ZURN ZTR Series ZTR6200-W2 AquaSense Exposed Sensor Battery Water Closet Flush Valve Instruction Manual
- June 5, 2024
- ZURN
Table of Contents
- ZURN ZTR Series ZTR6200-W2 AquaSense Exposed Sensor Battery Water Closet
- ZTR Series Flush Valve Package Contents
- Required Tools
- Optional Accessories
- Overview:
- Specifications:
- Important Safety Information:
- Prior to Installation:
- Sweat Solder Adapter Installation Instructions – STEP 1
- Control Stop Installation Instructions – STEP 2
- Flush Valve Installation – STEP 3
- Remove Sensor Cap (Applies to all versions) – STEP 4
- Battery Installation (Applies to battery and -LL versions only) – STEP
- Metal Sensor Cap Retrofit Installation Instructions
- Dip Switch Settings (when necessary)
- Sensor Range Adjustment (when necessary)
- Care and Cleaning Instruction
- TROUBLE SHOOTING GUIDE
- 2 Identify and remove any target from sensor field
- 3 Reduce sensor range distance (see page 10 for Sensor Range Adjustment
- 2 Remove valve from stop and fixture #3 Inspect/clean filter (see parts
- ZTR6200 Series Parts Breakdown (Plastic Cap)
- ZTR6200 Series Parts Breakdown (Metal Cap)
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ZURN ZTR Series ZTR6200-W2 AquaSense Exposed Sensor Battery Water Closet
Flush Valve
Water Closet Models:
ZTR6200-ONE 1.1 gpf
ZTR6200EV 1.28 gpf
ZTR6200-WS1 1.6 gpf
ZTR6200-WS1-DF 1.6/1.1 gpf
Urinal Models:
ZTR6203-ULF 0.125 gpf
ZTR6203-QRT 0.25 gpf
ZTR6203-EWS 0.5 gpf
ZTR6203-WS1 1.0 gpf
Power Options:
Battery (Standard)
- LL (Long Life Battery)
- HW (Hardwired using 7.6 VDC Power Supply Input)
Compliance:
- ADA Compliant – Operational Controls
- WaterSense Compliant
WARNING : Cancer and Reproductive Harm – www.P65Warnings.ca.gov
LIMITED WARRANTY
All goods sold hereunder are warranted to be free from defects in material and
factory workmanship for a period of three years from the date of purchase.
Decorative finishes warranted for one year. We will replace at no costs goods
that prove defective provided we are notified in writing of such defect and
the goods are returned to us prepaid at Sanford, NC, with evidence that they
have been properly maintained and used in accordance with instructions. We
shall not be responsible for any labor charges or any loss, injury or damages
whatsoever, including incidental or consequential damages. The sole and
exclusive remedy shall be limited to the replacement of the defective goods.
Before installation and use, the purchaser shall determine the suitability of
the product for his intended use and the purchaser assumes all risk and
liability whatever in connection therewith. Where permitted by law, the
implied warranty of merchantability is expressly excluded. If the products
sold hereunder are “consumer products,” the implied warranty of
merchantability is limited to a period of three years and shall be limited
solely to the replacement of the defective goods. All weights stated in our
catalogs and lists are approximate and are not guaranteed.
NOTICE: READ ENTIRE MANUAL PRIOR TO INSTALLING PRODUCT
ZTR Series Flush Valve Package Contents
Required Tools
Optional Accessories
Overview:
Zurn Aqua-Sense® ZTR Series Flushometer offers two models (closet/urinal) in a variety of flow rates. The ZTR design is a chrome plated brass body with an automatic sensor-operated piston-type valve. The flushometer incorporates a filtered bypass, high back pressure vacuum breaker, adjustable tailpiece, spud coupling, flange for top spud connection and a mechanical override pushbutton (MOB) for alternative flushing methods. The control stop has internal siphon- guard protection, vandal resistant stop cap, sweat solder kit, and cast wall flange with set screw. All internal and external gaskets and seals are chloramine resistant.
Specifications:
Voltage: 6 VDC Series [4 “AA” (Alkaline or Lithium) and/or external power option] Sensor Range: Factory set for user at end of elongated bowl or field adjustable by installer
Important Safety Information:
- Installer is responsible for ensuring the product is installed and conforms to all plumbing codes and ordinances.
- Do not convert or modify this Zurn product yourself. All warranties will be voided.
- Water supply lines must be sized according to building designer in order to provide adequate water supply for each fixture.
- Flush all water lines prior to making connections.
Prior to Installation:
- The ZTR flushometer is designed to operate optimally between 25 psi (running) to 80 psi (static) water pressure (172 to 552 kPa). Higher running pressure may be required for some fixtures. Consult fixture manufacturer for details.
- When installing a flushometer, it is important that the flush volume matches the requirements of the plumbing fixture.
- To protect chrome finish, do not use toothed tools to install or service the flushometer.
- Before installing your Zurn® Aqua-FIT® Faucet: the items listed below should already be installed on site.
- Closet
- Fixture carrier
- Drain line
- Water supply line
NOTE: The information in this manual is subject to change at any time without notice. Installations may be performed at different times of construction by different individuals. For this reason, these instructions should be left on-site with the facility or maintenance manager.
Sweat Solder Adapter Installation Instructions – STEP 1
NOTE: Before installation, turn off water supplies to existing fixture and remove flushometer if replacing an existing device.
STEP 1.1
Measure distance from finished wall to the center line of the fixture spud. If
necessary, cut water supply pipe 1-1/4″ shorter than this measurement. Deburr
by chamfering O.D. and I.D of end of water supply pipe.
STEP 1.2
Slide threaded sweat solder adapter onto water supply pipe until shoulder
stops on end of pipe. Then sweat-solder the adapter to water supply pipe.
STEP 1.3
Measure distance from finished wall to first thread of sweat solder adapter.
If necessary, cut chrome cover tube this length.
STEP 1.4
Slide wall escutcheon over chrome cover tube and slide both items over water
supply pipe. Press wall escutcheon flush against finished wall and tighten set
screw with hex wrench (supplied) to secure it in place.
Control Stop Installation Instructions – STEP 2
STEP 2.1
Install control stop assembly by threading it onto water supply pipe and
tightening with a smooth jawed wrench. Apply thread sealing compound or pipe
tape to male NPT thread on sweat solder adapter only.
STEP 2.2
When all stop valves are properly connected to the water supply line and water
pressure is available open the control stop using a flathead screwdriver and
turning the stop valve adjustment screw counterclockwise.
Prior to turning on main water supply line ensure all stop valves are closed
off tight by using a flathead screwdriver and turning
the stop valve adjustment screw clockwise.
Apply sealing compound here
Allow the water supply line to flush any debris or sediment that may be
present in the line. Close the control stop once the lines are completely
flushed.
Using a flathead screwdriver, turning counterclockwise, flush supply line by
opening the control stop. Turning clockwise will close control stop.
Flush Valve Installation – STEP 3
STEP 3.1
Prior to attaching flush valve to control stop(A) inspect and verify that the
O-ring (C) is located within the O-ring groove at the tailpiece. Ensure the
locking nut (D) and locking snap ring (E) are also present on the tailpiece.
See Figure 3.
STEP 3.2
Lubricate O-ring with water if necessary and carefully insert flush valve
tailpiece into the control stop valve to ensure O-ring remains seated. Tighten
locking nut using a smooth jawed wrench. See Figure 4.
STEP 3.3
Determine the length of vacuum breaker tube required to join the flush valve
and fixture spud, and cut if necessary. See Figure 5.
DO NOT use pipe sealant or plumbing grease on any valve component or coupling with the exception of the Control Stop Inlet! Ensure Vacuum Breaker does not twist or warp when tightening Vacuum Breaker Tube Nut.
STEP 3.4
Assemble and secure the vacuum breaker tube assembly and spud nut assembly to
the flush valve and fixture spud by hand tightening the spud nut and vacuum
breaker tube nut.
Adjust and plumb the valve assembly. Tighten all connections with smooth jawed
wrench and turn on water supply at the control stop. See Figure 5.
DO NOT cut vacuum breaker tube shorter than 6″ below the -C-L- indicator mark,
as vacuum breaker must be 6″ above the fixture. Consult plumbing Codes &
Regulations for specific details.
Remove Sensor Cap (Applies to all versions) – STEP 4
STEP 4.1
Use the 3/32″ Allen Wrench to loosen the internal set screw until it stops.
Screw will retract into the base to eliminate loss.
STEP 4.2
Rotate cap clockwise and pull cap up to remove.
STEP 4.3
Disconnect black solenoid plug before accessing batteries.
Battery Installation (Applies to battery and -LL versions only) – STEP
5A
STEP 5A.1
Remove sealed battery housing from sensor cap and remove top of sealed battery
housing by loosening the knurled screw by hand or with a flat head
screwdriver. Insert four batteries (supplied) into sealed battery housing and
ensure the batteries are inserted in the correct orientation. Reattach top to
the sealed battery housing.
STEP 5A.2
Connect sealed battery housing to sensor lens via RED connectors by aligning
arrows and pressing together.
Insert sealed battery housing into sensor cap. Ensure sticker on top of sealed
battery housing is oriented properly with the WHITE arrow pointing toward the
sensor lens. See Figure 8.1.
Utilize open space within the sensor cap to store the connected RED power connectors and BLACK solenoid connectors. See Figure 8.2.
Only use one battery type for installation. DO NOT mix and match Standard (Alkaline) and Long Life (Lithium) Batteries.
STEP 5A.3
Reattach the sensor cap and tighten cap screws.
Hardwire Installation (Applies to -HW versions only) – STEP 5B
STEP 5B.1
Route 10′ power supply cable (supplied) through the wall escutcheon
(supplied), wire supply tube (supplied) and the opening on the back of sensor
cap.
Connect power supply cable to sensor lens via RED connectors by aligning
arrows and pressing together.
Hand-tighten wire supply tube into the back of the sensor cap. Slide wall
escutcheon along wire supply tube until it is against the sensor cap.
Reattach the sensor cap to the flushometer valve body while ensuring wire
supply tube is properly inserted into thru-hole in wall.
Tighten the set screw using 3/32″ Allen wrench to secure sensor cap. Slide wall escutcheon flush with wall and secure using set screw and Allen wrench (supplied).
Connect ZTR-HW directly to HW6 Power Converter.
STEP 5B.2
Cut RED power connector from end of power supply cable not connected to the
Sensor Cap and strip back the wire insulation by minimum of 1/4″.
(Recommended if one to two ZTR flush valves are powered by one HW6.)
STEP 5B.3
Secure RED wire to Positive (+) and BLACK wire to Negative (-) screw terminals
on HW6.
Optional Junction Box (recommended when three or more ZTR flush valves
utilize one HW6)
Metal Sensor Cap Retrofit Installation Instructions
STEP 6.1
Remove vandal-resistant cover with Allen wrench from control stop (if present)
and turn control stop clockwise to turn off the water supply.
STEP 6.2
Press and hold the manual override button for 3 seconds to release any
residual pressure.
STEP 6.3
(For Hardwired Only) Loosen set screw in wall escutcheon and slide escutcheon
against the sensor cap
STEP 6.4
Use a 5/64″ Allen wrench to remove the two cap screws from the sensor cap and
remove the sensor cap. See Figure 17. Disconnect black solenoid plug.
STEP 6.5
(For Hardwired Only) Disconnect the red sensor plug and loosen the wire supply
tube. Remove both the wire supply tube and escutcheon. Keep for metal sensor
cap installation.
STEP 6.6
Remove the 4 sockets screws shown in Figure 18 using a M3 Allen wrench and
discard the screws
STEP 6.7
Note socket screw pockets in the ring insert and place over remaining 2 socket
screws See Figure 19.
STEP 6.8
Ensure ring insert set screws align with valve body holes shown in Figure 20.
Hand start the 4 new sockets screws(included) into the ring insert. Tighten
screws in the torque sequence shown on Figure 21.
STEP 6.9
Remove sealed battery housing from sensor cap and remove top of sealed battery
housing by loosening the knurled screw by hand or with a flat head
screwdriver. Insert four batteries (supplied) into sealed battery housing and
ensure the batteries are inserted in the correct orientation. Reattach top to
the sealed battery blousing.
STEP 6.10
Connect sealed battery housing to sensor lens via RED connectors by aligning
arrows and pressing together.
Insert sealed battery housing into sensor cap. Ensure sticker on top of sealed
battery housing is oriented properly with the WHITE arrow pointing toward the
sensor lens. See Figure 23.
Utilize open space within the sensor cap to store the connected RED power
connectors and BLACK solenoid connectors per the sticker on the battery
housing. See Figure 24.
STEP 6.11
(For Hardwired Only) Route 10′ power supply cable through the wall escutcheon,
wire supply tube, and the opening on the back of the metal sensor cap.
Connect the power supply cable to the sensor lens via the RED connectors by
aligning the arrows and pressing together.
Hand-tighten wire supply tube into the back of the sensor cap. Slide wall
escutcheon along wire supply tube until it is against the sensor cap.
STEP 6.12
Align set screw hole in sensor cap with key way in ring insert and place
sensor cap on valve body.
Rotate sensor cap counter clockwise until the set screw is visible in the
sensor cap hole and the sensor is facing forward. Using the 3/32″ Allen
wrench(provided) rotate the set screw clockwise to secure the cap.
Dip Switch Settings (when necessary)
Courtesy Flush
A courtesy flush can be enabled for the ZTR flushometer where the valve will
automatically flush at a specified interval based on customer preference.
Simply manipulate Dips witches #2 and #3 located on the Sensor Lens found on
the inside of the Sensor Cap to change the courtesy flush interval.
Courtesy Flush Interval | Dipswitch #2 | Dipswitch #3 |
---|---|---|
Disabled (Default Setting) | ON | ON |
24 hours | ON | OFF |
48 hours | OFF | ON |
72 hours | OFF | OFF |
Dual Flush Option (If Equipped) The dual flush option can be enabled by
turning switch #1 to the ON position.
Note: The ZTR Dual Flush must be originally ordered with the dual flush
option. Regular single flush valves will not function in dual flush mode
.
Sensor Range Adjustment (when necessary)
STEP 1.1
Place the Zurn Magic Magnet (optional accessory: P6900-ATMAG) against the cap
at the lower right corner of the Zurn logo under the sensor lens. Hold in
place until the valve automatically flushes and the red LED light flashes two
(2) times. Remove Magic Magnet from flush valve. The valve has entered
calibrate mode.
STEP 1.2
Place light-colored target at desired detection range away from sensor. After
10 more LED flashes followed by a double flash and/or flush the new detection
range will be calibrated and set.
Test new calibrated sensor range using targets of various material
types/textures to ensure calibration accuracy. Verify that sensor range does
not detect stall doors or other reflective surfaces.
Care and Cleaning Instruction
- Do not use any abrasive or chemical cleaners to clean the flushometer.
- ONLY use mildly warm soapy water, and then wipe the device dry with a clean/soft towel or cloth.
- Upon cleaning other areas of the restroom, be sure the sensor lenses are protected from other cleaning chemicals/solvents to prevent potential damages to the sensor and/or electronics.
- Turn off water supply and press manual override button to relieve all water pressure.
- Remove valve cap to expose ring insert. Using the M3 Allen Wrench remove the 4 screws and the ring insert.
- Remove the remaining 2 screws and the solenoid flange.
- Remove the piston kit from the valve body and inspect for damage to the seals or debris in the orifice. Excessive build up of debris may occur on filter screen.
TROUBLE SHOOTING GUIDE
PROBLEM | INDICATOR | POTENTIAL CAUSE | SOLUTION |
---|
**** Valve does not flush
| No lights on sensor board| Batteries not making contact| Remove and reinstall batteries correctly
– See step 5A for reference
Batteries reversed polarity
Sensor flashes (red) every 10 seconds| Low battery voltage indication| Replace
batteries – see Step 5A for reference
Sensor flashes (red) every 30 seconds| Continuous target detection of object
within sensor range| #1 Inspect and clean lens
2 Identify and remove any target from sensor field
3 Reduce sensor range distance (see page 10 for Sensor Range Adjustment
instructions.
Sensor detects user but fails to flush upon exiting sensor range| Batter power
level too low to activate full flush – sensor board automatically shuts down
to avoid open flush| Replace batteries See Step 5A for reference
Dirty sensor lens| Clean lens until free of debris
Loose or damaged solenoid connection| Inspect connection between solenoid and
sensor for proper insertion – step 4
No target detected| Install environment may require adjustment of the sensor
range from the factory settings| Re-calibrate sensor range – see Sensor Range
Adjustment (Figure 28) page 10
Valve does not shut off water (continuous flow)| Normal target detection|
Water pressure either too high or too low| Adjust water pressure to
recommended range:
35 to 80 psi running water pressure
Piston and / or solenoid plugged or damaged| Remove Piston and / or Solenoid to examine for damage or plugging. Clean piston / solenoid orifice if plugged.
Replace solenoid kit if solenoid di phragma is damaged.
Low or no power allowing solenoid to move to open position but not enough
power to return to closed position.| Replace batteries or restore power if
hardwired.
MOB (mechanical override button) sticking in open position| ****
Replace MOB.
Valve flows low (short flushing)| Valve does not evacuate fixture| Tailpiece filter is clogged with debris| #1 Turn stop off
2 Remove valve from stop and fixture #3 Inspect/clean filter (see parts
break- down – Part number 10)
Piston orifice is enlarged| Replace piston
Flush valve rating does not match fixture flush rating| Replace flush valve to
match fixture flush rating
Ghost flushing| Flush valve activates without target present.| Highly
reflective environment| Re-calibrate sensor range – see Sensor Range
Adjustment
Sensor range set too far, picking up other objects.
Continuous flushing| Valve flushes every 30 seconds.| Magnet stored in sensor
cap.| Remove magnet from sensor cap. Do not store magnet in flush valve.
Electronic Control Board| Cannot adjust sensor range| Processor latched| Reset
electronics module by removing cap, disconnect power connector and shorting
terminals together. Reconnect power, allowing 30 seconds to complete power up
sequence.
DIP switch settings| Configuration changes to DIP switches| ****
Remove cap from valve and disconnect power. Move DIP switch to desired position. Reconnect power, allowing 30 seconds to complete power up sequence.
For further assistance with troubleshooting, visit http://www.zurn.com/
ZTR6200 Series Parts Breakdown (Plastic Cap)
Parts Identification
- Cover screw
- Valve Cap/Sensor Assembly
- Solenoid
- Piston Cover Screws
- Solenoid Kit
- Flange O-rings
- Piston Kit
- Valve Housing
- Manual Override Button
- Filter
- Valve Assembly
- Vacuum Breaker
- Vacuum Breaker Tube
- Vacuum Breaker Tube Nut
- Spud Nut
- Spud Friction Washer
- Spud Sleeve
- Spud Escutcheon
- Setscrew for Control Stop Cover
- Vandal-Resistant Control Stop Cover
- Stop Cap Bonnet
- Stop Internals
- Piston Seal
- Stop Body
- Sweat Solder Adapter
- Supply Cover Tube
- Setscrew for Cast Wall Escutcheon
- Cast Wall Escutcheon
- Hex Wrench
- Top Valve Cap/Sensor Assembly
- Battery Housing
- Hardwired Top Valve Cap/Sensor Assembly
- Wire Supply Tube and Escutcheon
ZTR6200 Series Parts Breakdown (Metal Cap)
Parts Identification
- Ring Insert Assembly
- Valve Cap/Sensor Assembly
- Solenoid
- Piston Cover Screws
- Solenoid Kit
- Flange O-rings
- Piston Kit
- Valve Housing
- Manual Override Button
- Filter
- Valve Assembly
- Vacuum Breaker
- Vacuum Breaker Tube
- Vacuum Breaker Tube Nut
- Spud Nut
- Spud Friction Washer
- Spud Sleeve
- Spud Escutcheon
- Setscrew for Control Stop Cover
- Vandal-Resistant Control Stop Cover
- Stop Cap Bonnet
- Stop Internals
- Piston Seal
- Stop Body
- Sweat Solder Adapter
- Supply Cover Tube
- Setscrew for Cast Wall Escutcheon
- Cast Wall Escutcheon
- Hex Wrench
- Vandal Resistant Top Valve Cap/ Sensor Assembly
- . Battery Housing
- Vandal Resistant Hardwired Top Valve Cap/Sensor Assembly
- Wire Supply Tube and Escutcheon
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>