rubber insert) from the back shell.
Slide the cable nut and then Install the back shell onto the cable.
Push the threaded sleeve into the socket, tighten up the cap on the terminal.
Remove the ON-GRID connector: Press the bayonet out of the slot with a small screwdriver or the unlock tool and pull it out, or unscrew the threaded sleeve, then pull it out.
C.Load Wiring
Wire Stripping
- Installation of cable end connector
- Step 1: Set the parts on the cable.
- Step 2: Wire crimping cord end terminal can be inserted into the housing quickly according to the sign, torque 1.0+/- 0.1N·m.
- Step 3: The housing is inserted into socket, then the unlock key is inserted into socket.
- Step 4: Insert Seal and Clamp Finger into socket, then tighten the nut, torque 8+/-2N·m.
- Male female connection
- Disassembly Connector
- Step 1: Unmating the plug and the socket
- Step 2: tighten the unlock key, then pull the plug
Overview of EPS Box-TP
Technical Parameters
Model | EPS Box -TP |
---|
Grid
Max. AC Input Current (A)| 32
Rated AC Voltage (V)| 220/380, 230/400, 3L/N/PE
Rated AC Frequency (Hz)| 50/60
EPS
Max. EPS Input Current CA)| 25
Rated EPS Voltage (V)| 220/380, 230/400, 3L/N/PE
Rated EPS Frequency (Hz)| 50/60
Load
Rated Output Current (A), On Grid Mode| 32
Rated Output Current (A), EPS Mode| 32
Rated Grid Voltage (V)| 220/380, 230/400, 3L/N/PE
Rated Grid Frequency (Hz)| 50/60
General Data
Cooling Concept| Natural
Operating Temperature Range (°C)| -25〜+50
Demensions (WHD)(mm)| 340223170
Net Weight (Kg)| 2.8
Ingress Protection| IP65
FOXESS CO., LTD.
Add: No.939, Jinhai Third Road, New Airport Industry Area,
Longwan District, Wenzhou, Zhejiang, China
Tel: 0510- 68092998
WWW.FOX-ESS.COM
The copyright of this manual belongs to FOXESS CO., LTD. Any corporation or
individual should not plagiarize, partially or fully copy (including software,
etc.), and no reproduction or distribution of it in any form or by any means
is permitted. All rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>