Soler Palau 800 m3-h Slim Heat Recovery Units Owner’s Manual

October 30, 2023
Soler Palau

Soler Palau 800 m3-h Slim Heat Recovery Units

Soler Palau 800 m3-h Slim Heat Recovery Units product

COUNTER FLOW, HIGH EFFICIENCY HEAT RECOVERY UNITS SLIM Series

The SLIM Series Heat Recovery Units are designed for use in public buildings, offices, stores, schools, restaurants, and other similar spaces. They are suitable for both newly constructed buildings and renovation projects. The units are available in four sizes based on nominal airflow at 250-300 Pa: 800 m3/h, 1200 m3/h, 1600 m3/h, and 2000 m3/h.

Features

  • High efficient backward curved fans with EC external rotor motor
  • Robust construction with 30 mm double skinned panels with termoacoustic flameproof insulation A1/M0
  • Cabinet with integrated Plug&Play control
  • Low profile with lateral condensation connection and integrated condensation pump
  • Low pressure minipleat filters. Supply air (F7/ePM1 70%) and extract air (M5/ePM10 50%)
  • Counter flow heat exchanger (up to 94%) Eurovent certified

Options

The SLIM units can be ordered with an integrable preheater module. The preheater module can be mounted from the factory or installed on site as an accessory.

Accessory Modules

There are various accessory modules available for the SLIM Series Heat Recovery Units. Please refer to the product manual for more information.Soler Palau 800 m3-h Slim Heat Recovery Units
02 SL-DI Electric heater

  •  Finned heater elements where the fins are made from aluzinc and the tubes from stainless steel AISI 321.
  •  Built-in overheating protection thermostat with automatic reset at 60ºC and manual reset at 85ºC.
  • Integrated temperature sensor (on site connection to the unit).
  • Isolator switch installed on the unit.

SL-DC Hot water coil

  • 2 rows hot water coil made of copper pipes and aluminium fins.
  •  Motorized (24V) 3 way valve for proportional (0-10V) control (accessory).
  • Anti-frost protection by clamp-on sensor to the return flow pipe.
  •  Integrated supply air temperature sensor (on site connection to the unit).

SL-DFR Reversible water coil (Hot/Cold Water)

  • 3 rows water coil made of copper pipes and aluminium fins.
  • Motorized (24V) 3 way valve for proportional (0-10V) control (accessory).
  •  Anti-frost protection by clamp-on sensor to the return flow pipe.
  •  With welded condensate tray made of galvanized sheet metal.
  •  Condensate drain ½” located lateral on the modul. It has to be connected to a siphon (accessory).
  •  Built-in changeover thermostat (THCO) which controls a mixing valve.
  •  Integrated temperature sensor (on site connection to the unit).

SL-DF Cold water coil

  •  5 rows water coil made of copper pipes and aluminium fins.
  •  Motorized (24V) 3 way valve for proportional (0-10V) control (accessory).
  •  With welded condensate tray made of galvanized sheet metal.
  •  Condensate drain ½” located lateral on the modul. It has to be connected a siphon (accessory).
  • Integrated temperature sensor (on site connection to the unit).

SL-DX Direct expansion coil, provided without control

  •  4 rows coil made of copper tubes and aluminium fins.
  • Designed to work in evaporation or condensation mode.
  •  With welded condensate tray made of galvanized sheet metal.
  •  Integrated temperature sensor (on site connection to the unit).

MAIN ELEMENTS

Control Cabinet on the unit
Isolator switch
Wired control and components integrated in the cabinet
Easy access from the side (Left or Right version)
FUNCTIONS
AIRFLOW CONTROL
Three adjustable speeds
Reduced speed, normal speed, extra speed
Three adjustable working modes
CAV constant air volume
Fan speed is adjusted in dependency of the pressure lost of the filter in order to maintain the adjusted airflow
Each fan is connected to a pressure transmitter which allows to enter different setpoints to each fans
VAV variable air volume
Fan speed is adjusted in dependency of a external 0-10V signal. P.e. CO2 sensor, humidity sensor (accessories)
COP constant pressure
Fan speed is adjusted in dependency of a signal which comes form a external pressure sensor (accessory)
The fans maintain the adjusted pressure in the duct, increasing the speed when pressure falls or decrease speed when pressure rise
Time programming
Weekly timer, holiday periods
Boost function
Via external contact
Remote ON/OFF
Available contact to connect an external ON/OFF switch
TEMPERATURE CONTROL
Sensors
Outdoor air temperature sensor (ODA)
Supply air temperature sensor (SUP1)
Extract air temperature sensor (EXT)
Exhaust air temperature sensor (EHA)
Clamp-on sensor for frost protection of water coils (SL-DC, SL-DFR)
Change over thermostat installed on water inlet pipe (SL-DFR)
Supply air temperature sensor (SUP2) already integrated in all the post- treatment modules
Frost protection of the heat exchanger
Electric pre-heater (optional), speed reduction of the supply fan, bypass activation
Bypass
100% automatic proportional bypass used for free-cooling in summer time and defrost in wintertime
Four temperature control modes
Supply air temperature control
Extract air temprature control
Outdoor compensated supply air temperature control
Summer/winter control
UNIT MONITORING & PROTECTION

Filter clogging
Malfunction of connected sensor
Malfunction of fan
Malfunction of condensation pump
Heat exchanger
Fire alarm
Smoke alarm
Frost protection for water coils
Overheating electric battery
Heat exchanger efficiency
Alarm history
ACCESSORY MODULES
Electric heater battery (SL-PH, SL- DI)
Porportional control (PWM), for pre-heater and electric heater module
Water coils (SL-DC, SL-DFR, SL-DF)
Contact for motorized 3 way valve 0-1 OV
Direct expansion coils (SL- DX)
0-10V output for cooling or heating demand
External damper
Contact for spring return damper actuator (on/off)
COMMUNICATION
Remote touch screen panel
MODBUS RTU (RS 485)
BACNET IP
Webserver

REFERENCE

  1. Series:
    SLIM

  2. Size:
    800, 1200, 1600, 2000

  3. Preheating
    PH = With electric preheater integrated from factory
    – = Without preheater

  4. Handing
    L = Left handed R = Right handed

Technical Characteristics – Main Unit

Model| Connection (mm)| Nominal airflow (m3/h)| Efficiency heat exchanger (%)| Max. abs. Power (kW)| Max. Current (A)| Weight (kg)
---|---|---|---|---|---|---
SLIM-800| 400×200| 800| 92.4| 0.46| 2.9| 172
SLIM-800 PH| 500×250| 800| 92.4| 1.91| 12.9| 231
SLIM-1200| 600×300| 1200| 91.7| 0.91| 4.1| 266
SLIM-1200 PH| 600×350| 1200| 93.8| 0.93| 17.8| 315
SLIM-1600| 600×350| 1600| 92.4| 3.91| 12.8| 266
SLIM-1600 PH| 600×350| 1600| 92.4| 6.93| 15.9| 266
SLIM-2000| 600×350| 2000| 91.7| 4.5| 15.9| 315
SLIM-2000 PH| 600×350| 2000| 93.8| 8.47| 17.8| 315
Model| Connection (mm)| Nominal airflow (m 3 /h)| Efficiency heat **exchanger* (%)| Power supply| Max. abs. Power (kW)| Max. Current (A)| Weight (kg)**
---|---|---|---|---|---|---|---
SLIM-800| 400×200| 800| 92,4| 1/230V, 50Hz| 0,46| 2,9| 172
SLIM-800 PH| | 2,66| 12,9
SLIM-1200| 500×250| 1200| 92,4| 1/230V, 50Hz| 0,91| 4,1| 231
SLIM-1200 PH| 3,91| 17,8
SLIM-1600| 600×300| 1600| 91,7| 3/400V, 50Hz| 0,93| 3,7| 266
SLIM-1600 PH| | 6,93| 12,8
SLIM-2000| 600×350| 2000| 93,8| 3/400V, 50Hz| 0,97| 4,5| 315
SLIM-2000 PH| 8,47| 15,9

  • EXT: -10ºC @ 90%RH INT: 20ºC @ 50%RH

Acoustic Characteristics

The following table shows the average sound pressure level, in dB(A), in free field conditions at 3 m distance. Depending on the installation conditions, type of enclosures and characteristics of the materials used in walls and false ceilings, the real sound pressure levels may be different from the values given in the table.

Model| Inlet Sound Pressure (LpA)| Outlet Sound Pressure (LpA)| Radiated Sound Pressure (LpA)| Outlet Sound Power (LwA)| Radiated Sound Power (LwA)
---|---|---|---|---|---
SLIM 800| 45| 61| 48| 81| 68
SLIM 1200| 43| 64| 49| 84| 69
SLIM 1600| 55| 65| 51| 85| 68
SLIM 2000| 46| 63| 44| 83| 64
Model| **Sound pressure (LpA)*| Sound power (LwA)
---|---|---
Inlet| Outlet| Radiated| Inlet| Outlet| Radiated**
SLIM 800| 45| 61| 48| 65| 81| 68
SLIM 1200| 43| 64| 49| 63| 84| 69
SLIM 1600| 55| 65| 51| 75| 85| 68
SLIM 2000| 46| 63| 44| 66| 83| 64

  • Average sound pressure level, in dB(A), in free field conditions at 3 m distance.

Depending on the installation conditions, type of enclosures and characteristics of the materials used in walls and false ceilings, the real sound pressure levels may be different from the values given in the table.

Usage Instructions

The SLIM Series Heat Recovery Units are designed for use in public buildings, offices, stores, schools, restaurants, and other similar spaces. They are suitable for both newly constructed buildings and renovation projects. The units are available in four sizes based on nominal airflow at 250-300 Pa: 800 m3/h, 1200 m3/h, 1600 m3/h, and 2000 m3/h. The units come with various features such as high efficient backward curved fans, robust construction with termoacoustic flameproof insulation, low profile with lateral condensation connection and integrated condensation pump, low pressure minipleat filters, and counter flow heat exchanger (up to 94%) Eurovent certified. The SLIM units can be ordered with an integrable preheater module. The preheater module can be mounted from the factory or installed on site as an accessory. There are various accessory modules available for the SLIM Series Heat Recovery Units. Please refer to the product manual for more information.
For technical specifications such as connection size, nominal airflow, efficiency heat exchanger, power supply, current, weight, and acoustic characteristics, please refer to the product manual.
Low-Profile heat recovery units specially designed for false ceiling installation (indoors). Aluminium counter-flow heat exchanger up to 92% efficiency (EUROVENT certified), plug-fans with backward curved metal blades and EC motor. Integrated Bypass (100%) for Free-Cooling and Defrost. Suited for airflows up to 2.000 m3/h. Premium pre-configured control system for easy start-up with touch screen. The casing is made of 30 mm self-supporting double skinned panels (mineral wool, 100 kg/m3, thermal conductivity 0,037 W/mK). The inner and outer skin are made from galvanized steel. Easy access to all the components via the bottom access over generously sized SLIDING-doors. Filters are accessible from the side as well. Rectangular inlet and discharge connections.

Application
Public buildings, offices, stores, schools, restaurants, etc. Well suited for both newly constructed buildings and renovation projects.

Versions

  • Left hand / Right hand
  •  With integrated electric preheater / Without preheater.

Sizes by nominal airflow at 250-300 Pa
800 m3/h, 1200 m3/h, 1600 m3/h & 2000 m3/h.

Options
Integrable preheater module. SLIM units can be ordered with the preheater module mounted from factory or as an accessory to be installed on site.

Accessory modules (post-treatment):
External modules specially designed for the range.

  •  Electric battery.
  •  Hot water coil.
  • Cold water coil.
  • Reversible water coil for heating/cooling.
  •  Direct expansion.

TOP’s:

  • Sliding access doors – One Man Maintenance.
  •  Integrated condensation pump – Easy installing.
  •  Patented tight filter system – Good air quality.
  •  Patented Module fixation – Clean design.
  •  Bottom and side access to the filters – Easy maintenance.
  • All main components are easy removable.
  • Separate electrical cabinet facilitates commissioning and service.

Filter

  • M5 (ePM10 50%) filter on the extract air side to protect the heat exchanger.
  •  F7 (ePM1 70%) filter on the outdoor air side. It is possible to replace the F7 filter by a F9 (ePM1 80%) type on site.
  •  The filter clogging is controlled by differential pressure switches.

Control system

  •  Built-in programable control system (Plug & Play).
  •  Modbus RTU (RS485) and BACNET IP communication protocol.
  • Remote touchscreen panel included.

RECOVERY EFFICIENCY ACCORDING TO THE AIRFLOW
Values referring to the following conditions:
Outdoor temperature: -5ºC, RH=80%
Indoor temperature: +22ºC, RH=50%Soler Palau 800 m3-h Slim Heat Recovery
Units 04 RECOVERY EFFICIENCY RELATIVE TO OUTDOOR TEMPERATURE

Model| Airflow (m 3 /h)| OUTDOOR AIR| SUPPLY AIR| PERFORMANCE
---|---|---|---|---
Temperature (ºC)| RH (%)| Temperature (ºC)| RH (%)| Efficiency (%)| Recovered power (kW)
SLIM 800| 800| -10| 80| 17,6| 10,3| 86,2| 8,27
-5| 80| 17,8| 15,8| 84,4| 6,71
0| 70| 17,7| 21| 80,6| 5,12
5| 70| 18,2| 29,2| 77,6| 3,74
SLIM 1200| 1200| -10| 80| 17,6| 10,3| 86,2| 12,41
-5| 80| 17,8| 15,8| 84,4| 10,06
0| 70| 17,7| 21| 80,6| 7,69
5| 70| 18,2| 29,2| 77,6| 5,62
SLIM 1600| 1600| -10| 80| 17,8| 10,2| 86,9| 16,68
-5| 80| 18| 15,6| 85,1| 13,53
0| 70| 17,8| 20,9| 81,1| 10,31
5| 70| 18,3| 29,1| 78| 7,53
SLIM 2000| 2000| -10| 80| 18| 10| 87,6| 21,02
-5| 80| 18,2| 15,4| 85,9| 17,07
0| 70| 18,1| 20,6| 82,1| 13,05
5| 70| 18,4| 28,7| 79,1| 9,54

  • For indoor temperature 22ºC, RH=50%.

TECHNICAL CHARACTERISTICS OF EXTERNAL MODULES

Electric PRE-HEATER

Type| Supply power (kW)| Absorved current (A)| Voltage (V)| Weight (kg)| Max. Air pressure drop (Pa)
---|---|---|---|---|---
SL-PH 800 2,2 M| 2,2| 10| 1/230V, 50Hz| 1,8| 30 Pa
SL-PH 1200 3 M| 3| 14| 1/230V, 50Hz| 3,6| 30 Pa
SL-PH 1600 6 T| 6| 9| 3/400V, 50Hz| 5,4| 30 Pa
SL-PH 2000 7,5 T| 7,5| 11| 3/400V, 50Hz| 7,2| 30 Pa

Electric POST-HEATER

Type| Supply power (kW)| Absorved current (A)| Voltage (V)| Weight (kg)
---|---|---|---|---
SL-DI 800 3 M| 3| 14| 1/230V, 50Hz| 34,5
SL-DI 1200 4 M| 4| 18| 1/230V, 50Hz| 42
SL-DI 1600 7,5 T| 7,5| 11| 3/400V, 50Hz| 51,6
SL-DI 2000 9 T| 9| 14| 3/400V, 50Hz| 54,4

Hot water coil

Type| Heating capacity **(kW)*| Water content (L)| Weight (without liquid) (kg)| Recommended 3 way valve**
---|---|---|---|---
SL-DC 800 2| 4,5| 0,4| 7,6| 3WV DN15 KVS1 PROP 24V
SL-DC 1200 2| 6,6| 0,7| 9,7| 3WV DN15 KVS1,6 PROP 24V
SL-DC 1600 2| 9,3| 1| 11,4| 3WV DN15 KVS2,5 PROP 24V
SL-DC 2000 2| 11,7| 1,1| 12,4| 3WV DN15 KVS2,5 PROP 24V

Reversible water coil for 2 pipes installation

Type| Heating capacity (kW) (1)| Cooling capacity (kW) (2 )| Water content (L)| Weight (without liquid) (kg)| Recommended 3 way valve
---|---|---|---|---|---
SL-DFR 800 3| 4,3| 3,4| 0,6| 8,4| 3WV DN15 KVS1 PROP 24V
SL-DFR 1200 3| 7,2| 5,8| 1| 10,8| 3WV DN15 KVS1,6 PROP 24V
SL-DFR 1600 3| 9,2| 6,76| 1,3| 12,6| 3WV DN20 KVS4 PROP 24V
SL-DFR 2000 3| 11,7| 8,6| 1,7| 13,7| 3WV DN20 KVS4 PROP 24V

  1.  Referred to nominal air flow. In/Out water temperature 50/40ºC.
  2. Referred to nominal air flow. In/Out water temperature 7/12ºC.

Chilled water coil

Type| Cooling capacity **(kW)*| Water content (L)| Weight (without liquid) (kg)| Recommended 3 way valve**
---|---|---|---|---
SL-DF 800 5| 4,8| 1| 10,5| 3WV DN15 KVS1,6 PROP 24V
SL-DF 1200 5| 8,3| 1,6| 13,7| 3WV DN15 KVS2,5 PROP 24V
SL-DF 1600 5| 10,9| 2,3| 15,8| 3WV DN15 KVS2,5 PROP 24V
SL-DF 2000 5| 13,8| 3| 17,3| 3WV DN20 KVS4 PROP 24V

  • Referred to nominal air flow. In/Out water temperature 7/12ºC.

Direct expansion coil

Type| Cooling power (kW) 7ºC EVAP| Heating power (kW) 39ºC COND| Filling capacity (l)| Weight (without refrigerant) (kg)
---|---|---|---|---
SL-DX 800 4| 4,5| 4,4| 0,8| 9,7
SL-DX 1200 4| 7,4| 7,2| 1,2| 12,7
SL-DX 1600 4| 8,4| 8,8| 1,7| 15,5
SL-DX 2000 4| 11,6| 11,6| 2,3| 16,6

  • R410A. Sub cooling= 0ºC. Overheating= 5ºC

MAIN COMPONENTS (SYNOPTIC INSTALLATION EXAMPLE )

Soler Palau 800 m3-h Slim Heat Recovery Units 05

  • F1 Supply filter
  • F2 Extract filter
  • BP Bypass damper
  • M1 Supply motor
  • M2 Extract motor
  • HEX Heat Exchanger
  • DP1 Pressure switch
  • DP2 Pressure switch
  • DP3 Pressure transmitter
  • DP4 Pressure transmitter
  • Ti Temperature probe (T sup)
  • Tr Temperature probe (T indoor)
  • Te Temperature probe (T out)
  • Tx Temperature probe (T exha)

STANDARD CONFIGURATIONS

DIMENSIONS – MAIN UNIT

Model| A| A1| B| B1| C| D| D1| E| E1| F| G| H
---|---|---|---|---|---|---|---|---|---|---|---|---
SLIM 800| 1700| 1659| 1080| 1130| 380| 400| 420| 200| 220| 85| 110| 110
SLIM 1200| 1700| 1659| 1560| 1610| 380| 500| 520| 250| 270| 155| 250| 110
SLIM 1600| 1700| 1659| 1760| 1810| 420| 600| 620| 300| 320| 155| 250| 110
SLIM 2000| 2000| 1953| 1760| 1810| 500| 600| 620| 350| 370| 155| 250| 110
Model| I| J| K| L| M| N| O| P| Q| R| S
---|---|---|---|---|---|---|---|---|---|---|---
SLIM 800| 55| 125| 45| 167| 8| 685| 80| 22| 14,4| 17| M8
SLIM 1200| 55| 75| 45| 167| 8| 685| 80| 22| 14,4| 17| M8
SLIM 1600| 55| 65| 45| 167| 8| 677| 80| 22| 14,4| 17| M8
SLIM 2000| 55| 95| 45| 167| 8| 785| 86| 22| 14,4| 17| M8

SL-DC Hot water coil
Version -R SL-DC Hot water coil
Version -L
SL-DF/DFR/DX Cold water coil / Reversible / DX
Version -R
SL-DF/DFR/DX Cold water coil / Reversible / DX
Version -L
SL-DF / SL-DFR / SL-DX

Size/Model| A| B| C| d| D| E| F| G| H| IA| J| K
---|---|---|---|---|---|---|---|---|---|---|---|---
800| 700| 540| 380| 17| 22| 73| 145| 584| 482| 685| 400| 200
1200| 700| 780| 380| 17| 22| 73| 145| 824| 482| 925| 500| 250
1600| 700| 880| 420| 17| 22| 73| 145| 924| 482| 1025| 600| 298
2000| 700| 880| 500| 17| 22| 73| 145| 924| 482| 1025| 600| 350
Size/Model| L| M| N| O| P| Q| R| S| T| U| V| W| X
---|---|---|---|---|---|---|---|---|---|---|---|---|---
800| 420| 220| 55| 85| 55| 125| 107,6| 133| 88,4| 100| 22,7| 119,8| 54
1200| 520| 270| 125| 155| 55| 75| 107,6| 133| 88,4| 100| 22,7| 119,8| 54
1600| 620| 320| 125| 155| 55| 67| 97,6| 133| 88,4| 100| 22,7| 119,8| 54
2000| 620| 370| 125| 155| 55| 95| 102,6| 133| 88,4| 100| 22,7| 119,8| 54

SL-DI Electric battery
Version -R
SL-DI Electric battery
Version -L SL-DI

Size/Model| A| B| C| d| D| E| F| G| H
---|---|---|---|---|---|---|---|---|---
800| 700| 540| 380| 17| 22| 73| 145| 584| 482
1200| 700| 780| 380| 17| 22| 73| 145| 824| 482
1600| 700| 880| 420| 17| 22| 73| 145| 924| 482
2000| 700| 880| 500| 17| 22| 73| 145| 924| 482
Size/Model| IE| J| K| L| M| N| O| P| Q
---|---|---|---|---|---|---|---|---|---
800| 645| 400| 200| 420| 220| 55| 85| 55| 125
1200| 885| 500| 250| 520| 270| 125| 155| 55| 75
1600| 985| 600| 298| 620| 320| 125| 155| 55| 67
2000| 985| 600| 350| 620| 370| 125| 155| 55| 95

PERFORMANCE CURVES

  • qv: Flow rate (m3/h).
  • psf: Static pressure in Pa and mmcda.
  • Pabs = Absorbed power at maximum speed (W).
  •  Normal dry air at 20°C and 760 mm.c.d.Hg.
  •  Tests performed according to ISO 5801 and AMCA 210-99.
  •  Absorbed power corresponding to a single circuit.

Soler Palau 800 m3-h Slim Heat Recovery Units 19

  • qv: Flow rate (m3/h).
  •  psf: Static pressure in Pa and mmcda.
  •  Pabs = Absorbed power at maximum speed (W).
  •  Normal dry air at 20°C and 760 mm.c.d.Hg.
  • Tests performed according to ISO 5801 and AMCA 210-99.
  •  Absorbed power corresponding to a single circuit.
    Soler Palau 800 m3-h Slim Heat Recovery Units 20

Soler Palau 800 m3-h Slim Heat Recovery Units 23

SPECIFIC ACCESSORIES

SLIM units are complemented with a wide range of air treatment accessories, specifically designed to integrate in the supply.

Hot water coil SL-DC
External module that includes a hot water coil. Suitable to be combined with 2 tube-systems.

Reversible water coil
SL-DFR
External module that includes a reversible water coil. Suitable to be combined with 2 tubes systems, both for heating and cooling applications

Direct expansion coil
SL-DX
External module that includes a direct expansion coil for R-410A. Allows the integration of the unit in air conditioning systems of the main existing manufacturers.

Electric post-heater
SL-DI
External module that includes an electrical battery.

Chilled water coil
SL-DF
External module that includes a chilled water coil. Suitable to be combined with 2 tube-systems.

MOUNTING ACCESSORIES

Soler Palau 800 m3-h Slim Heat Recovery Units 30

Heat recovery unit model| Connection (h x w)| M5
spare filter| F7
spare filter| F9 filter (to replace F7 filter)| Rectangular flexible connection| Antivibration mounts (4 pieces kit)| Isolation dampers| On-off damper actuator (spring return)
---|---|---|---|---|---|---|---|---
SLIM 800| 400 x 200 mm| AFR-SLIM 800 M5| AFR-SLIM 800 F7| AFR-SLIM 800 F9| IAE-200| KIT AM CAD-COMPACT / SLIM| IJK-200| LF-230 S
SLIM 1200| 500 x 250 mm| AFR-SLIM 1200 M5| AFR-SLIM 1200 F7| AFR-SLIM 1200 F9| IAE-225| KIT AM CAD-COMPACT / SLIM| IJK-225| LF-230 S
SLIM 1600| 600 x 300 mm| AFR-SLIM 1600 M5| AFR-SLIM 1600 F7| AFR-SLIM 1600 F9| IAE-285| KIT AM CAD-COMPACT / SLIM| IJK-285| LF-230 S
SLIM 2000| 600 x 350 mm| AFR-SLIM 2000 M5| AFR-SLIM 2000 F7| AFR-SLIM 2000 F9| IAE-315| KIT AM CAD-COMPACT / SLIM| IJK-315| LF-230 S

ACCESSORIES

IJK
Manual motorisable dampers. Supplied with standard rectangular flanges. Manufactured from galvanised sheet steel. Fitted as standard with removable handle. Shaft diameter: 10 mm.
IAE
Rectangular flexible connection.

Model| A| B| C| D| E| F| G| Weight (kg)
---|---|---|---|---|---|---|---|---
IJK-200| 162| 400| 200| 420| 220| 440| 240| 3,3
IJK-225| 162| 500| 250| 520| 270| 540| 290| 4,2
IJK-285| 162| 600| 300| 620| 320| 640| 340| 5,4
IJK-315| 162| 600| 350| 620| 370| 640| 390| 5,8

Model A B C D E F
IAE-200 198 220 240 400 420 440
IAE-225 248 270 290 500 520 540
IAE-285 298 320 340 600 620 640
IAE-315 348 370 390 600 620 640

LF 230 S
On-Off actuator with spring return. Power supply: 230 V 50 Hz.

REQUIRED ACCESORIES FOR EXTERNAL MODULES (WATER COILS)
3 WAY VALVE WITH PROPORTIONAL ACTUATOR
Three way motorized control valve. Pressure 16 bar.
Rp” internal nut.
Nickel-plated forged brass casing. Stainless steel valve cone. Stainless steel shaft.
Average temperatures -10ºC…+120ºC. 5Nm mounted rotatory actuator.
AC/DC 24V, proportional.
90s/90º valve response time.
DC 2…10V working range.
IP 54.

Heat recovery unit model| 3-way-valve for SL-DC modules| 3 -way-valve for SLDFR modules| 3-way-valve for SL-DF modules
---|---|---|---
SLIM 800| 3WV DN15 KVS1 PROP 24V| 3WV DN15 KVS1 PROP 24V| 3WV DN15 KVS1,6 PROP 24V
SLIM 1200| 3WV DN15 KVS1,6 PROP 24V| 3WV DN15 KVS1,6 PROP 24V| 3WV DN15 KVS2,5 PROP 24V
SLIM 1600| 3WV DN15 KVS2,5 PROP 24V| 3WV DN20 KVS4 PROP 24V| 3WV DN15 KVS2,5 PROP 24V
SLIM 2000| 3WV DN15 KVS2,5 PROP 24V| 3WV DN20 KVS4 PROP 24V| 3WV DN20 KVS4 PROP 24V

Note: These are only general recommendations that will meet the KVS requirements in a certain installation type. It is hightly recommended to select the 3WV through Easy Vent Selector.

ELECTRIC ACCESORIES FOR VENTILATION CONTROL

Accesories for Variale Air Volume.
VAV by CO 2 level| Accesories for constant air flow operation CAV| Accesories for constant pressure operation COP
---|---|---
Duct| Ambience
SCO2-G 0-10V| AIRSENS CO2| Airflow transmitters included in the unit (factory mounted)| TDP-S

AIRSENS CO2
Indoor air-quality control device with a built-in CO2 sensor. Especially designed to create DCV systems directly used with single-phase or ECOWATT fans, depending on the relay or analogue control output selected.
Main features:
4 working modes:

  •  Relay output and Modbus (reading).
  •  0-10V output and Modbus (reading).
  • 2-10V output and Modbus (reading)
  •  Full Modbus control.

Adjustable set point. Air-quality level indicator (3-LED diffuser). Adjustable brightness 3-LED diffuser.

Model| Electrical supply| Power (W)| Relay| Analogue output| Lecture range| IP
Protection| Dimensions LxWxH (mm)
---|---|---|---|---|---|---|---
AIRSENS-CO2| 100-240 VAC
50/60Hz| 0,7W| 3A
250 VAC| 0-10 V
2-10 V| 450-2000 ppm| IP30| 122x23x89

TDP-D
Pressure sensor with display. It controls the pressure at the fan inlet.
SCO2-G 0/10V
CO2 sensor for duct installation. It controls the ventilation depending on the CO2 levels in the air circulating through the extraction duct. Outlet: 0-10V. Power: 24 VDC.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Soler Palau User Manuals

Related Manuals