ZURN 950XL3 Double Check Backflow Preventer Instructions
- June 13, 2024
- ZURN
Table of Contents
950XL3 Double Check Backflow
Preventer Instructions
950XL3 Double Check Backflow Preventer
Double Check Valve Assembly (3/4”, 1”, 1 1/4”, 1 1/2” & 2”)
This product contains a weighted average lead content less than 0.25% for wetted surfaces.
Meets the requirements of NSF/ANSI/CAN 61 and 372
- Installation
- Testing
- Maintenance Instructions
INSTALLATION INSTRUCTIONS
CAUTION: Installation of Backflow Preventers must be performed by qualified,
licensed personnel. The installer should be sure the proper device has been
selected for the particular installation. Faulty installation could result in
an improperly functioning device.
ZURN WILKINS Model 950XL3 Double Check Valve assemblies are for use on potable
water lines where a health hazard does not exist in the event of a backflow
situation.
Proper performance is dependent upon following these installation instructions
and prevailing governmental and industry standards and codes. Failure to do
so, according to ZURN WILKINS Limited Warranty “…releases ZURN WILKINS of any
liability that it
might otherwise have with respect to that device.” Such failure could also
result in an improperly functioning device.
Damage to the device could result wherever water hammer and/or water thermal
expansion could create excessive line pressure.
Where this could occur, shock arresters, check valves and/or pressure relief
valves should be installed downstream of the device.
If installation is in a pit or vault, the Backflow Preventer must never be
submerged in water because this could cause a cross-connection. Make sure that
the pit or vault always remains dry by providing ample drainage.
-
Before installing a Model 950XL3 Backflow Preventer, flush the line thoroughly to remove all debris, chips and other foreign matter. If required, a lead-free strainer should be placed upstream of the Backflow Preventer.
CAUTION : Do not use a strainer in seldom used emergency waterlines such as fire lines. -
Provide adequate space around the installed unit so that the test cocks will be accessible for testing and servicing.
-
Install valve at least 12 inches above surrounding flood level.
-
Always consult local codes for installation methods, approvals and guidance.
VERTICAL INSTALLATION
Vertical installation is acceptable in applications where inlet and outlet
piping are flowing vertically upwards.
All the basic installation instructions apply to such installations.
INDOOR INSTALLATION
Indoor installation is preferred in areas that are subject to freezing
conditions. All the basic installation instructions apply to such
installations.
PARALLEL INSTALLATION
Where uninterrupted service from a single meter connection must be maintained,
two or more Backflow Preventers may be connected in parallel. All the basic
installation instructions apply to parallel installation. Be sure to allow
adequate room between the units for testing and repair.
! WARNING : Cancer and Reproductive Harm –
www.P65Warnings.ca.gov
! ADVERTENCIA : Cáncer y daño reproductivo –
www.P65Warnings.ca.gov
! AVERTISSEMENT : Cancer et néfastes sur la reproduction –
www.P65Warnings.ca.gov
PLACING THE MODEL 950XL3 IN SERVICE
After the installation of a Model 950XL3 has been completed, place the unit in
service as follows:
-
Start with both shut-off valves closed.
Slowly open the inlet shut-off valve until the backflow preventer is completely pressurized. -
When the unit has been pressurized, vent any trapped air by slightly opening each of the four test cocks.
-
Slowly open the downstream shutoff valve.
The Model 950XL3 Double Check Valve assembly is now in service. -
After the Model 950XL3 has been properly installed, test the device (see “Testing Procedures”). If the device fails the test, remove the check valve assembly and thoroughly flush the device. Clean rubber seals and seats of all debris and place unit back in service.
OUTDOOR INSTALLATION
The Model 950XL3 Backflow Preventer may be installed outdoors only if the
device is protected against freezing conditions.
Exposure to freezing conditions will result in improper function or damage to
the device. The installation location must be kept above 32°F. All the basic
installation instructions apply.
Testing Procedures
MODEL 950XL3 DOUBLE CHECK VALVE ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1 – TIGHTNESS OF #1 CHECK VALVE
REQUIREMENT: The static pressure drop across check valve #1 shall be at least
1.0 psid.
PROCEDURE:
- Slowly open all 4 test cocks to remove any foreign material and attach fittings.
- Attach hose from the high side of the test kit to the #2 test cock.
- Open test cock #2 and bleed all air from the hose and gauge by opening the high side bleed needle valve. Close high side bleed needle valve. Close #2 shut-off valve then close the #1 shut-off valve.
- Hold gauge at same level as test cock #3. Slowly open test cock #3. Record the static pressure drop across check valve #1 after gauge reading stabilizes and water stops running out of test cock #3.
- Close all test cocks, open shut-off valve #1 and remove test equipment.
TEST NO. 2 – TIGHTNESS OF #2 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #2 shall be at least 1.0 psid.
PROCEDURE:
- Attach hose from the high side of the test kit to the #3 test cock.
- Open test cock #3 and bleed all air from the hose and gauge by opening the high side bleed needle valve. Close high side bleed needle valve. Close #1 shut-off valve.
- Hold gauge at same level as test cock #4. Slowly open test cock #4. Record the static pressure drop across check valve #2 after gauge reading stabilizes and water stops running out of test cock #4.
- Close all test cocks, slowly open shut-off valve #1 & #2 and remove test equipment.
Maintenance Instructions
All Model 950XL3 Double Check Valve Backflow Preventers must be inspected and maintained by licensed personnel at least once a year or more frequently as specified by local codes. Replacement of worn or damaged parts must only be made with genuine “ZURN WILKINS” parts. The ZURN WILKINS Certificate of Limited Warranty provides that failure to do so “…releases ZURN WILKINS of any liability that it might otherwise have with respect to that device.” Such failure could also result in an improperly functioning device.
CHECK CARTRIDGE ASSEMBLY
GENERAL MAINTENANCE
- Clean all parts thoroughly with water after disassembly.
- Carefully inspect rubber seal rings and o-rings for damage.
- Test unit after reassembly for proper operation (see “Testing Procedures”).
SERVICING CHECK VALVES
-
Close inlet and outlet shut-off valves.
-
Open No. 2, No. 3 and No. 4 test cocks to release pressure from valve.
-
Unscrew check valve cover screws using appropriately sized wrench or screwdriver.
-
Remove check cover and check cartridge assembly. Ensure that the #1 seat o-ring is removed from body.
-
Inspect rubber o-rings for cuts or embedded debris.
-
Press and rotate #2 spring retainer to remove #2 poppet.
Press and rotate #2 seat to remove #1 poppet. CAUTION: Checks are spring loaded. Take extra care with 2″ valves, s these springs are longer and stiffer than other sizes. -
Inspect rubber seal ring for cuts or embedded debris.
-
To remove seal ring, remove screw and washer.
-
If the reverse side of the seal ring is unused, it is possible to invert the seal ring. This would be considered a temporary solution to fixing a fouled check and should be replaced with a new seal ring as soon as possible.
-
Inspect both seats for wear on the seating surface. If damaged, replaced seat.
-
Inspect valve cavity and remove any debris.
-
Reverse the above procedure to reinstall check valve assembly and check cover, making sure the 3 test cocks remain open.
Wiring Diagram for 950XL3BFSS
NOTE : Model 950XL3BFSS features Zurn Wilkins model 49BRXLSST butterfly valves with supervisory switch. The gearbox ships from the factory with a cable gland to protect the internals from dust and moisture during shipping, storage, and installation. For outdoor installations the electrical contractor shall remove the cable gland prior to installing the appropriate conduit and junction box for making the supervisory switch connections outlined below. Steps shall be taken to ensure that the connection to the gearbox forms a watertight seal. Failure to do so may result in water intrusion that may cause the switch to malfunction. Contact the factory for a replacement switch if needed.
Green Lead provided is ground for switch housing
Switch Rating: 10AMP/ 115 VAC .5AMP/28 VDC
Cap unused leads with wire nuts and tuck inside junction box (not provided)
NOTE : Supervisory tamper switches are for indoor and outdoor use.
Troubleshooting
PROBLEM | POSSIBLE CAUSES | CORRECTIVE ACTION |
---|---|---|
1. LEAKING CHECK VALVES | 1. Debris on seat or seal ring | 1. Clean seat and |
seal ring area
2. LOW OR NO FLOW| 2. Damaged seat| 2. Replaced seat
| 3. Damaged seat o-ring| 3. Replaced seat o-ring
| 1. Device installed backwards
2. Shut-off valves or valve upstream may
not be fully open
3. Low supply pressure| 1. Verify flow directions arrow
2. Turn handles counterclockwise
3. Attach pressure gauge to test cock #1 and
verify pressure
Performance Characteristics
Capacity thru Schedule 40 Pipe (GPM)
Pipe size| 5 ft/sec| 7.5 ft/sec| 10 ft/sec| 15 ft/sec
3/4″| 8| 12| 17| 25
1″| 13| 20| 27| 40
1 1/4″| 23| 35| 47| 70
1 1/2″| 32| 48| 63| 95
2″| 52| 78| 105| 167
SPECIFICATIONS
Minimum working water pressure | 20 PSI |
---|---|
Maximum working water pressure | 175 PSI |
Minimum working water temperature | 33°F |
Maximum working water temperature | 180°F |
Hydrostatic test pressure | 350 PSI |
Threaded end connections | ANSI B1.20.1 |
Proper performance is dependent upon licensed, qualified personnel performing
regular, periodic testing according to ZURN WILKINS’ specifications and
prevailing governmental & industry standards and codes and upon following
these installation instructions.
Failure to do so releases ZURN WILKINS of any liability that it might
otherwise have with respect to that device. Such failure could also result in
an improperly functioning device.
IS950XL3 (REV. B 9/22)
1747 Commerce Way,
Paso Robles, CA 93446
Phone:855-663-9876
Fax:805-238-5766
www.zurn.com