ZURN ZER Series AV Exposed Sensor Diaphragm Flush Valve Installation Guide
- May 15, 2024
- ZURN
Table of Contents
AquaSense AV™
ZER Series
Automatic Sensor-Operated,
Battery-Powered Flushometer
Installation, Operation, Maintenance and Parts Manual
ZER6000AV-CP / ZER6000AV-CPM
ZER6003AV-CP / ZER6003AV-CPM
Sensor-Operated, Battery-Powered Closet/Urinal Systems
ZER6000AV-CPM
ZER6000AV-WS1-CPM
ZER6001AV-CPM
ZER6001AV-WS1-CPM
ZER6003AV-CPM
ZER6003AV-WS1-CPM
WARNING: Cancer and Reproductive Harm – www.P65Warnings.ca.gov
LIMITED WARRANTY
All goods sold hereunder are warranted to be free from defects in material and factory workmanship for a period of three years from the date of purchase. Decorative finishes warranted for one year. We will replace at no costs goods that prove defective provided we are notified in writing of such defect and the goods are returned to us prepaid at Sanford, NC, with evidence that they have been properly maintained and used in accordance with instructions. We shall not be responsible for any labor charges or any loss, injury or damages whatsoever, including incidental or consequential damages. The sole and exclusive remedy shall be limited to the replacement of the defective goods. Before installation and use, the purchaser shall determine the suitability of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith. Where permitted by law, the implied warranty of merchantability is expressly excluded. If the products sold hereunder are “consumer products,” the implied warranty of merchantability is limited to a period of three years and shall be limited solely to the replacement of the defective goods. All weights stated in our catalogs and lists are approximate and are not guaranteed.
PRIOR TO INSTALLATION
Prior to installing the ZER Flushometer, install the items listed below:
- Closet or urinal fixture
- Drain line
- Water supply line
IMPORTANT:
- ALL PLUMBING IS TO BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES AND REGULATIONS.
- WATER SUPPLY LINES MUST BE SIZED TO PROVIDE AN ADEQUATE VOLUME OF WATER FOR EACH FIXTURE.
- FLUSH ALL WATER LINES PRIOR TO OPERATION (See Step 9).
- DIRT AND DEBRIS CAN CAUSE FLUSH VALVE TO RUN CONTINUOUSLY.
The ZER is designed to operate with 20 to 80 psi (138 to 552 kPa) of water
pressure. THE MINIMUM PRESSURE REQUIRED TO THE VALVE IS DETERMINED BY THE TYPE
OF FIXTURE SELECTED. Consult fixture manufacturer for pressure requirements.
Protect the chrome or special finish of this flushometer. DO NOT USE TOOTHED
TOOLS TO INSTALL OR SERVICE THE VALVE.
1.) Install stop valve assembly (A) using proper size supplyescutcheon and sweat solder adapter kit if applicable. Thread sealing compounds should be used on male NPT threads only.
2.) Prior to inserting the flush valve tailpiece (B) into stop valve, be certain that the O-ring seal (C) is located in O-ring seal groove at the end of the tailpiece and the locking nut (D) and locking snap ring (E) are located as shown. Care should be taken not to damage the O-ring when inserting the tailpiece into the stop valve. If lubrication is needed, wetting the O-ring with water will be sufficient.
3.) Insert the flush valve tailpiece (B) into the stop valve (A) and hand tighten the lock nut (D) to the stop valve. Plumb the entire unit.
4.) Determine the length of vacuum breaker tube (F) required to join the flush
valve and fixture spud. Cut the vacuum breaker tube, if required, to this
length. Assemble the vacuum breaker tube assembly and spud nut assembly to the
flush valve and fixture spud.
5.) Hand tighten spud nut and vacuum breaker tube nut to fixture and flush
valve. Adjust the valve assembly for plumb. Tighten fixture spud nut, vacuum
breaker tube nut and lock nut with a wrench. Do not turn water on until
batteries are inserted – see 6.
6.) ACTIVATION
Using supplied battery compartmentwrench,remove battery compartmentfrom the
E-Z Flush™ unit.
Load batteries into compartment tray (note position of batteries in tray), and reinstallbattery tray into the E-Z Flush unit.
Secure tray with battery compartment wrench. The last three turns of the
wrench will activate the E-Z Flush unit. The E-Z Flush System is now
operational.
Your E-Z Flush unit comes preset from the factory. If special circumstances
require adjustment of the activation distance, see Appendix A – Adjusting Your
E-Z Flush.
The E-Z Flush unit has a 10-minute start-up sequence in which the Object Lock
Sensor will flash the User-In-View yellow L.E.D. continuously as long as a
user is in view. After the start-up sequence is completed and when the Object
Lock Sensor has a user in view, the User-In-View yellow L.E.D. will flash only
3 times after a 5-second delay. This delay prevents needless flushes when
someone walks by. Sensor units should not be located across from each other or
in close proximity to highly reflective surfaces.
7.) VISUAL INDICATOR GUIDE
8.) ADJUSTING YOUR E-Z FLUSH
Before the supply water is turned on, be sure all stop valves to the flush valves are closed off tight. The stop valves can be opened and closed by using the adjusting screw located at the center of the stop valve cap (T) , behind the adjusting screw cover if already installed. Stop valve adjustments can only be made by using the adjusting screw. It is not necessary to remove the stop valve cap when making adjustments. If for any reason it becomes necessary to remove the stop valve cap, be certain the water is shut off at the main supply valve.
9.) When all flush valves are connected to the fixtures and water pressure is
available, it is recommended that the supply piping be flushed to remove dirt,
pipe chips, etc., from system.
Use the following procedure to flush out the supply piping:
A. Remove the main valve body cover .(O)
B. Remove the working parts from the flush valve (P) and (Q) (shown in 9b).
C. Replace the plastic cover (P) and main body cover (O) without reinstalling
the working parts.
D. Open the stop valve by using the stop adjusting screw and flush out all
debris from pipe and connections.
E. Shut stop, open cover, reinstall the working parts, replace both covers and
tighten.
This procedure should also be repeated when the system is drained for seasonal
use, as occurs in athletic fields, recreation parks, etc.
10.) The ZER flush valves are preset for fixture volume as marked on the valve cartons. The valve does not require regulation for variation in water pressure within its operating range. To set the flush valve for proper operation, gradually adjust the stop valve open, using the adjusting screw, while actuating the valve until the rate of water flow into the fixture is not excessive, yet is sufficient to adequately evacuate the waste. The final setting for urinals should be such that the fixture will not overflow when the valve is actuated in succession. The stop cap screw cover should be replaced after final adjustments have been made.
APPENDIX A
TO CHANGE ACTIVATION DISTANCE FOR THE OBJECT LOCK SENSOR
- Remove battery compartment tray as shown in Step 6.
- Remove cover and sensor adjustor tool as shown in Step 6.
- Replace battery compartment in E-Z Flush to activate unit.
- Press sensor range reset button (the yellow L.E.D. will flash continuously when it has an object in view for the 10-minute reset period).
- Stand at desired activation distance.
- Use sensor adjustor tool and turn Distance Adjustment Screw all the way down and then turn slowly up until yellow L.E.D. begins to flash.
- Ensure Object Lock Sensor is not detecting stall door or wall by closing door, stepping out of sensor path and making sure yellow L.E.D. is not flashing. If sensor locks onto door or wall, unit will not flush properly. Shorten activation distance.
- Remove battery compartment, replace sensor adjustor tool and cover. Replace battery compartment tray to reactivate E-Z Flush unit.
- After 10-minute start-up sequence, the yellow L.E.D. will flash only 3 times when a user is in view (after a 5-second delay).
WIRING DIAGRAM
TROUBLE SHOOTING GUIDE
PROBLEM | CAUSE | SOLUTION |
---|---|---|
Yellow L.E.D. light flashes 3 times when there are no users. | Front of Object |
Lock Sensor is covered or Object Lock Sensor is set too far out, registering
the opposite wall or door as a user.| Remove item covering sensor or adjust
Object Lock Sensor activation distance. (See Appendix B – Adjust- ing the E-Z
Flush.)
Yellow L.E.D. light flashes continu- ously when Object Lock Sensor is
activated by a user.| E-Z Flush unit is in 10-minute start-up mode (when first
activated), or Sensor Range Reset Button has been depressed.| Yellow L.E.D.
light will flash only 3 times, acknowledging a user is in view after the
10-minute start-up mode.
Red L.E.D. light flashes.| Batteries need replacing.| Replace batteries.
Not enough water to fixture or too much water to fixture.| Diaphragm damaged
or valve control stop improperly adjusted.| Replace diaphragm and/or adjust
valve control stop.
Valve will not operate.| Object Lock Sensor range set too close to E-Z Flush,
batteries are dead, or water supply is turned off.| Adjust Object Lock Sensor,
replace batteries, or turn water on. If the E-Z Flush does not begin to
function, call Customer Service at 1-800-997- 3876.
Valve does not shut off.| Dirt or debris preventing diaphragm from functioning
properly.| Remove dirt or debris, check by-pass hole in diaphragm.
Valve does not flush even after Object Lock Sensor has been adjusted.|
Batteries are dead.| Replace batteries. If the E-Z Flush does not begin to
function, call Customer Service at
1-800-997-3876.
AquaVantage® Exposed E-Z Flush Repair Kits
Part Identification
- Seal
- Collar Gasket
- Sensor Module
- Manual Overide Push Button
- Replacement Sensor Lens
- Chrome Plastic Cover
- Chrome Metal Cover
- Battery Drawer
- O-Ring
- Allen Wrench
- Handle Nut Wrench
- Valve Body Cover
- Plastic Cover
- Trip Mechanism
- Diaphragm Repair Kit
- Valve Body
- Vacuum Breaker Duckbill
- Vacuum Breaker Tube
- Vacuum Breaker Tube Nut
- Spud Nut
- Spud Friction Washer
- Spud Sleeve
- Spud Escutcheon
- Tailpiece
- Snap Ring
- Tailpiece O-Ring
- Locking Nut
- Setscrew for Cast Wall Flange
- Cast Wall Escutcheon
- Supply Cover Tube
- Sweat Solder Adapter
- Stop Body
- Piston Seal
- Piston
- Stop Spring
- Guide O-Ring
- Piston Guide
- Guide Holder
- Adjusting Screw
- Stop Cap
- Snap Cap Screw Cover
- Vandal – Resistant Control Stop Cover
- Setscrew for Control Stop Cover
Covers and Repair Kits | Product No. |
---|---|
Outside Cover – CP – Item 10 | P6000-LL-CP |
Inside Cover – Item 11 | P6000-L |
Low Consumption Closet Kit – 1.28 gal. flush | P6000-ECA-HET |
Low Consumption Closet Kit – 1.6 gal. flush | P6000-ECA-WS1 |
Water Saving Closet Kit – 3.5 gal. flush | P6000-ECA-WS |
Full Flow Closet Kit – 4.5 gal. flush | P6000-ECA-FF |
Ultra Low Flush Urinal Kit – 0.125 gal. flush | P6000-EUA-ULF |
Extra Water Saver Urinal Kit – 0.5 gal. flush | P6000-EUA-EWS |
Low Consumption Urinal Kit – 1.0 gal. flush | P6000-EUA-WS1 |
Water Saving Urinal Kit – 1.5 gal flush | P6000-EUA-WS |
Full Flush Urinal Kit – 3.0 gal. flush | P6000-EUA-FF |
Repair Parts – Inside Parts | Product No. |
--- | --- |
Urinal Relief Valve – Item 12 | P6000-EU13 |
Closet Relief Valve – Item 12 | P6000-EC13 |
Flush Connections and Spud Coupling Kits | Product No. |
--- | --- |
Flush Tube Assembly for Flush Valves Includes Items 15-19, Specify Diameter
and Length| P6000-A
Vacuum Breaker Repair Kit, Item 17| P6000-B
Spud Coupling Assembly Includes Items 20- 23 Specify Size.| P6000-H
Control Stop Repair Kit and Parts| Product No.
---|---
Control Stop Repair Kit for 1″ and 3/4″, Includes Items 33-39| P6000-D-SD
Seal Seat for 1″ and 3/4″, Includes Item 33| P6000-D42
VP Control Stop Repair Kit for 1″ and 3/4″, Includes Items 33-39| P6000-D-VP
Sweat Solder Connection with Cast Wall Flange, Includes Items 29-31|
P6000-YBYC
Adjustable Tailpieces| Product No.
---|---
Adjustable Tailpiece for Standard Flush Valve Includes Items 24-26| P6000-J1
Tailpiece Coupling Assembly Includes Items 25-27| P6000-K
Tailpiece Locking Ring Includes Item 25| P6000-C30
Tailpiece 0-Ring Includes Items 26| P6000-C31
Coupling Nut Includes Item 27| P6000-C32
Handle Assembly and Repair Kits| Product No.
---|---
Chrome Plastic Cover, Item 6| PERK6000-L-CPCR
Chrome Metal Cover, Item 7| PERK6000-L-CPMCR
Replacement Sensor Lens Item 5| PERK6000-SCR
Battery Drawer, Item 8| PERK6000-BD
Repair Kit Includes Items 1, 2, 4, and 9| PERK6000-RK
Repair Kit Includes Items 1, 2, Retainer and Cup Seal| PERK6000-MRK
Sensor Module| PERK6000-SR
Rev. H | Date: 11/11/22 | C.N. No. 144844 | Prod./Dwg. No. FV237
Patent zurn.com/patents
US 1.855.ONE.ZURN CANADA 1.877.892.5216
ZURN.COM
References