ZURN 500XL Water Pressure Reducing Valve with Integral By Pass Check Valve Instruction Manual

June 4, 2024
ZURN

ZURN 500XL Water Pressure Reducing Valve with Integral By Pass Check

Valve

ZURN-500XL-Water-Pressure-Reducing-Valve with Integral Bypass Check-Valve-
PRODUCT

Application

Zurn Wilkins model 500XL is designed for installation on potable water lines to reduce high inlet pressure to a lower outlet pressure. The high flow capacity makes this device most suitable for industrial water lines and commercial water systems. The direct-acting integral by-pass design prevents buildup of excessive system pressure caused by thermal expansion. The balanced piston design enables the regulator to react in a smooth and responsive manner to changes in system flow demand, while at the same time, providing protection from inlet pressure changes.
Standards Compliance

  • ASSE® Listed 1003 (1/2″ thru 2 1/2″)
  • IAPMO® Listed (1/2″ thru 2″)
  • CSA® Certified (1/2″ thru 2″)
  • City of Los Angeles Approved (1/2″ thru 2″)
  • Meets the requirements of NSF/ANSI/CAN 61

Materials

  • Main valve body Low Lead Cast bronze ASTM B 584
  • Access covers Low Lead Cast bronze ASTM B 584 Low Lead Brass
  • Fasteners Stainless steel, 300 series
  • Stem & plunger Low Lead Cast bronze ASTM B 584 Low Lead Brass
  • Elastomers Buna Nitrile (FDA approved) EPDM (FDA approved)
  • Cap gaskets Natural vulcanized fibre Acetal (Delrin™ 500)
  • Springs Oil tempered wire, ASTM A 229
  • Seat Stainless steel, 300 series

Features
Sizes: 1/2″, 3/4″, 1″, 1 1/4″, 1 1/2″, 2″, 2 1/2″, 3″

  • Maximum working water pressure 300 psi
  • Maximum working water temperature 140° F
  • Reduced pressure range 25 psi to 75 psi
  • Factory preset (field set 2 1/2” & 3”) 50 psi
  • Threaded connections (FNPT) ANSI B1.20.1
  • Copper connections (FC) ANSI B 16.22
  • CPVC tailpiece: Max.hot water temp. 140°F @ 100 psi
  • Cold water rated temp. 73.4°F @ 400 psi

Options

(Suffixes can be combined)

  • standard with single union FNPT inlet x FNPT outlet (1/2” thru 2”) and less union (21/2” & 3”)
  • C – copper sweat connection (1/2″ thru 2″) copper sweat strainer 3/4″ & 1″ only All other strainers are FNPT
  • HR – 75 psi to 125 psi spring range, factory set at 85 psi (field set 2 1/2” & 3”)
  • HLR – 10 psi to 125 psi spring range, factory set at 50 psi
  • HTSTSC – 180°F maximum temp, stainless steel trim, spring, sealed cage
  • L – less integral by-pass check valve (3/4”-2”)
  • LPV – 180°F maximum temp with 10 psi to 35 psi spring range, factory set at 20 psi
  • SC – sealed cage bell housing and stainless steel adjustment screw
  • SW – made for salt water service
  • YSBR – with lead-free bronze “Y” strainer on inlet 510XL – 400 psi inlet rating and 75 psi to 125 psi spring range, factory set at 85 psi (field set 2 1/2” & 3”)
  • P – tapped and plugged for gauge
  • G – tapped and plugged with gauge
  • CPVC – CPVC tailpiece connection (3/4”-1”)

Accessories

Repair kit (rubber only)

Dimensions & Weights (do not include pkg.)

SIZE|

CONNECTIONS

| DIMENSIONS (approximate)| WEIGHT
---|---|---|---
A| B| C| D
in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| lbs.| kg.
1/2| 15| SINGLE UNION| 4 1/2| 108| 6| 152| 1 5/8| 41| 2 3/4| 70| 3| 1.5
3/4| 20| SINGLE UNION| 4 5/8| 118| 6| 152| 1 1/8| 29| 2 3/4| 70| 4| 2.0
1| 25| SINGLE UNION| 5 1/8| 130| 6 7/8| 175| 1 5/8| 41| 3 5/16| 84| 6| 3.0
1 1/4| 32| SINGLE UNION| 6 5/16| 160| 7 1/4| 184| 1 3/4| 45| 4| 102| 7| 3.0
1 1/2| 40| SINGLE UNION| 8 5/16| 211| 10| 254| 1 7/8| 48| 5| 127| 14| 6.5
2| 50| SINGLE UNION| 9 1/2| 241| 10 3/4| 273| 2 1/8| 54| 6 1/2| 165| 20| 9.0
2 1/2| 65| LESS UNION| 10| 254| 14 1/2| 368| 3| 76| 8| 203| 28| 12.5
3| 80| LESS UNION| 11 1/8| 283| 16| 406| 3 1/2| 89| 8| 203| 44| 20.0

Flow Characteristics

MODEL 500XL 1/2″ THRU 3″ (STANDARD & METRIC)

ZURN-500XL-Water-Pressure-Reducing-Valve with Integral Bypass Check-Valve-
FIG2

“Flow curves are based on a 50 psi pressure differential

Typical Installation
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. The assembly shall be installed with sufficient side clearance for testing and maintenance. The Model 500XL may be installed in any position. If installed in a pit, vault, or inside the application, specify the “SC” sealed cage option. Multiple installations are recommended for wide demand variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet).
Caution: Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify the correct pressure setting. Do not bottom adjustment bolt on the bell housing.

ZURN-500XL-Water-Pressure-Reducing-Valve with Integral Bypass Check-Valve-
FIG3

Specifications

The Pressure Reducing Valve shall be certified to NSF/ANSI/CAN 61, consisting of a low lead bronze body and bronze bell housing, a separate access cover for the plunger and a bolt to adjust the downstream pressure. The bronze bell housing and access cap shall be threaded to the body and shall not require the use of ferrous screws. The assembly shall be of the balanced piston design and shall reduce pressure in both flow and no-flow conditions. The assembly shall be accessible for maintenance without having to remove the body from the line. The Pressure Reducing Valve shall be a ZURN WILKINS Model 500XL.

Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 In Canada | Zurn Industries Limited 7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216 www.zurn.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>