ICM Controls ECA100-1 3 Phase Motor Protection Relay Instruction Manual

June 13, 2024
ICM CONTROLS

ECAIOO_II
MOTOR PROTECTION RELAY
INSTALLATION INSTRUCTIONS

ECA100-1 3 Phase Motor Protection Relay

Rated Voltage, Ue 208/220 440/480 VAC
Voltage Operation Limits, Ue 124 ⇒300 264 ⇒672 VAC
  1. ECAI00-II GENERAL DESCRIPTION
    The ECAI00-II electronic three-phase relays are specially designed for the protection of air conditioning and refrigeration compressors and ventilation motors from the causes of current, voltage and power failures, all with enhanced reliability and with connectivity.
    WARNING
    Only qualified electrical technicians with knowledge of overload relays and associated machinery should perform the installation, starting up, and maintenance of the system. Adhere to all local and national electric codes. Disconnect all electrical
    power at the source prior to any installation or maintenance work. Failure to comply could result in equipment damage, personal injury, OR even death.
    WARNING: This product may start automatically, the user must take cautions to avoid hazards to people.
    CAUTION: This product has been designed for industrial environment. Use of this product in residential enviroment may cause unwanted electromagnetic disturbances in which casethe user may be required to take adequate mitigation measures. CAUTION: An incorrectly applied or installed ECAIOO-II can result in damage to the components or reduction in product life. Wiring or application errors, or operating/storing in excessive ambient temperatures may result in malfunction of the ECAIOO-II.

  2. ECAI00-I1 OVERVIEW
    FRONT SIDE VIEW BACK SIDE VIEW
    1Indicator Lights (LED’s)
    – Normal (ON) – Continuous Green.
    Start Delay (TC) – Blinking Green.
    – Overload (OL) – Continuous Red.
    Phase Reversal (PR) – Blinking Red.
    – Unbalance (UB) – Continuous Red.
    Single Phasing (SP) – Blinking Red.
    – Overvoltage (OV) – Continuous Red.
    Undervoltage (UV) – Blinking Red.
    2. Current (FLA) Setting Knob.
    3. Start Delay (TC) Setting Knob.
    4. Back Groove for DIN Rail mounting.
    5. Attachable Mounting Ear for Flat Surface mounting.
    6. Supporting Brackets for DIM Rail mounting.
    7. Current Sensing Holes for motor wiring.
    8. Power Supply Voltage Input (LI L2 13).
    9. Contacts for Relay (95-96) and (97-98).
    Tipped { 95-96 closed | parma {i open 97-98 open 97-98 closed
    10. 10 Port. (for Serial Communication).
    11. AUTO / MANUAL Start Mode Slide-Switch.
    12. START Push Button.
    13. 10 PORT cover.

  3. ECAI00-I11 DIN RAIL AND FLAT SURFACE MOUNTING

CAUTION: ECAI00-II must be installed in an accessible position free from dust, dirt, dampness and vibrations. Allow enough space for air circulation around the enclosure and easy access to all operator controls. Indoors Use only. |

3.1 Instructions for Mechanical Installation
Place ECAIOO-II at an inclined with is back side placed toward the upper edge of the DIN Rail and push down ECAIOO-II relay, as shown in figure until it CLICKS on the rail. 3.2 Instructions for Mechanical Installation
a) Take off the two (2) attachable mountings ear located at back side of ECAIOO-II, insert and slip both attachable mounting ears into the ECAIOO-II back side grooves. b) Place ECAS00-II over a flat surface panel and mount it using (2) #8 x 1/2″ screws Recommendiation for Flat Surface Mounting:
Make two (2) holes (5/32″) on panel surface before installing.Refer Section 5 for dimensions.
NOTICE: When ECAIO0-II is set to MANUAL Start mode, the indicator lights (Red LED 1, Red LED 2, Red LED 3) will be lit up sequentially after the Start Delay (TC) is over. The condition remains until the user presses the START Push button to re-start.

ECAIOO-II DISMOUNTING INSTRUCTIONS

WARNING: Disconnect power supply (Circuit Breaker OFF) A and electrical wiring before dismounting ECAIOO-II.
Electrical shock will result in death or serious injury.
8.1 Instructions for Mechanical Dismounting (DIN RAIL)
a) Using a Flathead screwdriver, pull downward the mounting bracket that you can see at the rear and bottom side of the ECAIOO-II, as shown In figure. b) With screwdriver at position (2), pull out ECAIOO-II from DIN Rail as shown in figure: Recommendation for DIN Rail Dismounting:
Pull downward 2 mm with a soft movement when using screwdriver for dismounting. Strong movement could break the supporting bracket
8.2. Instructions for Mechanical Dismounting (FLAT SURFACE)
a) Unscrew both screws fixed on Flat Surface through attachable mounting ears and then pull out the ECAIOO-II relay from flat surface as shown in figure. HOW TO ORDER THE ECAIO0-II

ECALOO-II
Motor protector COLD-HOT CURVES (Class 10)
(*) [nom = Current value on ECAIOO-II adjusted previously by the user Inom term is referred to FLA (Full Load Amperage) adjustable on the product
Hot Curve Cold Curve
After the first stall/trip of the motor due to a fault  condition, the protective relay will disconnectsooner, according to the hot curve.

MODBUS REGISTER MAPPING

GROUP| REGISTER ADDRESS| NAME| READ/WRITE| MIN| MAX| SIZE| UNITS| DESCRIPTION/FORMAT| FACTORY ETTING
---|---|---|---|---|---|---|---|---|---
PRODUCT ID| 0| PRODUCT ID
_| R| 16| 16| | | FO| 16
1| MODEL| R| 2| 36| 1| | F1|
2| VERSION| R| 0| 255| 1| | F2|
3| MODBUS ADDRESS| R/W| 1| 127| 1| | F3| 1
HISTORY| 10| LAST_FAILURE_POINTER| R/W| 0| 20| 1| | F6|
11| TOTAL_NUMBER_OF_FAULTS| RAN| 0| 20| 1| | F6|
ADJUSTMENTS| 12| CONTROL_ON_OFF| RNV| 0| 5| 1| | F10|
TIMERS| 14| (TC) START UP DELAY| R| 0| 202| 1| | F30|
OUTPUT| 15| ACUMULATED_HEAT| R| 0| 65530| 1| | F31|
16
17| FREQUENCY| R| 95| 244| 1| | F32|
18| PHASE| R| 0| 100| 1| %| F33|
19| VL3L1| R| 0| 255| 1| | F20|
20| VL 1L2| R| 0| 255| 1| | F20|
21| VL2L3| R| 0| 255| 1| | F20|
22| IC| R| 0| 255| 1| | F34|
23| IA| R| 0| 255| 1| | F34|
24| IB| R| 0| 255| 1| | F34|
KNOB VALUE| 25| (FLA) CURRENT SETTING| R| 18| 73| 1| | F43|
26| (TC) START UP DELAY SETTING| R| 2| 150| 1| | F29|
27| START MODE| R| 0| 1| 1| | F19| 0
28| MOTOR THERMAL CLASS| R| 3| 10| 1| | F6|
FAULT HISTORY| 0029-0049| FAULT 01/20 – 20/20| R| 0| 202| 1| | F30|

9.1 MODBUS DATA FORMAT

CODE TYPE DESCRIPTION
FO 8 bits PRODUCT ID
16 ECAI00- I I
F1 8 bits PRODUCT MODEL
bits 2…0 VOLTAGE MODEL (1 A 4): 2 = 208V II 4 = 480V
bits 3,4,5,6,7 Reserved
bits 5…3 CURRENT MODEL (1 a 4):
2 = 12A@ECA100-11
3 = 32A©ECA100-11
4 = 80A@ECA100-11
F2 8 bits SOFTWARE VERSION
bits 4 0 Software Version – Minor Number(0 a 31)
bits 7…5 Software Version – Major Number (0 a 7)
F3 16 bits MODEL
byte 0 Address (1 a 127)
byte 1 null. not used
F6 16 bits Unsigned char
byte 0 Value
byte 1 null. not used
F10 16 bits ADJUSTMENT – CONTROL ON/OFF
0 ON
1 OFF – FAILURE MODE
2 OFF – TRIP DELAY BECAUSE OF VOLTAGE FAILURES
3 OFF – MODBUS
4 OFF – MANUAL MODE
5 OFF – 3RD FAILURE

ECAI00-I] CONNECTION DIAGRAM

WARNING: (Risk of Electric Shock). Disconnect power
A supply before installing ECAIO0-I1. Electric Shock will result; in death or serious injury.
CAUTION: Check that the rated voltage and current of the  selected ECAI00-II model corresponds to the line voltage and motor current. ,
4.1 Terminal designation

4.2 Basic Diagram Installation
4.2.1 ECAIOO-II 208/220 VAC Models

4.2.2 ECAIOO-II 440/480 VAC Models
Requires auxiliary control voltage from 24 to 250 VAC.

Recommendations for Wiring:

  • Avoid overtightening M2.5 screw terminals during wiring of connections. Torque max. 4.5 Ib-in (5.18 kgf-cm)
  • Wire Strip Length 6-7 mm.
  • Screw Terminal wire size: D AWG 10 (4 mm?) B AWG 18.
  • Current Sensing Holes (conduits) wiring size: AWG 4(| | mm).
  • Connect L| L2 L3 terminal for Voltage input in parallel connection before line starter circuit through Contactor (as shown in Basic Diagram Installation).
  • Feed the the three phases going to the motor through the three current sensing holes. Using less than three wires may cause undesired current unbalance

ECAIOO-I1 GENERAL DIMENSIONS

ECAI00-11 ADJUSTMENT

CAUTION: By means of an Ammeter, make sure that the Operational Current (I) is less than FLA (Full Load Amperes) indicated at the motor nameplate. Failure to comply may result in damage to the motor. _
ATTENTION: Any accidental or Intentional change of setting knob positions after overload asjustment will cause varlations In the ECA100-II’s protective performance from previous setup. In this case, repeat procedure for ECAIO0-II adjustment indicated In Section 6.1
6.1 Procedure for Overload Adjustment
ATTENTION: You should follow this procedure with the motor running at full load conditions, according to the rated values indicated on Motor Name Plate.
a) Turn OFF the circuit breaker. NOTE: Make sure that wiring is according to connection diagram (see item 4.2).
b) Slide the AUTO/MANUAL start mode slide – switch to MANUAL position.

¢) Turn ON the circuit breaker. (The motor remains OFF as the contactor is open through deactivation of the ECANO-II) d) Turn right che Current setting knob (FLA) up to the maximum value. e) Press the START push button and hold it pressed (motor starts running and reaches steady-state operation) while you execute steps .
f) and (g). f} Slowly turn left the Current secting knob (FLA) undil the green LED turns ON. At this point, the adjusted level is the actual Motor Operational Current. g) Slowly tum right the current setting knob (FLA) up to desired protection level: h) Use AUTO/MANUAL start mode slide-switch to select the desired motor start mode.
NOTICE: Incase the AUTOMMANUAL start mode side – switchis set on MANUAL and the ECAIOG-II relay wips dus to any fault decoction, you shall press START push button to re-activate the Contactor or Line Starter Circuit.
Although the AUTO/MANUAL start made slide – switch is set on AUTO, pressing START push bumon is required @ three (3) current fadures have appeared mn less than 30 minutes and qualilied technicians have detected and solved causes of failures. I)Using a fiat screwdriver, turn the TC setting knob unsil you set the start delay datired (TC & che ore between Vokage fauk recovery and restart the system according to appication needs),

ECAI00-II OPERATION

ECAIO0-8 constantly supervises motor current and line volcage.
‘When any harmful condidon occurs, the ouput ts deactivated until the faulc disappears and che mocor has completely cooled. Specific timing such | as Start Up Delay (TC) is incorporased for automatic restart mode, to prevent nuisance tripping due to rapid power fluctuations. In the event of three current failures in less than thirty (30) minutes, che output is deactivated until manual restart is done, Checking causes of three successive failures is recommended before restarting because it can be an indication of mechanical problems such as the condensing unit not being able to dissipate heat adequatedy or that there is a problem in the wiring operation, of a damage to the contractor
ECANOO-M provides two {2} sorting knobs co select che maximum allowed current (FLA) and the start up delay (TC) once the voltage fault.
andlor overload disappears. One START push-button and one selectable AUTO/MANUAL Sart Mode Slide-Switch are included a5 well a6 4 Comaunication Port with ModBus RTU prococol It also provides indicator lights (LEDs) to indicate faults and load status, as shown in following table:
LED Diagnostics and Fault Conditions

| Continuous Light| Blinking Light
---|---|---
Red Led| Normal (ON)| Start Delay (TC)
Red Led I| Overload failure (OL)| Phase Reversal failure (PR)
Red Led 2|  Voltage Unbalance or Current Unbalance failure (UB)| Voltage Single Phasing or Current Single Phasing failure (SP)
Red Led 3| Overvoltage failure (OV)| Undervoltage failure (UV)

ECAIOO-II also indicates any combination of fault conditions.
9.1 MODBUS DATA FROMT

CODE TYPE DESCRIPTION
F19 1 bits START MODE
0 MANUAL
AUTO
F20 8 bas Unsigned char – To calculate Voltage – ECA100-11
Value VOLTAGE =f Worn’ ( Value /300 + 0,6) pa
f_Vnom = Factor Rated Voltage
f_Vnom= 214 © Voltage Model = 208V
f_Vnom= 460 © Voltage Model = 480V
F29 16 bits Unsigned char – To calculate Start Up Delay – ECA100-11
Value START UP = ((2 • Value ) + 1) (s)
F30 8 bits FAULT HISTORY REGISTER – ECA100-11
0 No Fault
bit 0 OV – Over Voltage
bit 1 UV – Under Voltage
bit 2 CUB – Current Unbalance
bit 3 VUB – Voltage Unbalance
bit 4 VSP – Voltage Single Phasing
bit 5 CSP – Current Unbalance
bit 6 PR – Phase Reversal
bit 7 OL – Overload
F31 32 bits Unsigned char – To calculate Acurnuleted Heat – ECA100-11
ACUMULATED HEAT = ((HEAT_H’256 + HEAT_L)/ 616) (%)
byte 0 HEAT_L
byte 1 null. not used
byte 2 HEAT_H
byte 3 null. not used
F32 8 bits Unsigned char – To calculate AC Power Frequency – ECA100-11
Value FREQUENCY = 15625 / ( Value + 128 ) (Hz)
F33 8 bas Unsigned char – To calculate Phase – ECA1004 1
Value PHASE = Value ‘ 3,6 (degree)
F34 8 bits Unsigned char – To calculate Current – ECA100-11
Value CURRENT = Value • K1 ‘ Value(I_MAX) I ( K2 • 250 )
I_MAX Is the value of the modbus address referenced in note F43
K1 = 40 K2 = 73 © Current Model = 1,0 – 4.0 A
K1 = 125 K2 = 73 © Current Model = 3,5 -12.5 A
K1 = 320 K2 = 73 © Current Model = 10,0 – 32.0 A
K1 = 800 K2 = 73 © Current Model = 25,0 – 80.0 A
F43 8 bits Unsigned char -To calculate (FLA) CURRENT SETTING – ECA100-11
Value (I_MAX) (FLA) Current Setting = Value • K1 /1(2
K1 = 4 K2 = 73 © Current Model = 1.0 – 4.0 A
K1 = 12.5 K2 = 73 © Current Model = 3.5 – 12.5 A
K1 = 32 K2 = 73 © Current Model = 10.0 – 32.0 A
K1 = 80 K2 = 73 © Current Model = 25.0 – 80.0 A

ECAIOO-II TECHNICAL SPECIFICATIONS

A) Power Supply Circuit

a.1 Rated Voltage, Ue 208/220 440/480 VAC
a.2 Voltage Operation Limits, Ue 124—>300 264-472 VAC
a.3 Average Comsumption, In 38 mA
a.4 Frequency Operation Limits, FN 42—q0Hz 50/60 Hz
a.5 Rated Duty Uninterrupted Duty

B) Application Data, Environmental Conditions, Operation Limits and Installing

b 1| Designed according to
European Standards| IEC61010-1, IEC60255-6
IEC60947-1| LVD & EMC
---|---|---|---
b.2| UL Listing| Aux. Device NKCR Certified for USA
Aux. Device NKCR7 Certified for Canada| E527483
b.3| CE Marking| CE, Low Voltage Devices| IEC60947-1
b.4| Ambient Air Temperature (Operation)| -5 °C to 55 °C (23 °F to 131 °F)|
b.5| Ambient Air Temperature (Storage)| -10 °C to + 70 °C (14 °F to 158 °F)|
b.6| Maximun Relative Humidity| 85% R.H.|
b.7| Vibrations| Class 1, Amplitude <0.035mm or 1G
10Hz < f < 150Hz| IEC
60255-21-1
b.8| Degree of Protection| IP20, Protected against objects >12.5mm| IEC 60529
b.9| Pollution Degree| Degree 3| !EC 60255-5
b.10| Overvoltage Category| Category III| IEC 60255-5
b.11| Rated Insulation Voltage| 500V| According to UL
b.12| Impulse Voltage Test| 5 KV| !EC 60255-5
b.13| Dielectric Voltage-Withstand Test| 2.5 KV 50/60 Hz@1 min| UL 508
b.14| Flammability Rating of Enclosure| VO| UL-94
b.15| Enclosure Material| Polymers: PC, ABS, NYLON|
b.16| Mounting Position| Any Position|
b.17| Mounting Features| Symmetrical DIN Rail| DirrEC  43880
Flat surface mountinq,screw 3116″x1/2″| NEMA Style
b.18| Terminals Screw Type| Flat M3|
Tightening Screw Torque| 5.1 Kgf-cm / 4.4 lb-in|
Terminals Wiring| 210 AWG (4mm2)51 8 AWG|
b.19| Current Sensing Holes for Motor Wiring| ms 11 mm, AWG 4|
b.20| Dimensions| 92 x 91 x 96 (L x W x H)| mm
b.21| Weight| 398 (0.87)| glib

C) Control Characteristics

c.1| Auxiliary Relay Contact Rating| 8300 Pilot Duty| UL 508
Section 139.1
---|---|---|---
c.2| Electrical Life Expectancy| 100.000 Operations|
c.3| Mechanical Life Expectancy| 10.000.000 Operations|
c.4| Utilization Category| AC-15, Capacity for loads> 72 VA| 1E060947-5-1

D) Range Setting, Measuring

(According to Voltage Model) 208 480 VAC
d.1 Voltage Measurement Range, Um 145-285 300-625
(According to Current Model) 3.5-12.5 10 32 25-80 A
Current measuremente range, In 0.7 – 125 1 2.0 – 320 I 4.0 – 800
d.2 Frequency Measurement (Parameter available only through 10 Port)
Accuracy ± 2% Hz

E) Algorithms and Protection Functions
F) Communications and Other Special Functions
(*) 10 Link RS485 is required for 10 Port communication. It is available by separately.
G) Immunity and Emissions, Electromagnetic Compatibility
(EMC) tor Heavy Industrial Environment

7313 William Barry Blvd North
Syracuse, NY 13212, United States.
Note: Technical data are valid at the time of printing. We reserve the right to subsequent alterations

Documents / Resources

| ICM Controls ECA100-1 3 Phase Motor Protection Relay [pdf] Instruction Manual
ECA100-1 3 Phase Motor Protection Relay, ECA100-1, 3 Phase Motor Protection Relay, Motor Protection Relay, Protection Relay
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ICM CONTROLS User Manuals

Related Manuals