ZURN 600XL Water Pressure Reducing Valve Instructions
- June 3, 2024
- ZURN
Table of Contents
ZURN 600XL Water Pressure Reducing Valve
Application
Zurn Wilkins model 600XL is designed for installation on potable water lines to reduce high inlet pressure to lower outlet pressure. The integral strainer makes this device most suitable for residential and commercial water systems requiring frequent cleaning because of sediment and debris. The direct-acting integral by-pass design prevents the buildup of excessive system pressure caused by thermal expansion. The balanced piston design enables the regulator to react in a smooth and responsive manner to changes in system flow demand, while at the same time, providing protection from inlet pressure changes.
Standards Compliance
- ASSE® Listed 1003
- IAPMO® Listed
- CSA® Certified
- City of Los Angeles Approved
- Meets the requirements of NSF/ANSI/CAN 61
Materials
- Main valve body
- Low Lead Cast Bronze ASTM B 584
- Access covers
- Low Lead Cast Bronze ASTM B 584
- Low Lead Brass
- Fasteners
- Stainless Steel, 300 Series
- Stem & plunger
- Low Lead Cast Bronze ASTM B 584
- Low Lead Brass
- Elastomers
- Buna Nitrile, (FDA Approved)
- EPDM, (FDA Approved)
- Cap gaskets
- Natural Vulcanized Fibre Acetal (Delrin™)
- Strainer screen
- Stainless Steel, 300 Series Strainer
- Seat
- Stainless Steel, 300 Series
Features
- Sizes: 1/2″, 3/4″, 1″, 1 1/4″, 1 1/2″, 2″
- Maximum working water pressure 300 psi
- Maximum working water temperature 140°F
- Reduced pressure range (standard) 25 psi to 75 psi
- Factory preset 50 psi
- Hydrostatic test pressure 300 psi
- CPVC tailpiece: Max. hot water temp. 140°F @ 100 psi
- Cold water rated temp. 73.4°F @ 400 psi
Options
(Suffixes can be combined)
- standard with 20 mesh strainer screen, SU, FNPT
- C – copper sweat connection (3/4″ thru 2″)
- HR – 75 psi to 125 psi spring range, factory set at 85 psi
- HLR – 10 psi to 125 psi spring range, factory set at 50 psi
- HTSTSC – 180°F maximum temp, stainless steel trim, spring, sealed cage
- L – less integral by-pass check valve
- LU – less union assembly, female x female (3/4″ & 1″ only)
- LPV – 180°F maximum temp with 10 psi to 35 psi spring range, factory set at 20 psi
- SC – sealed cage bell housing and stainless steel adjustment screw
- 610XL – 400 psi inlet rating and 75 psi to 125 psi spring range, factory set at 85 psi
- P – tapped and plugged for gauge
- G – tapped and plugged with gauge
- CPVC – CPVC tailpiece connection (1/2” – 1”)
- CH – Chrome stem & plunger
Dimensions & Weights
(do not include pkg.)
SIZE|
CONNECTIONS
| DIMENSIONS (approximate)| WEIGHT
---|---|---|---
A| B| C| D
in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| lbs.| kg.
1/2| 15| SINGLE UNION| 5 1/2| 133| 6 1/4| 159| 1 1/4| 32| 2 3/4| 70| 3| 1.5
1/2| 15| LESS UNION| 4 1/2| 114| 6 1/4| 159| 1 1/4| 32| 2 3/4| 70| 3| 1.5
3/4| 20| SINGLE UNION| 5 5/16| 135| 5 1/2| 140| 1 1/4| 32| 2 3/4| 70| 3| 1.5
3/4| 20| LESS UNION| 4 7/8| 121| 5 1/2| 140| 1 1/4| 32| 2 3/4| 70| 3| 1.5
1| 25| SINGLE UNION| 6 1/8| 156| 7 1/4| 184| 2| 51| 3 3/8| 86| 5| 2.5
1| 25| LESS UNION| 5 3/4| 146| 7 1/4| 184| 2| 51| 3 3/8| 86| 5| 2.5
1 1/4| 32| SINGLE UNION| 7 1/8| 181| 8| 203| 2| 51| 3 7/8| 100| 7| 3.0
1 1/2| 40| SINGLE UNION| 9 1/8| 232| 10| 254| 2 1/2| 64| 5| 127| 13| 6.0
2| 50| SINGLE UNION| 10 1/4| 260| 12| 305| 3| 76| 6 1/2| 165| 21| 9.5
Flow Characteristics
“Flow curves are based on a 50 psi pressure differential”
Typical Installation
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accor-dance with the latest edition of the Uniform Plumbing Code. The Model 600XL may be installed in any position. If installed in a pit, vault or inside application, specify the “SC” sealed cage option. Multiple installations are recommend for wide demand variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet). CAUTION: Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify correct pressure setting. Do not bottom adjustment bolt on bell housing.
Specifications
The Pressure Reducing Valve shall be certified to NSF/ANSI/CAN 61, consist of a low lead bronze body and bronze bell hous-ing, shall have separate access covers for the plunger and strainer screen and shall have a bolt to adjust the downstream pressure. The Pressure Reducing Valve shall be of the balanced piston design and shall reduce pressure in both flow and no-flow conditions. The bronze bell housing and access caps shall be threaded to the body and shall not require the use of ferrous screws. The Pressure Reducing Valve shall be a ZURN WILKINS Model 600XL.
Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph.
855-663-9876, Fax
805-238-5766
In Canada | Zurn Industries Limited
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6,
877-892-5216
www.zurn.com