SFA LIVBOITSMART Smart Control Box Instruction Manual
- June 13, 2024
- SFA
Table of Contents
LIVBOITSMART 07.2022
Smart Control Box
Installation and operating manual
SAFETY
1.1 IDENTIFICATION OF WARNINGS
| Meaning
---|---
DANGER| This term defines a high risk of danger, which can lead to death or
serious injury, if not avoided.
WARNING| This term defines a medium risk of danger, which can lead to serious
or minor injury, if not avoided.
NOTICE| This term characterises dangers to the machine and its proper
operation.
| Warning of a general danger.
The danger is specified by indications given in the table.
| This symbol characterises dangers associated with the voltage and provides
information on voltage protection.
1.2 GENERAL POINTS
This operating and installation manual contains important instructions to
follow for the fitting, operation and maintenance of the XXX control box.
Following these instructions guarantees safe operation and prevents injury and
property damage.
It always has to be available on site of operation of the machine/plant. Not
only the general safety instructions mentioned in this main point on safety
have to be observed, but also the special safety instructions mentioned in the
other sections.
Failure to comply with this operating and installation manual will result in
the loss of warranty rights and rights to damages.
TRANSPORT/DISPOSAL
2.1 TRANSPORT
For all transportation, the control panel must be switched off (see 7.
Shutdown)
ENVIRONMENTAL TRANSPORT CONDITIONS:
Parameters | Value |
---|---|
Relative humidity | 85% maxi. (no condensation) |
Ambient temperature | -10°C to+70°C |
2.2 DISPOSAL
**** The device must not be disposed of as household waste and must be
disposed of at a recycling point for electrical equipment. The device’s
materials and components are reusable.
The disposal of electrical and electronic waste, recycling and recovery of any
form of used appliances contribute to the preservarion of our environment.
DESCRIPTION
3.1 APPLICATION
The Smart control box is a monitoring and control box for SFA lifting
stations. It allows the operation and parameterization of the connected
station, as well as the real time consultation of the activity and operation
history.
3.2 TECHNICAL DATA OF THE CONTROL BOX
Nominal supply voltage | 1 ~ 220-240 V AC |
---|---|
Network frequency | 50-60 Hz |
Protection class | IP 54 |
Power cable | Type |
mm2
Length| 2.5 m
3.3 TECHNICAL DATA OF THE DETECTION DEVICE
- Analog level sensor
- Signal 0-5 V
- Input voltage 0-12 V
3.4 DIMENSIONS
Sanicubic
INSTALLATION
DANGER
| Submersion of the control device.
Risk of electric shock!
Only use the control device in rooms safe from floods.
4.1 WALL MOUNTING
The Smart controm box must be installed indoors, in a place protected from
humidity and frost.
The Smart control box is supplied with a wall bracket.
- Mount the wall bracket horizontally, using the appropriate fixings for your wall.
- Snap the Smart control box onto the bracket.
4.2 CONNECTION OF THE FLOAT (SANIFOS) AND PUMP CABLES
Cables are connected via waterproof terminal blocks.
4.2.1 Preparation of the conductive wires
Conductor| PE| 1~: N, L
3~: L1, L2, L3
---|---|---
Disassembly length y (mm)| 33| 25
Stripping length x (mm)| 8| 8
4.2.2 Connectors wiring for pumps (Sanipump)
NOTICE
| It is imperative to respect the colours of the wires when making the connections so as not to cause a mal- function.
Sanifos with Sanipump GR/VX Single-phase version:
: Green/Yellow wire
Position 1: Brown wire
Position 2: Blue wire
Position 3: White wireSanifos with Sanipump GR/VX Three-phase version:
: Green/Yellow wire
Position 1: Brown wire
Position 2: Black wire
Position 3: Grey wire Sanifos with Sanipump SLD (single- or three-phase
version):
: Green/Yellow wire
Position 1: Black wire
Position 2: Grey wire
Position 3: Brown wire Note: The terminal blocks are already mounted on
the Sanicubic pump cables.
4.2.3 Connectors wiring for floats (Sanifos)
Follow this wiring diagram:
Connect the 2 wires to slots 1 and 2, regardless of colour. It is only
important to respect these two locations.
The wiring is identical for the 3 floats.
4.2.4 Using the terminal blocks
4.2.4.1 Assembling the connector 4.2.4.2 Closing the connector
4.2.4.3 Opening the connector 4.2.5 Connection to the Smart Control Box
4.2.5.1 Connecting and locking the connector 4.2.5.2 Unlocking and
disconnecting the connector 4.2.5.3 Location of Connector Connections
Sanifos Pump 1: Pump 1
Pump 2: Pump 2
OFF: Low level float
ON: High level float
ALARM: Alarm float
SanicubicPump 1: Pump 1
Pump 2: Pump 2
PRESSOSTAT: ON/Alarm level
NOTICE
__
__
| Pulling force on the cables.
Risk of tearing.
Cut the cables to the correct length.
Strip cables and wires.
Never pull or move the cables when they are connected.
Do not exert any constraints, e.g. by bending the cable too tightly.
DANGER
| Electrical connection work performed by an unqua – lified
personnel.
Risk of electric shock!
The electrical connection must be carried out by a qualified electrician.
The electrical connection must comply with the stan- dards in force in the
country of installation.
The device’s power supply must be connected to ground (class I) and protected
by a high sensitivity differential circuit breaker (30 mA) rated at:
– 25 A for single-phase Sanicubic 2 VX, Sanifos with 2 single-phase Sanipump
SLD,
– 16 A for all other cases.
The connection must be used exclusively to provide the power to the Smart
Control Box.
4.4 CONNECTING THE WIRED EXTERNAL ALARM BOX
The cable from the external alarm box is already connected to the elec- tronic
board.
- Connect the jack to the bottom of the external alarm box.
Note: The power supply of the external alarm box is done through the Smart box. If the jack plug is incorrectly inserted, the external alarm box will signal a power failure (see 6.4.4 Operation).
4.5 CONNECTION TO THE BMS
Option of a remote alarm facility : dry contact (no voltage).
3 BMS are available: a BMS with NO (Normally Opened) contact, a BMS with NC
(Normally Closed) contact and a configurable NO BMS (see
6.3.3 Settings Menu).
This contact opens (Normally Closed contact)/closes (Normally Opened contact)
as soon as the station is in alarm mode and remains opened/closed as long as
the default has not been corrected.
The terminals can be connected to a BMS (Building Management System) system or
to a live system (max. AC 250V / 16A, DC 250V / 17A).
- Use one of the pre-holes on the side of the enclosure.
- Open the hole by tapping firmly with a screwdriver.
- Connect the connection cable directly to the circuit board using the illustrations below:
Location of BMS
COMMISSIONING
5.1 START-UP CONFIGURATION
At the first start-up, it may be necessary to configure the box by selecting
the connected station using the and keys:
– the installation tank: [Sani]Cubic 1, [Sani]Cubic 2, [Sani]Fos 500,
[Sani]Fos 610 or [Sani]Fos 1300,
– the type of pump: Brushless, Grinder, Vortex or Solida.
Note: In case of an error or a change in the installation, it is possible
to access this menu (see 10.1 Return to the start-up screen)
The operating parameters must then be selected: date, time, language and
brightness of the display.
Note: The date and time must be set correctly for alarm management, alarm
history and maintenance frequencies. For each configuration screen, validate
the selected setting by pressing the validation button.
On the last screen (see opposite), press the confirmation button one last time
to start the Smart box operation.
5.2 CHECKS TO BE CARRIED OUT FOR THE COMMISSIONING OF A SANIFOS LIFTING
STATION
-
Set the language, date and time.
-
Define the use of the station: Individual, Collective or Commercial.
-
Check that the quick connectors are correctly connected to the Smart unit.
-
Check that the led on both pumps are green.
-
Check the power supply voltage on the display.
-
Fill the tank with water via the connected sanitary appliances.
-
Check that the pumps switch on automatically at the set water level.
-
Check that the water operating intensity of the pumps, shown on the display, is between
– 4 and 7 A with Sanipump GR, Sanipump VX (single-phase and three-phase), Sanicubic 1, Sanicubic 2, Sanicubic 2 VX three-phase,
– 6 and 12 A with Sanicubic 1 VX single-phase, Sanicubic 2 VX single-phase,
– 7 and 10 A with Sanipump SLD single-phase,
– 3 and 5 A with Sanipump SLD three-phase. -
Check the correct operation of the motors in forced operation.
-
heck that the wired alarm box is switched on.
-
Check the level of water in the tank at the end of the cycle:
– Sanicubic: the water level must be below the longest dip tube.
– Sanifos with Sanipump VX or Sanispump SLD: the water level must be above the pump cover plate.
– Sanifos with Sanipump GR: the water level is +/- 10 cm from the bottom of the tank. -
Set the delay time accordingly.
-
Set the delay for the start of the auxiliary pump. Measure the duration of an ON-OFF cycle and enter a value equal to at least 2 times the ON-OFF cycle value.
-
Check that the data has been correctly recorded by the Smart box (log, pumping time…).
OPERATION
6.1 PRESENTATION OF THE FRONT OF THE BOX
6.1.1 Key identification
- Current switch
- Enter Key
- Back
- Navigation
- Activation/deactivation of the pumps
- Pump operation indicator light
- Forced operation of pumps
6.1.2 Operating lights
The light is green when the pump is activated.
The light is red when the pump is deactivated (by a manual lockout or
automatically following a fault).
6.2 USING THE CONTROL BOX
6.2.1 On screen display
6.2.1.1 Normal operation 6.2.1.2 Alarm display
Alarm indicator in real time, with identification of the problem detected for
quick maintenance.
A special window giving the alarm type and the alarm time remains open for
some time.
As soon as the fault disappears, return to the general screen on which an
alarm notification appears. To remove the alarm notification, simply press one
of the two forced-on buttons. Details of the alarms can be consulted in the
alarm log.
6.2.2 Pump activation/deactivation
In the case of maintenance or replacement of a pump, it is possible to
deactivate each pump independently.To deactivate the pump:
Press continuously for 5 seconds on the selected pump. The led turns red and a
cross is diplayed on the shut-down pump.
To reactivate the pump: Press again continuously for 5 seconds. The led turns
green and the cross turns off.
6.2.3 Navigating the menu Pressing the “Enter” key
takes you to the main menu:
Navigation through the menus and submenus is done using the arrow keys, Enter
and Back: 6.3 PRESENTATION OF THE MENUS
6.3.1 Language Menu Allows you to choose the language used in the
interface.
Enter the “Languages” menu by pressing the “Enter” key. Then press (previous
language) and (next language) to scroll through the available languages.
- Press to confirm the choice.
- Press to return to the main menu.
6.3.2 Logs Menu Allows:
– consult the alarm logs,
– consult the pump operation log,
– consult the operating levels of the level sensors,
– consult the software versions.
- Enter the “Logs” menu by pressing the “Enter” key.
- Then press and to scroll through the submenus. Confirm with to enter the submenu.
6.3.2.1 Alarm logs
Possibility to consult the history of the last 32 alarms.
- Then press (previous alarm) and (next alarm) to scroll through the alarm messages.
- Press to return to the main menu.
No modifications are possible.
The oldest alarms are automatically deleted when the number of searchable
alarms is exceeded.
6.3.2.2 Pumps operation
Allows you to view the operating information of the pumps.P1: Pump 1
P2: Pump 2
START-UP: total number of starts for each pump
T_MAX: maximum running time for each pump (maximum duration of an ON-OFF
cycle)
TOTAL: total running time of each pump since its first use.
- Press to return to the main menu.
No modifications are possible.
The resetting of the pump counter is reserved for professionals (see 8.1
Resetting the pump log)
6.3.2.3 Sensors operation
Allows to consult the activation height of the level sensors ON, OFF (for
Sanifos) and ALARM. Sanifos ALARM: Switch-on level in case of alarm;
simultaneous operation of both pumps.
ON: Standard switch-on level.
Standard operation with one pump at a time. Alternating pump at each cycle.
OFF: Pump switch-off level.
Sanicubic ALARM: Switch-on level in case of alarm; simultaneous operation of
both pumps.
ON: Standard switch-on level.
Standard operation with one pump at a time. Alternating pump at each cycle. A
sensor being activated:
– is white on the display
– has a value of 1.
6.3.2.4 Consulting software versions and configuration
Allows you to consult:
– the tank-pump combination (Model) selected for the installation,
– the software versions for the control box’s motherboard and the screen card.
This may be necessary in case of maintenance or intervention on the
enclosure.MODEL: the model of the station connected to the
box as set at the time of commissioning. If it does not match, see 10.1 Return
to the start-up screen to change the model.
– HW: the hardware version for the motherboard and the display board.
– SW: the software version for the motherboard and for the display board.
- Press to return to the main menu.
This information cannot be changed.
6.3.3 Settings Menu
Allows you to:
– set the date and time,
– adjust the brightness of the display, activate/deactivate the audible alarm,
– set the pump delay time,
– set the delay time for the auxiliary pump to start,
– select the frequency of maintenance,
– set the BMS parameters
6.3.3.1 Setting the date
The date setting is particularly important for alarm management and
maintenance monitoring.
- Then press and to select the value.
- Then press and to switch from day to month and month to year.
- Press to confirm the choice.
- Press to return to the main menu. 6.3.3.2 Setting the hour
The hour setting is imporant for alarm management.
- Then press and to select the value.
- Then press and to switch from hour to minute and minute to second.
- Press to confirm the choice.
- Press to return to the main menu.
6.3.3.3 Various Then press and to scroll through the submenus. Confirm
with to enter the submenu.
Brightness adjustment
Allows you to adjust the brightness of the display during use.
- Press and to select the value.
- Press to confirm the choice.
- Press to return to the main menu.
Enable/disable audible alarm
Selects whether the alarm notification (display of an alarm window) is
accompanied by an audible signal.
- Press and to choose between «Enable» or «Disable».
- Press to confirm the choice.
- Press to return to the main menu.
6.3.3.4 Setting the Stop delay time
The stop delay time is an additional pumping time when the pump’s stop level
has been reached. It allows the tank to be emptied as much as possible and
optimises the pumping of surface matter.– Mode: This pump stop delay
can be managed manually («Manual») or automatically («Automatic») depending on
the station configured at commissioning and the duration of the last pumping
times (for more details see 10.3 Learning loops).
– Duration: In Manual mode, you can enter a time delay value between 0 and 120
seconds, in increments of 1 s.
- Press and to choose between «Manual» and «Automatic».
- Press and to switch from Mode to Duration.
- Press and to choose the duration.
- Press to confirm the choice.
- Press to return to the main menu.
Note:
– If the automatic management mode has been chosen, the “Duration” parameter
cannot be modified.
– If Sanipump SLD was selected, the value is 0 s and cannot be changed.
6.3.3.5 Setting the start of the auxiliary pump
When one of the pumps is running continuously, the second pump is activated
after the time set in this menu to support the first pump. This activation of
the auxiliary pump corresponds to an abnormal case (e.g. a hydraulic problem
on the 1st pump) and will cause the automatic deactivation of the 1st pump.
To be relevant, the set time must be at least twice the duration of a normal
ON-OFF cycle. ACTIVATION AFTER: The delay for starting the
auxiliary pump is adjustable and must be between 15 s and 5 min (5 s
increments).
- Then press and to select the value.
- Press to confirm the choice.
- Press to return to the main menu.
6.3.3.6 Setting the maintenance frequency Indicates when the next maintenance
is due. A reminder on the display will appear on the scheduled date.
The maintenance frequencies are different depending on the area of use of the
station (according to EN12056-4):
– collective: 3 months;
– commercial: 6 months;
– individual: 12 months.
Changing the type of use:
Important: Validating a use type for the installation resets the maintenance
counter to 0.
- Then press (previous use) and (next use) to select the intensi- ty of use for the station.
- Press to confirm the choice.
- Press to return to the main menu.
6.3.3.7 BMS
The BMS (Building Management System) menu allows setting the conditions for the configurable BMS NO (Normally Open). It is possible to set a voltage or current condition for its operation. By default, the BMS is set to “Disable”.
- Press to switch from «Disable» to «Enable»
- Press to confirm the choice.
The possible modifications concern:
– the PARAMETER that defines the condition: U (voltage) or I (current),
– the CONDITION < (below) or > (above),
– the value: from 150 to 450 V (in increments of 10 V) or from 1 to 25 A (in
increments of 1 A).
- Press and to change the setting.
- Press and to switch from Parameter to Condition then from Condition to the value.
- Press to confirm the choice.
- Press to return to the main menu.
6.4 REMOTE WIRED ALARM BOX
6.4.1 Technical data
Audio and visual information
5 m cable length
Protection index: IP44
6.4.2 Dimensions 6.4.3 Installation
- The alarm box must be installed indoors, in a damp-free location.
- The alarm signal must always be visible to the user.
Note: It does not require an independent power supply. The power supply
is provided by the Smart box. In the event of a power cut, the battery of the
alarm box takes over.
6.4.4 Operation
The red general alarm LED indicates that there is an alarm in the Smart
Control Box. The alarm unit sounds as long as the fault is present. To stop
the alarm, press the reset button under the alarm unit or solve the problem on
the Smart Control Box.
The yellow «mains» LED indicates the power supply status of the alarm unit:
– light on steady = Smart Control Box on mains supply
– flashing and buzzer = power failure on the Smart Control Box. After 1
minute, the siren is discontinued.
The alarm box can be completely switched off by pressing and holding the reset
button (*).
6.5 SFA CONNNECT (OPTIONAL)
The SFA connect option allows, thanks to your WiFi box, to link your Smart box
to a Smartphone application. It is then possible to remotely consult the
operating information of your lifting station (power supply check, maintenance
status…) and to be informed in real time of alerts by notification or email.
Please refer to the manual delivered with SFA Connect.
SHUTDOWN
The Smart control box has a battery to keep the unit powered up in case of a
power failure.
When switching off the Control Box, the power supply to the box must be
switched off as well as this battery to allow the system to be powered down. 2
possibilities exist:
- During the 30 seconds following the powering up of the unit, switching the current switch to the OFF position allows a complete shutdown.
- Press the “Back”, “P1” and “P2” keys simultaneously.
MAINTENANCE
8.1 RESETTING THE PUMP LOG
It may be necessary to reset a pump’s operating counters to 0, e.g. if the
pump is changed.
Press the “Enter” and “P1” (or “P2” depending on the pump) keys
simultaneously.
The 3 parameters (number of starts, maximum pumping time and total running
time) are then reset to 0 for the pump in question.
8.2 MAINTENANCE UPDATE The icone indicates that the maintenance of the
installation has to be done.
Once the maintenance has been done, enter a new frequency setting (see 6.2.3
Navigating the menu): the new maintenance date is set and the icon disappears.
FAULT FINDING
Alarm message on the display | Possible cause | Remedy |
---|---|---|
No AC | No power supply. | Check power supply. |
Turn the current switch into position ON (I)
Pump P1 switched OFF| Pump 1 deactivated (activation lamp lights up red).|
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify the cause of
the problem.
Pump P2 switched OFF| Pump 2 deactivated (activation lamp lights up red).|
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify the cause of
the problem.
No pump activated| Pumps deactivated (activation lamps light up red).|
Reactivate the pumps by pressing the activation buttons.
In case of automatic deactivation, check the alarm log to verify the cause of
the problem.
Levels sensors fault| Clogged sensor| Clean the sensor, unclog the compression
chambers. Remove deposits in the tank.
Blocked sensor| Check that the floats move freely.
Remove deposits in the tank.
Incorrect wiring of the sensors.| Check the wiring of the sensor terminals.
Incorrect connection of the sensors.| Check the correct location of the float
connection on the casing.
Incorrect position of the floats on the rail.| Check the position of the
floats.
Float defective.| Contact after-sales service.
P1 I=0 Amp P2 I=0 Amp| Pump disconnected.| Check pump connection.
Check the wiring of the pump terminals.
Thermal break.| Pump connection occurs automatically after a delay.
Thermal break is a symptom of a malfunction that requires a thorough check.
Defective pump.| Check the pump.
P1 hydraulic issue P2 hydraulic issue| Problem pump cover plate. Impeller
problem.| Check pump hydraulics.
Clogged pipe.| Check the discharge pipe.
Shut-off valve closed| Open the shut-off valve
P1 I>Imax P2 I>Imax| Blockage of the pump.| Check for foreign bodies
Motor failure| Contact after-sales service.
Evacuation issue| Unable to evacuate water from the station.| Check for
clogged discharge pipe.
Check that the shut-off valve is open.
Check that both pumps are working properly.
FOR PROFESSIONALS
10.1 RETURN TO THE START-UP SCREEN
You can return to the settings made when the device was commissioned by
pressing the 4 arrow keys , , , and .
In particular, the choice of the connected station can be changed.
10.2 EXPLANATION OF THE LEDS ON THE ELECTRONIC BOARD
Note: The photograph below is used as an example. Indeed, the location of
the LEDs may vary but the colours and their indications are identical to all
electronic boards.
Blue LED: level indication
LED on = level sensor activated
Red LED: BMS operation
– LED on = event defined by the BMS condition is in progress
– LED off = no BMS event in progress
Green LED: pump operation
– LED on = pump running
– LED off = pump off
NOTICE
__| If the enclosure has been opened, take care not to pinch or pull the cable when refitting the front panel.
10.3 LEARNING LOOPS
The management of the delay time in “Automatic” mode is not adjustable.
It is calculated using a learning loop that averages the last 5 switch-ons. An
increasing delay time is the symptom of a drop in output flow and may
therefore indicate a fault in the discharge installation (clogging, etc.).
GUARANTEE
Smart Control Box is guaranteed for 2 years for parts and labour, subject to correct installation, use and maintenance of the unit.
- Brown
- Red
- Green
- Blue
- White
- Black
AUSTRALIA
SFA Saniflo Australia Pty Ltd Unit 9-10, 25 Gibbes Street Chatswood NSW 2067
Tel. +61 298 826 200
NEW ZEALAND
SFA Saniflo New Zealand Ltd PO Box 383 Royal Oak, Auckland 1345 Tel : 09 390
4615
SERVICE HELPLINES
Australia New Zealand Tel. +1300 554 779 Tel. 0800 107 264