ZURN 375XL Pressure Principle Installation Guide

June 7, 2024
ZURN

Zurn logo

Model 375XL

Reduced Pressure Principle Assembly

Application

Ideal for use where Lead-Free* valves are required. Designed for installation on potable water lines to protect against both backsiphonage and backpressure of contaminated water into the potable water supply. Assembly shall provide protection where a potential health hazard exists.

Standards Compliance
  • ASSE® Listed 1013
  • IAPMO® Listed
  • CSA® Certified B64.4
  • AWWA compliant C511
  • Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California
  • UL® Classified (less shut-off valves only, 3/4″-2″)
  • C-UL® Classified (less shut-off valves only, 3/4″-2″)
  • Meets the requirements of NSF/ANSI 61*
  • (0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
Materials

Housing         Reinforced Nylon, FDA approved
Fasteners        Stainless Steel, 300 Series
Elastomers     Silicone (FDA Approved) Buna Nitrile (FDA Approved)
Internals         Delrin, Nylon
Springs           Stainless Steel, 300 series
Ball Valves      Low Lead Cast Bronze, ASTM B 584
Struts              Stainless Steel, 300 Series

Features

Sizes:           1/2″, 3/4″, 1″, 1-1/4″, 1-1/2″, 2″
Maximum working water pressure          175 PSI
Maximum working water temperature    180°F
Hydrostatic test pressure                         350 PSI
End connections Threaded FNPT         ANSI B1.20.1

ZURN 375XL Pressure Principle

Options

(Suffixes can be combined)

           – with full port QT ball valves (standard)
S         – with Model SXL lead-free bronze “Y” type strainer
FT      – with integral male 45° flare SAE test fitting
AG     – with air gap
SAG   – with Model SXL lead-free bronze “Y” strainer and air gap
B        – with black fusion epoxy coated ball valves & struts for theft protection

Accessories

Repair kits
Thermal expansion tank (Mdl. XT)
Soft seated check valve (Mdl. 40XL2)
Shock arrester (Model 1260XL)
QT-SET Quick Test Fitting Set
Blow out / Flush fitting (RK34-375BOF (1/2″ or 3/4″), RK1-375BOF or RK114-350-375BOF)

MODELS 375XLSE

OPTIONAL LEAD-FREE STRAINER-A OPTIONAL
LEAD-FREE STRAINER-B OPTIONAL LEAD-FREE
STRAINER-C

OPTIONAL LEAD-FREE STRAINER-D OPTIONAL
LEAD-FREE STRAINER-E OPTIONAL LEAD-FREE
STRAINER-F

Dimensions & Weights (do not include pkg.)

Dimensions & Weights

Rev. N
Date: 12/19
Document No. BF-375XL
Patent No. 7,784,483, & 7,905,250
Product No. Model 375XL
Page 1 of 2

Flow Characteristics                                 ♦ Rated Flow (established by approval agencies)

MODEL 375XL 1/2″ – 1″ (STANDARD & METRIC)

MODEL 375XL 1_2 _1 \(STANDARD & METRIC\)  FLOW RATES (GPM)MODEL 375XL 1-1/4″ – 2″ (STANDARD & METRIC)

MODEL 375XL 1-1-4-B
Typical Installation

Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.

Relief Valve Discharge Rates
(Worst case condition – If 1st check or relief valve is lodged wide open)

Relief Valve Discharge Rates

MODEL 375XLSAG (SHOWN)

INDOOR INSTALLATION OUTDOOR INSTALLATION

INDOOR INSTALLATION         OUTDOOR INSTALLATION

Specifications

The Reduced Pressure Principle Backflow Preventer shall be certified to NSF/ANSI 61, ASSE® Listed 1013, rated to 180°F, and supplied with full port ball valves. The main body shall be Nylon and the seat disc elastomers shall be silicone. If installed indoors, the installation shall be supplied with an air gap adapter. The Reduced Pressure Principle Backflow Preventer shall be a ZURN WILKINS Model 375XL.


Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada | Zurn Industries Limited
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216

**WWW.Zurn.com

Page 2 of 2**

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

ZURN User Manuals