Soler Palau MELLIZO Twin Fan Instruction Manual

June 13, 2024
Soler Palau

Soler Palau MELLIZO Twin Fan

Product Information

The MELLIZO twin fan is a product designed by Soler & Palau. It consists of two inline centrifugal fans housed in an acoustically lined cabinet. Each fan operates independently and can be used for run and standby functions. The unit also has a duty-share function that can be set for 3 to 24 hours, with the display indicating the status of the unit.

Speed Control Inputs

  • Variable Speed Control : Allows manual variable speed control using an optional secondary S&P REB ECOWATT or REB-CVF controller.
  • Automated variable speed control : Can be achieved by providing a 0-10V signal from an external source.

Installer-defined Fixed Speed Control
The Mellizo twin fan offers the option for installer-defined fixed speed control.

This can be set as

  • Continuous duty or on-demand duty triggered by an external switch.
  • One, two, or three speeds defined during installation to provide a minimum/middle/maximum speed ventilation system. The middle and maximum speeds can be selected using an external switch/sensor (either Volt-free and/or 230V).

Note: The fan requires a minimum output of 3 Volts to ensure start-up momentum.

Product Usage Instructions

Transport and Handling
Ensure proper care is taken during transportation and handling to avoid any damage to the MELLIZO twin fan.

Safety Rules
During installation, follow the safety rules provided to ensure safe and proper operation of the fan.

EC Declaration of Conformity
The MELLIZO twin fan complies with the EC declaration of conformity.

Designation of Equipment
The equipment is designated as the MELLIZO twin fan.

Guarantee
A guarantee is provided for the MELLIZO twin fan. Refer to the warranty terms and conditions for more information.

RECOMMENDATIONS

You have purchased a MELLIZO twin fan designed specifically by Soler & Palau to perform the functions described in the table of contents.
Before you install and start up this product, please read this instruction book carefully because it contains important information for your safety and the safety of users during installation, use and maintenance. Once installation is complete, please pass the instruction book on to the end user. Please check that the equipment is in perfect condition when you unpack it since any factory defect is covered under the S&P guarantee. Please also check that the equipment is the one that you have ordered and that the information on the instruction plate meets your requirements.

GENERAL

The Mellizo range comprises of two inline centrifugal fans in an acoustically lined cabinet; each fan works independently for run and standby plus 3 to 24 hours duty-share function with the display indicating the status of the unit.

Speed Control Inputs

  • Variable Speed Control
  • Manual variable speed control via an optional secondary S&P REB ECOWATT or REB-CVF controller, or
  • Automated variable speed control via a 0-10V signal from an external source.

Installer-defined Fixed Speed Control

  • An upon-installation defined duty either continuous or on-demand (triggered by an external switch), or
  • One, two or three speeds defined during installation to provide a minimum/middle/maximum speed ventilation system, the middle and maximum speeds being selected by an external switch/sensor (either Volt-free and/or 230V).
  • Note that there is a 3-Volt minimum output to the fan to ensure start-up momentum.

Remote Switching

  • The switching between the (up to) three speeds can be activated by either
  • (Up to) Three Volt-free contacts, or
  • (Up to) Three 230V supply inputs
  • On/Off – Volt-Free Contact and/or 230V
  • External Fire Fan Shut-Off Switch – An external “Fire” switch (Volt-Free) can be connected, If the switch opens signifying that the fire alarm has been activated, then the MULTI-REG Controller will automatically stop the fan.

Fan-Fail Detection by Fault Sensing

  • Automatic monitoring of the impeller rotation via the Tacho pulse (frequency generator) signal.
  • Low current sensing to indicate a connection open circuit problem.
  • Sixty seconds time-delay of fault detection on start-up to allow input levels to normalise.
  • Facility to connect an Airflow Switch or Differential Pressure Switch (DPS), for use on fans where other options are not practical. There is approximately a 60 seconds delay in the operation of the airflow switch monitoring system, to allow full airflow to develop.

Outputs

  • Digital Display
  • Running, Stopped and/or fault condition.
  • Fan speed percentage and 0-10V output condition.
  • Countdown to fault status monitoring condition (allows fan to gain speed).
  • Diagnostic – Reasons for fan stop/fail.

Analog Switch Outputs
Output to BMS of fan run and fault indicated by an individual set of contacts capable of controlling a maximum load of up to 230 Volts at 8 Amps.

TRANSPORT AND HANDLING

  • The equipment packaging has been designed to withstand normal transport conditions. The equipment must not be transported without its original packaging as it could become damaged.
  • The product must be stored in its original packaging and in a dry and clean place until it is installed. Do not accept any equipment that is not supplied in its original packaging or that shows signs of having been tampered with.
  • Prevent the packaging from falling or being knocked
  • Do not place heavy loads on top of it.
  • When handling heavy products, adequate lifting equipment techniques and equipment should be used to avoid injury.
  • Do not lift a product by pulling the wires, terminal/control enclosure, shutter or impeller to avoid damaging the product.

SAFETY RULES

ON INSTALLATION

  • Installation and commissioning must be done by a qualified professional specialist.
  • Ensure that installation complies with mechanical and electrical regulations in each country.
  • Once commissioned, the equipment must comply with the following Directives
    • Standard for Low Pressure Instalments 2006/95/CE
    • Machinery Standard 2006/42/CE
    • Standard for Electromagnetic Compatibility 2004/108/CE
    • Do not use this equipment in explosive or corrosive atmospheres.

AT START UP

  • Make sure there are no loose elements near the ventilator, as they could run the risk of being sucked up by it. If it is going to be installed in a duct, check that it is clean of any element that could be sucked up by the ventilator.
  • When installing an apparatus, make sure that all the fittings are in place and that the structure which supports it is resistant enough to bear its weight at full functioning power.
  • Before you handle this equipment, ensure it is disconnected from the mains power supply.
  • Check that the mains voltage and frequency are the same as specified on the name plate.
  • Follow the wiring diagram to make the electrical connections.
  • Check that the earthing, if any, is correct and that the thermal and surge protection has been connected and are within the relevant limits.
  • If a ventilator is installed in a duct, the duct must be exclusively for the ventilation system.

MECHANICAL INSTALLATION

The product should only have the airflow going vertically up and horizontally. In this orientation it is suitable for fitment onto a suitable supportive structure and secured through the 4 fixing holes provided.

Soler-Palau MELLIZO-Twin-Fan \(1\)

  • Leave an air space of not less than 150mm around the edges control enclosure to allow cooling air to flow freely.
  • Leave an additional gap in front of the control enclosure lid to allow for access during installation/wiring/maintenance.
  • Do not install in close proximity to other heat sources.
  • The maximum ambient temperature for the control board must not exceed 40°C.

The 2 fans integrated into the product are separately wired into a MELLIZO control panel located in an enclosure box positioned on the external casing.

MELLIZO POWER CONNECTIONS

This basic wiring must be followed for every installation!!!

  • L – Live
  • N – Neutral
  • E – Earth

Soler-Palau MELLIZO-Twin-Fan \(2\)CONTROL WIRING

REMOTE ENABLE (VOLT-FREE CONTACT) Soler-Palau MELLIZO-Twin-Fan
\(3\)

Fan speed set-point (Min Speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan.

REMOTE ENABLE (230V)

Soler-Palau MELLIZO-Twin-Fan \(4\) Fan speed set- point (Min Speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan.

0-10V (1 SIGNAL)

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed (0-10V)
The speed is defined by the voltage from the 0 – 10V signals from the external devices; the minimum output is 3V.

0-10V (2 SIGNALS) Soler-Palau MELLIZO-Twin-Fan
\(6\)PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed (0-10V)
The speed is defined by the highest voltage from the two 0 – 10V signals from external devices; the minimum output is 3V.

REB-CVF

Soler-Palau MELLIZO-Twin-Fan \(7\)

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed
The speed is defined by rotating the dial on the REB-CVF.

REB-ECOWATT Soler-Palau MELLIZO-Twin-Fan \(8\)

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed
The speed is defined by rotating the dial on the REB-ECOWATT.

PREP/COOK SWITCH

Soler-Palau MELLIZO-Twin-Fan \(9\)

Prep speed set-point (Min speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Cook speed set-point (High speed)
The speed is defined by the ‘High speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

SET SPEEDS (VOLT-FREE CONTACT)

Soler-Palau MELLIZO-Twin-Fan \(10\) Trickle speed set-point (Min speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Second speed set-point (Mid speed)
The speed is defined by the ‘Mid speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Third speed set-point (High speed)
The speed is defined by the ‘High speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

SET SPEEDS (230V) Soler-Palau MELLIZO-Twin-Fan
\(11\)

Trickle speed set-point (Min speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Second speed set-point (Mid speed)
The speed is defined by the ‘Mid speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Third speed set-point (High speed)
The speed is defined by the ‘High speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

AIRSENS (0-10V)

Soler-Palau MELLIZO-Twin-Fan \(12\)

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed
The speed is defined by the AIRSENS sensor, which will proportionally increase its control voltage depending on the pollutants or humidity in the air.

AIRSENS (TRICKLE/BOOST)

Soler-Palau MELLIZO-Twin-Fan \(13\)

Trickle speed set-point (Min speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Boost speed set-point (High speed)
The speed is defined by the ‘High speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

AIRSENS (REMOTE ENABLE) Soler-Palau MELLIZO-Twin-Fan
\(14\)

Fan speed set-point (Min Speed)
The speed is defined by the ‘Min speed’ Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan.

EXTERNAL FAULT

Soler-Palau MELLIZO-Twin-Fan \(15\)

External fault (SW1)
When the fan is in normal running conditions the switch should be in the closed position. If additional switches are required then then can be connected in series. During start-up there is a 60 seconds delay to allow the airflow to increase. When the fault switch opens signifying loss of airflow, the controller will automatically stop the fan and display “EXTERNAL SW1 FAULT”.
Following an “EXTERNAL SW1 FAULT”, a manual re-start will be required.

Fire shut-off (SW2)
When the fan is in normal running conditions the switch should be in the closed position. When the fault switch opens signifying the fire alarm has been activated, the controller will automatically stop the fan and display “FIRE ALARM ACTIVATED”.
Following an “FIRE ALARM ACTIVATED”, a manual re-start will be required

RELAY OUTPUT

Fan A (Maximum current load 8A)

Fan A is a run relay that will activate when Fan A is operating, below is the operation

  • Fan Running – Continuity between COM and NO
  • Fan Stopped – Continuity between COM and NC

Fan B (Maximum current load 8A)
Fan B is a run relay that will activate when Fan B is operating, below is the operation

  • Fan Running – Continuity between COM and NO
  • Fan Stopped – Continuity between COM and NC

Fault (Maximum current load 8A)
Fault is a fault relay that will activate when either fan is in fault condition, below is the operation: Fan Running/Stopped – Continuity between COM and NC
Fault with Fan – Continuity between COM and NO

TIMER FUNCTION

Soler-Palau MELLIZO-Twin-Fan \(17\)

Timer function
The over-run timer works when you alter the ‘Timer’ potentiometer, this will allow you to add an over-run of 0 to 15 minutes; the over-run function will operate for both remote enable and boost functions.
If a 10-minute over-run is set then the remote enable will over-run for 10 minutes and the boost will over-run for 10 minutes.

MAINTAINENCE

  • Before manipulate the device, make sure that it is disconnected from the mains and that no one can turn it on during the intervention.
  • The apparatus must be regularly inspected. These inspections should be carried out bearing in mind the ventilator’s working conditions, in order to avoid dirt or dust accumulating on the impeller, motor or back-draught shutter. This could be dangerous and perceptibly shorten the working life of the ventilator unit.
  • While cleaning, great care should be taken not to unbalance the impeller or motor.
    In all maintenance and repair work, the safety regulations in force in each country must be observed.

Warranty

  • S&P Limited Warranty
  • 24 (TWENTY-FOUR) MONTH PRODUCT WARRANTY
  • S&P UK Ventilation Systems Limited warrants that the MULTI-REG Control will be free from defective materials and workmanship for the period of 24 (twenty-four) months from the date of original purchase. In the event that we find any part is defective the product will be repaired or at the company’s discretion, replaced without charge provided that the product has been installed in accordance with the enclosed instructions and all applicable standards and national and local building standards.

IF CLAIMING UNDER WARRANTY
Please return the completed product, carriage paid, to your local authorized distributor. All returns must be accompanied by a valid Invoice of Sale. All returns must be clearly marked “Warranty Claim”, with an accompanying description stating the nature of the fault.

THE FOLLOWING WARRANTIES DO NOT APPLY

  • Damages resulting from improper wiring or installation.
  • Damages resulting when using the fan/control with fans/motors/controls/sensors other than those supplied and manufactured by the S&P Group of Companies.
  • Removal or alteration of the S&P data plate label.

WARRANTY VALIDATION

The end user must keep a copy of the Invoice of Sale to verify a purchase date.

RECYCLING

  • Dismantling and recycling must be carried out by qualified personnel and in compliance with local and international regulations.
  • Disconnect the electrical equipment from the power supply making sure that no one can start it during the operation. Disassemble and eliminate the parts to be replaced according to current national and international standards.

EEC legislation and our consideration of future generations mean that we should always recycle materials where possible; please do not forget to deposit all packaging in the appropriate recycling bins. If your device is also labelled with this symbol, please take it to the nearest Waste Management Plant at the end of its serviceable life.

EC DECLARATION OF CONFORMITY
Herewith we declare that the fan/control designated below, on the basis of its design and construction in the form brought onto the market by us is, in accordance with the relevant EC Council Directives on Electromagnetic Compatibility. If alterations are made to the apparatus without prior consultations with us, this declaration becomes invalid. We further declare that the equipment identified below may be intended to be assembled with other equipment/machines to constitute machinery, which shall not be put into service until the assembled machinery has been declared in conformity with the provisions of these relevant EC Council Directives.

DESIGNATION OF EQUIPMENT
EMC Directive 2014/30/EU based on conformity to the requirements of: –
BS EN IEC 61000-6-3:2021 // BS EN 61000-4-4:2012 // BS EN IEC 61000-4-11:2020 // BS EN 61000-4-2:2009 // BS EN 61000-4-8:2010 // BS EN IEC 61000-4-3:2020 // BS EN 61000-4-6:2014 // BS EN 61000-4-5:2014+A1:2017
EN 60204-1:2018 // EN 61000-3-2:2014 //EN 61000-3-3:2013 // EN 61000-6-2: 2005

  • AC:2005//EN 61000-6-
    3:2007+A1:2011+AC:2012 // //EN62311:2008 // EN ISO 12100:2010 // EN ISO 12499:2008 //EN ISO 13857:2019

GUARANTEE

  • S&P Limited Warranty
  • 24 (TWENTY-FOUR) MONTH PRODUCT WARRANTY
  • S&P UK Ventilation Systems Limited warrants that the CAB TWIN ECOWATT N /ACODS fan control will be free from defective materials and workmanship for the period of 24 (twenty-four) months from the date of original purchase. In the event that we find any part is defective the product will be repaired or at the company’s discretion, replaced without charge provided that the product has been installed in accordance with the enclosed instructions and all applicable standards and national and local building standards.

IF CLAIMING UNDER WARRANTY
Please return the completed product, carriage paid, to your local authorized distributor. All returns must be accompanied by a valid Invoice of Sale. All returns must be clearly marked “Warranty Claim”, with an accompanying description stating the nature of the fault.

THE FOLLOWING WARRANTIES DO NOT APPLY

  • Damages resulting from improper wiring or installation.
  • Damages resulting when using the fan/control with fans/motors/controls/sensors other than those supplied and manufactured by the S&P Group of Companies.
  • Removal or alteration of the S&P data plate label.

WARRANTY VALIDATION

The end user must keep a copy of the Invoice of Sale to verify a purchase date.

  • S&P UK VENTILATION SYSTEMS LTD
  • S&P HOUSE
  • WENTWORTH ROAD
  • RANSOMES EUROPARK
  • IPSWICH
  • SUFFOLK
  • TEL. 01473 276890
  • WWW.SOLERPALAU.CO.UK