INSTALLATION MANUAL
Z-KEY
Z-KEY-P
Z-KEY-E
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol **indicates conditions or
actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbol **indicates conditions or
actions that might damage the instrument or the connected equipment. The
warranty shall become null and void in the event of improper use or tampering
with the module or devices supplied by the manufacturer as necessary for its
correct operation, and if the instructions contained in this manual are not
followed.
**| WARNING: The full content of this manual must be read before any
operation. The module must only be used by
qualified electricians. Specific documentation is available via QR-CODE shown
on page 1.
---|---
| The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate
measures during any operation.
| Electrical and electronic waste disposal (applicable in the European Union
and other countries with recycling).
The symbol on the product or its packaging shows the product must be
surrendered to a collection centre authorized to recycle electrical and
electronic waste.
| [ www.seneca.it/products/z-key-p](http://www.seneca.it/products/z-key-p)
---|---
| [ www.seneca-it/products/z-key-e](http://www.seneca-it/products/z-key-e)
| [ www.seneca.it/products/z-key**](http://www.seneca.it/products/z-key)
CONTACT INFORMATION
Technical support| support@seneca.it| Product
information| sales@seneca.it
---|---|---|---
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised.
The content of this document corresponds to the described products and
technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MI00580-4-EN
INSTALLATION MANUAL
MODULE LAYOUT
Dimensions: 17.5 x 102.5 x 111 mm, Weight: 100 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | ON | The device is powered correctly |
COM
Z-KEY-P/ Z-KEY-E version| Flashing| Profinet or Ethernet/IP communication
active
Off| No Profinet or Ethernet/IP communication
TX1| Flashing| Data transmission on port #1 RS485
RX1| Flashing| Data receipt on port #1 RS485
TX2| Flashing| Data transmission on port #2 RS485/RS232
RX2| Flashing| Data reception on port #2 RS485/RS232
ETH ACT Green| Flashing| Packet transmission on Ethernet port
ETH LNK Yellow| ON| Ethernet connection present
TECHNICAL SPECIFICATIONS
CERTIFICATIONS|
---|---
INSULATION|
ENVIRONMENTAL CONDITIONS| Temperature: -25 °C – + 65 °C; Humidity:;30%– 90%
non condensing.
Altitude: Up to 2000 m above sea level; Storage temperature: -30 °C – + 85 °C
Protection rating: IP20 (Not evaluated by UL)
ASSEMBLY| IEC EN60715, 35mm DIN rail in vertical position.
POWER SUPPLY| Voltage: 11 – 40 Vdc; 19 – 28 Vac 50 – 60 Hz; Absorption: Max.
1,5W
CONNECTIONS| 3-way removable screw terminals, pitch 5 mm
Rear connector IDC10 for DIN bar 46277
RJ45 front connector
COMMUNICATION PORTS| RS232 or RS485 switchable on terminal 10 – 11 – 12
(serial port 2)
Maximum Baud rate 115 k, maximum cable length RS232 < 3m
RS485 IDC10 rear connector: Maximum Baud rate 115 k. (serial port 1)
RJ45 front Ethernet connector: 100 Mbit/s, maximum distance 100 m
CONFIGURATION| Configuration and FW update via webserver; Via DIP – SWITCH
Via EASY SETUP 2 configuration software
ATTENTION
The device may only be powered by a power supply unit with a limited energy
electric circuit max.
40Vdc / 28Vac output in accordance with CAN/CSA-C22.2 No. 61010-1-12 / UL Std.
No. 61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2 according to
CSA 223/UL 1310.
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
SETTING THE DIP-SWITCHES
WARNING
The DIP-switch settings are read only at boot time. At each change, perform a
restart.
SW2 DIP-SWITCH: Through DIP-SWITCH-SW1 it is possible to set the IP
configuration of the device:
DESCRIPTION | DIP 1 | DIP 2 | DIP 3 | DIP 4 |
---|
To obtain the configuration from the Flash memory, both SW1
DIP switch selectors must be set to OFF| | | RESERVED| RESERVED
To reset the device to factory settings both SW1 DIP switches
must be set to ON| | | RESERVED| RESERVED
To force the device’s IP address to the standard value of
SENECA Ethernet products: 192.168.90.101| | | RESERVED| RESERVED
Reserved| | | RESERVED| RESERVED
ATTENTION
DIP3 and DIP4, on models where they are present, must remain OFF.
If set otherwise, the instrument will not operate correctly.
RS232/RS485 SETTING: RS232 or RS485 configuration on terminals 10-11-12
(serial port 2)
SW2
1| ON| | RS232 ACTIVATION
0| OFF| | RS485 ACTIVATION
PROFINET AND WEBSERVER MODE
The device is normally in Profinet mode; in Profinet mode the device can be
configured only through the Easy Setup2 software.
In order to access the internal webserver it is necessary to put the device in
Webserver mode using the Easy Setup2 or Seneca Device Discovery software. it
is also possible to change the operating mode by pressing the side button PS1
following the procedure given in the user manual.
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
N.B.: For the Z-KEY-P version it is first necessary to activate webserver mode
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail.
For optimal operation and long life, adequate ventilation must be provided.
Avoid positioning ducting or other objects that obstruct the ventilation
slots.
Avoid mounting modules over heat-generating equipment. Installation in the
bottom part of the electrical panel is recommended.
ATTENTION
These are open-type devices and intended for installation in an end enclosure
/ panel offering mechanical protection and protection against spread of fire.
ELECTRICAL CONNECTIONS
CAUTION
To meet the electromagnetic immunity requirements:
– use shielded signal cables;
– connect the shield to a preferential instrumentation earth system;
– separate shielded cables from other cables used for power installations
(transformers, inverters, motors, etc…).
POWER SUPPLY | SERIAL PORT 2: RS485 SW2 = OFF | SERIAL PORT 2: RS232 SW2 = ON |
---|---|---|
ATTENTION
Use only copper or copper-clad aluminium or AL-CU or CU-AL conductors
IDC10 CONNECTOR
The illustration shows the meanings of the various IDC10 connector pins if signals are to be sent via them directly.
MI00580-4-EN
INSTALLATION MANUAL SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY;
Tel. +39.049.8705359
– Fax +39.049.8706287