MAJESTIC B36LA Built in Wood Burning Corner Fireplace Instruction Manual
- June 13, 2024
- Majestic
Table of Contents
- MAJESTIC B36LA Built in Wood Burning Corner Fireplace
- Listing And Code Approvals
- IMPORTANT SAFETY INFORMATION
- OPERATION GUIDELINES
- FIREPLACE FEATURES
- FIREPLACE COMPONENTS
- “E” CHIMNEY COMPONENTS
- FIREPLACE LOCATION
- FLOOR PROTECTION
- CLEARANCES
- FIREPLACE INSTALLATION
- MOBILE HOME INSTALLATION
- CHIMNEY INSTALLATION
- CHIMNEY OFFSET INSTALLATION
- CHIMNEY OFFSET AND CAP INSTALLATION
- OUTSIDE COMBUSTION AIR PRECAUTIONS & RECOMMENDATIONS
- COMBUSTION AIR ASSEMBLY
- GAS APPLIANCE INSTALLATION
- FIREPLACE OPERATION
- MAINTENANCE & SAFETY
- PARTS DIAGRAM AND LIST
- LIMITED WARRANTY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MAJESTIC B36LA Built in Wood Burning Corner Fireplace
Installation, Operation and Maintenance Manual For Residential Installation
36” Built-in Wood Burning Corner Fireplace with Optional Outside Air and
Glass Doors
WARNING: This fireplace has not been tested with an unvented gas log set. To reduce risk of fire or injury, do not install an unvented gas log set into fireplace.
Congratulations!
You have chosen the finest wood burning fireplace available. Your fireplace
has been designed for years of heating and viewing enjoyment. Please take time
to read this entire manual before installing or operating your fireplace.
Listing And Code Approvals
The instructions contained in this manual provide the information necessary to install this fireplace in accordance with Underwriter’s Laboratories requirements and in compliance with the National Fire Protection Association Standard No. 211. Some codes may require the fireplace and chimney be electrically grounded. Before beginning the installation, you should check with local building officials to obtain required permits and assure compliance with local regulations and coded. If you encounter problems with code requirements, contact your dealer for assistance. These Fireplace models are listed by Underwriters Laboratories, Inc. to U.L. 127-standard for factory- built fireplaces. The design of this fireplace and these instructions complied with applicable safety standard for a factory built fireplace in effect at the time the fireplace was manufactured. You should be aware, however, that failure to install, operate, and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths, injuries, and property damages. It is very important that the persons installing and/or supervising the installation of this fireplace have appropriate skills in using the tools and techniques required; and reading and comprehension skills sufficient to read and follow these instructions. These instructions contain warnings, cautions, and notes to emphasize important safety information. To assure that safe and satisfactory service is received from this fireplace, please read the following special notices and all the contents of this manual.
IMPORTANT SAFETY INFORMATION
Installer
Please leave these instructions with the owner.
Owner
Please retain these instructions for future reference.
- Read these instructions entirely before beginning any part of the installation. Save these instructions for any future repairs.
- Use these instructions as a guide during the installation of the fireplace.
- Be sure these instructions become the property of and are reviewed by all future users of this fireplace to encourage proper operation and maintenance.
- All the parts used with this fireplace system must be installed in accordance with these installation instructions. Failure to do so may be hazardous and will void the warranty.
- This fireplace and accessories should not be altered in any way that is not specifically recommended in this manual.
- Refer to your local building code for local requirements pertaining to installation of factory-built fireplaces. These fireplaces are intended for installation and use according to standard NFPA NO.211 of the National Fire Protection Association.
- This fireplace must not be installed with a masonry flue.
- This fireplace and chimney should not be used for venting a wood or coal burning heater or fireplace insert. WARNING: Do not install a separate solid fuel insert or gas fireplace insert into this fireplace and chimney system without written authorization.
- WARNING: Do not pack required air spaces with combustible material or insulation not specifically recommended for use in such areas.
Intended Product Usage
This fireplace is intended for supplemental heating only and is not intended
for use as a primary heating system. The fireplace is designed to sit directly
on a combustible floor. The fireplace must be installed with clearances to
combustible building materials specified in this manual. Only parts
manufactured by MHSC and labeled for use with the fire-place should be used in
the installation of this fireplace except for special roof flashings that may be
fabricated locally. The use of improper parts in the installation can be
hazardous and void the warranty offered by MHSC. This fireplace is designed to
burn wood. This fireplace is not designed to burn coal, unplumbed liquid fuels,
unplumbed gaseous fuels or household refuse. Any attempt to burn these fuels
in the fireplace can be hazardous. This fireplace is designed for installation
in mobile homes if it is installed in accordance with Figure 32 in this
manual, which includes using and OAC6 combustion air assembly, WB36LR glass
door, SVT firestop thimble, and use either the LLK or RLK louver kit.
- WARNING: Do not install in a sleeping room of a mobile home.
- CAUTION: If installed in a mobile home, the structural integrity of the floor, wall and ceiling/roof must be maintained.
- WARNING: This fireplace and chimney must not be used for venting a solid fuel heater or fireplace insert unless written authorization is given by MHSC. Failure to heed this warning may cause fire hazard and will void the warranty.
Improper Installation
Improper installation or use of this fireplace will void the warranty and can
cause:
- Damage to the fireplace from overheating.
- Hazardous temperatures to develop on combustible materials adjacent to the fireplace or chimney.
- The emission of smoke, sparks or hazardous gases into the dwelling.
- Leakage of rain water into the dwelling.
OPERATION GUIDELINES
As wood is burned in the fireplace, room air enters the air slot on the lower
front edge and circulates around the firebox.
The air circulation around the firebox serves to cool the fireplace and must not
be blocked in any manner. Blocking of the inlet slot or outlet louver will
cause the firebox to reach hazardous temperatures. When an OAC4 combustion air
assembly and a combustion air duct are attached to the connecting point on the
left of the fireplace, combustion air may enter the firebox through a dampened
opening behind the side panel. This feature is designed for your benefit to
reduce the room air used for combustion and to prevent excessive loss of heat
from the room. When the fireplace is in use, this damper should be open. When
the fireplace is not in use, the damper should be closed to prevent cold air
from entering the firebox. The combustion air damper is open when the lever,
located on the side of the firebox is up and closed when the lever is down.
Outside air for combustion is optional unless required by federal, state or
local building codes. See the section of this manual providing the
instructions for installation of the combustion air assembly. Glass doors
should be installed to receive the maximum benefit from your fireplace. For
large fires, the maximum heating benefit from the fireplace will be obtained with
the doors open due to the high amount of radiant heat being emitted out of the
front opening of the fireplace. With a small fire, or before retiring in the
evenings, it is best to operate the fireplace with the doors closed to prevent
excessive room air from being drawn up the chimney. When the doors are open,
the mesh screens should be closed to help keep burning embers from popping out
of the firebox. The unique design of the fireplace allows the routing of the
combustion air duct downward, horizontally or upward to obtain the outside
combustion air. This permits maximum flexibility in planning your installation.
Refer to Page 22, Figure 24 for typical installation methods. Be sure to
review the precautions and recommendations in the section of this manual
pertaining to outside combustion air assembly. The fireplace is also equipped
with a flue damper, which must be open when the fireplace is in use. The flue
damper control lever is located inside the fireplace. The counterweighted
damper is operated by simply pushing up to open or pulling down to close the
damper. When the fireplace is not in use, the damper should be closed to
prevent cold air form entering the chimney as well as preventing warm air in
the room from escaping up the chimney.
NOTE: It is normal for a small amount of smoke to be released from the upper portion of the fireplace the first few times you use your new fireplace. This results from an oil residue on the metal. Open a door or window to allow the smoke to escape.
WARNING: Fireplaces equipped with glass doors should be operated only with the doors fully open or doors fully closed. If doors are left partly open, gas and flame may be drawn out of the fireplace opening, creating risks of both fire and smoke. All fireplace chimneys are in direct contact with cold air on the exterior of the structure. Consequently, when the fireplace is not in use, cold air can fall down the chimney of the fireplace to cool off the fire- place chase. Therefore, the fireplace chase must be insulated to minimize the risk of cold air infiltration to the home. Even if the fireplace chase is adequately insulated, this cannot completely ensure that cold air infiltration into the structure will be eliminated. Cold air infiltration is a possibility with any fire-place or device that freely communicates with the air on the outside of the structure. Today’s homes are more energy-efficient and, therefore, better insulated and tightly constructed. Unfortunately, when air is removed from the house, as by a bathroom fan, or consumed by a furnace, additional air is needed to replace the air consumed. Unless the additional air is supplied, this can cause a negative pressure in the home. When this happens, the house will draw in outside air from the cracks in the windows, down the fireplace flue or other locations of air leakage in the home. Because cold air infiltration may be unavoidable in some structures, MHSC is not responsible for heat loss or air infiltration through or around the fireplace.
FIREPLACE FEATURES
NOTE: Combustible materials should not be installed below top spacer. Noncombustible materials such as brick or tile may be used to trim face of the fireplace but should not cover any portion of the louvered panel or cool air inlet. Combustibles must not overlap the black painted face of the fireplace.
FIREPLACE COMPONENTS
Model Number | Description |
---|---|
B36LA, B36RA | Left or right end open fireplace. Includes wire firescreen, |
sealing flue damper and outside com- bustion air capability. When installed, outside combustion air can be connected to left side. Refer
to installation instructions for details.
S48| 4-foot chimney section (8-inch diameter flue)
S36| 3-foot chimney section (8-inch diameter flue)
S18| 11/2-foot chimney section (8-inch diameter flue)
S12| 1-foot chimney section (8-inch diameter flue)
SE30| 30° elbows (package contains two 8-inch diameter elbows). One pair is
required for each offset.
Maximum – two pairs (4 elbows) per chimney.
SCS| Chimney support (required when chimney height exceeds 30 feet)
SC| Round chimney cap for contemporary installations. Includes storm collar.
SCL| Round telescoping chimney cap
SQL8| Square telescoping chimney cap
612| 0-6/12 pitch flashing for contemporary installation. One required with SC
round chimney cap on
0-6/12 pitch roof
1212| 6/12 – 12/12 pitch flashing for contemporary installation. One required with SC round chimney
cap on 6/12 – 12/12 pitch roof
SF| 141/2” firestop spacer – One required at each ceiling or floor level
SF-30| Firestop spacer – for 30° chimney incline through ceiling or floor
FP-4-U| 4-inch insulated combustion air duct – 8 foot lengths
403| 4-inch duct connector (for splicing FP-4 ducts). Includes two clamps
OAC4| 4-inch outside combustion assembly
WB36LR| Optional polished brass glass door kit
H1658| Hearth extension board for front opening (16” x 58”)
H1627| Hearth extension board for end opening (16” x 27”)
S8| Telescoping assembly for use with telescoping chimney caps
Figure 2 – Residential Installation – Using “E” Series Triple Wall Thermosyphoning Chimney Components
NOTE: Combustible materials should not be installed below top spacer. Noncombustible materials such as brick or tile may be used to trim the face of the fireplace but should not cover any portion of the louvered panel or cool air inlet. Combustibles must not overlap the black-painted face of the fireplace.
“E” CHIMNEY COMPONENTS
- When installing “E” series triple wall chimney system on the B36LA and B36LR, do not mix chimney system components other than those listed below.
- Maintain 2” airspace clearance to combustibles.
- Use same offset and rise chart for chimney when installing elbows.
Model Number | Description |
---|---|
E48 | 4-foot chimney section (8-inch diameter flue) |
E36 | 3-foot chimney section (8-inch diameter flue) |
E18 | 11/2-foot chimney section (8-inch diameter flue) |
E12 | 1-foot chimney section (8-inch diameter flue) |
EE30 | 30° elbows (package contains two 8-inch diameter elbows). One pair is |
required for each offset.
Maximum – two pairs (4 elbows) per chimney.
ECS| Chimney support (required when chimney height exceeds 30 feet)
LFCC-1| Round chimney cap for contemporary installations. Includes storm
collar.
LFCCL-1| Round termination cap for chase installation (includes inlet air
telescope)
612| 0-6/12 pitch flashing for contemporary installation. One required with SC
round chimney cap on
0-6/12 pitch roof
1212| 6/12 – 12/12 pitch flashing for contemporary installation. One required with SC round chimney
cap on 6/12 – 12/12 pitch roof
LF-FS-2| 17” firestop spacer – One required at each ceiling or floor level below
20 foot chimney height
LF-FS-30| Firestop spacer – for 30° chimney incline through ceiling or floor
LFSQT| Square termination for chase installation. Model T8 telescope assembly
requried but not included
T8| Telescoping assembly for use with telescoping chimney caps
LF-FF| Flat flashing for chase installation (36” x 72”)
FIREPLACE LOCATION
CAUTION: Do not install fireplace over carpeting.
This fireplace does not require any special foundation. If the fireplace is to
be trimmed with large stone or brick facing, an adequate foundation is
required to support these materials. Use Figures 5 and 6 as a guide for
selecting a location and determining the space required for the fireplace. The
location for the fireplace should be adjacent to the load bearing wall and away
from objects that will create drafts that could disturb the normal flow of air
into the fire. Such objects are frequently opened doors and central heat and
air outlets and returns. Figure 4 illustrates various types of locations and
installation and Figure 1 gives additional information concerning installation
heights, construction details, and methods on installation. A location that
requires cutting the least number of joists and rafters for the chimney
installation will simplify and reduce installation cost. The opening required
for passage of the chimney through the roof, ceilings and floors must be 17
inches square as indicated by Figures 6, 7 and 8. The 17 inch square opening
provides for the installation of the model LF-FS-2 firestop spacer in a
residential installation. Since the pitch of the roof influences the opening
size required at the roof level, table 1 should be used as a guide for sizing
the roof opening. Proper selection of a chimney outlet location is also
important. Objects such as overhanging or nearby trees, adjacent building or
embarkments or unusual roof designs can all create air turbulence and
interfere with chimney performance and cause the fireplace to spill smoke into
the room. A factory-built fireplace, properly installed in a single story wing
of a multi-story building as shown in Figure 9, may be affected by
environmental factors that will cause poor chimney draft and occasional
spillage of smoke from the fireplace opening. Although this occurs
infrequently, location of the fireplace in the preferred location as indicated
by Figure 9 is recommended. If the chimney is to pass through living areas or
spaces used for storage, be sure that it will be possible to enclose the
chimney to prevent contact with and possible damage to the chimney. Elbows may
be used to avoid obstructions such as electrical wires, water, or sewer pipes,
attic fans, heating ducts, etc. Refer to the section of this manual concerning
chimney offsets for proper elbow installation and use. If the failure is to be
installed in an outside wall, the surrounding walls should be enclosed and
insulated. Failure to properly enclose the fireplace will cause a heat loss and
diminish the fireplace efficiency due to transfer of heat through the fireplace
to the outside.
FLOOR PROTECTION
All fireplaces installed over a combustible floor must incorporate a noncombustible earth extension. It is required to protect the floor in front of the fireplace from both radiant heat and sparks. Hearth extension dimensions should be determined by using the chart below. Use hearth extensions as il- lustrated in Figures 5, 10 and 11 or use an acceptable thickness of a durable noncombustible material with an equal or greater insulating value than K – .43 BTU in/ft2-HR-F°, or a thermal resistance that equals or exceeds R = 1.16. These materials should be covered with a decorative noncombustible veneer.
NOTE: Any noncombustible material with a K factor value that is less than .43, or whose R value is more than 1.16 or 1/2” thick material is acceptable.
HOW TO DETERMINE HEARTH EXTENSION REQUIREMENTS
The following information is provided to determine required thickness for any
non-combustible material when either the K or R values are known. They are
expressed as the following: K = BTU-in/ft2-HR-F° or R = HR-F°/BTU. These
materials should be covered by a decorative noncombustible material such as
tile, brick, stone or slate. To determine the thickness needed for a material
other than those listed in the chart, use the following formulas to calculate
that which will be an acceptable equivalent. The ability of insulating
material to retard the transfer of heat may be expressed as either Thermal
Con-ductance (C), Thermal Conductivity (K) or Thermal Resistance (R). The
mathematical relationship of these values and the formulas for converting one
value to another is as follows:
- C = K divided by the material thickness
- (Example: C = .43 divided by 1/2 (.50) C = .86)
- K = C multiplied by the material thickness
- (Example: K = .86 multiplied by 1/2 (.50) K = .43)
- R = The material thickness divided by K
- (Example: R = 1/2 (.50) divided by .43 R = 1.16)
With either type hearth extension minor shifting of the supporting floor or expansion and contraction may eventually cause a crack to develop between the hearth extension and the face of the fireplace. To help prevent the crack from developing, the hearth extension materials must be firmly fastened in place. Wall ties should be screwed to the face of the fireplace and imbedded n the mortar joints of brick, stone or other noncombustible materials. The metal safety strip packed with the fireplace must be placed beneath the fire-place and extended under the hearth extension or into a mortar joint of the hearth extension. In the event a crack does eventually develop, the metal safety strip will serve as a barrier to prevent sparks or embers from falling from the fireplace onto combustible flooring materials. Refer to Figure 5 for an alternate hearth extension using brick only.
WARNING: The space between the hearth extension and fireplace must be sealed with a noncombustible material. When installing the hearth extension, be careful not to block the heat circulating air inlets (louvers, slots, etc.) Figure 5
Wall Protection
A model WS wall shield or an equivalent must be installed when the closed end
of the fireplace is closer than 24” from a wall perpendicular to the face of
the fireplace. Figures 10 and 11. The WS wall shield should be attached
securely to the wall by driving nails or screws through it into the wall
studs. The wall shield should be covered by a decorative noncombustible
material such as brick, tile, slate, etc. The WS wall shield is constructed of
1” of Micore CV230 insulation board, manufactured by U.S. Gypsum Corporation,
covered by a sheet of galvanized metal. An alternate insulating material with
a K factor of .43 or lower can be used. Refer to the preceding section for
instructions for selecting an alternate insulating material.
WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness and which are known to the State of California to cause cancer, birth defects or other reproductive harm. Also, operation, installation and servicing of this product could expose you to airborne particles of glass wool fibers known to the State of California to cause cancer through inhalation.
CLEARANCES
FIREPLACE INSTALLATION
Location Selection
Unpack and check the fireplace and chimney for damage. If any items have been
damaged, report this to your dealer. Before beginning the installation, be
sure you have the proper parts in sufficient quantity. Refer to the Parts
Diagram and List section of this manual for proper identification of parts. Do
not substitute parts. Use only parts listed for use with Model B36LA and B36RA
fireplaces.
Fireplace Installation
- Refer to Figure 1 for examples of typical fireplace framing.
- Be sure the location of the fireplace will provide the required safety clearances as specified by this instruction manual.
- Set the fireplace in the desired location and be sure it is securely supported and leveled. Install metal safety strip for hearth extension as shown by Figures 10, 11 and 12. Check the face of the fireplace with a carpenter’s level to make sure the fireplace is plumb. If it is not plumb, plumb it by placing shims under the edges of the fireplace.
- Block in the fireplace to prevent any shifting of the firebox. Secure the fireplace with nails or screws through the flanges located on each side of the fireplace. Install chimney and other fireplace components as needed.
NOTE: Some local codes may require electrically grounding the fireplace and chimney.
Chimney Installation
In order to assure safe and satisfactory performance of the fireplace, it is
very important to properly install the chimney. This is an important part of
the installation and the sections of this manual pertaining to chimney
installation should be reviewed very thoroughly. For your safety, some of the
important things to remember in regard to chimneys are listed below:
- Use only parts and accessories labeled for use with this fireplace.
- Use only undamaged parts and accessories.
MOBILE HOME INSTALLATION
WARNING: Operating doors in this position is incorrect.
CHIMNEY INSTALLATION
- Enclose the chimney where it passes through the living spaces to prevent contact with and possible dam-age to the chimney.
- Install firestop spacers at each ceiling level.
- Install the proper chimney cap or chimney housing on the chimney to prevent the entry of rain and debris into the chimney and to assure the proper venting of smoke.
- Do not use more than four elbows in the chimney.
NOTE: To select the proper chimney height, refer to Figure 1. The flue outlet must be a minimum of three feet above the highest point where the chimney penetrates the roof and a minimum of two feet above all portions of the building within ten feet. If the chimney is to include elbows to offset the chimney, refer to the Chimney Offset and Cap Installation section of this manual. There must be at least two inches air space between all sections of the chimney and combustible materials between floors.
- Lay out, cut and frame openings through all ceilings and the roof at the point where the chimney will pass through. Unless the chimney is to be offset, the point where the center line of the chimney will pass through the ceiling and roof can be determined with a plumb line as shown by Figure 15. The fireplace should be located in the planned installation position. After the center line is established and a nail is driven to mark the point, the opening can be cut if you are satisfied with the chimney location relative to ceiling and roof joists and/or any other obstructions. The roof opening center line should be marked by driving a nail through the roof from underneath that will penetrate the roof and can be located from the rooftop. If the chimney is to penetrate a pitched roof, the hole in the roof must be rectangular instead of square and should be sized according to Table1.
- Install the firestop spacer as required from beneath the ceiling unless the space above is attic space. In an attic, the firestop spacer should be installed at the floor level of the attic. You must have joists or headers on all four sides of the spacer and use a minimum of four 8-penney nails to secure the spacer.
- To install the “S” series chimney sections, insert the male end of the flue, the smallest diameter pipe, into the flue outlet of the fireplace and press down until the snap locks engage. Continue the process, adding the chimney sections on top of each other until the chimney is at least six inches above the roof opening on all sided. As the chimney sections are installed, check each joint to make sure it is properly locked to the previous section. If additional strength of the outer pipe joints is desired, you may use two or three sheet metal screws placed through the area where the outer pipes overlap one another. To install these screws, drill a 1/8-inch diameter hole through the chimney sections, taking care not to penetrate the inner flue pipe. WARNING: Be very careful when drilling the holes into the outer pipe. The drill must not penetrate the inner stainless steel pipe.
Table 1
Minimum Required Roof Opening Minimum Framed Opening
Roof Pitch
| “S” Series
Double Wall
| “E” Series
Triple Wall Chimney
0/12| 14¹⁄₂” x 14¹⁄₂”| 17” x 17”
1/12| 14¹⁄₂” x 14⁵⁄₈”| 17” x 17¹⁄₈”
2/12| 14¹⁄₂” x 14³⁄₄”| 17” x 17¹⁄₄”
3/12| 14¹⁄₂” x 15”| 17” x 17¹⁄₂”
4/12| 14¹⁄₂” x 15¹⁄₄”| 17” x 17³⁄₄”
5/12| 14¹⁄₂” x 15³⁄₄”| 17” x 18¹⁄₄”
6/12| 14¹⁄₂” z 16¹⁄₄”| 17” x 18³⁄₄”
7/12| 14¹⁄₂” x 16⁷⁄₈”| 17” x 19³⁄₈”
8/12| 14¹⁄₂”x 17¹⁄₂”| 17” x 20”
9/12| 14¹⁄₂” x 18¹⁄₈”| 17” x 20⁵⁄₈”
10/12| 14¹⁄₂” x 18⁷⁄₈”| 17” x 21³⁄₈”
11/12| 14¹⁄₂” x 19³⁄₄”| 17” x 22¹⁄₄”
12/12| 14¹⁄₂” x 20¹⁄₂”| 17” x 23”
CHIMNEY OFFSET INSTALLATION
NOTE: If you intend to have a total fireplace installation of more that 30 feet you must use a chimney support at or below 30 feet to support the weight of additional chimney pipe. If it is impossible to nail the chimney support to the load bearing framing of the building at the 30 foot level, the chimney support may be installed at a lower level if the height of the chimney above the support does not exceed 30 feet. The effective height of the chimney support is 16³⁄₄”. Chimney supports must be installed at 30 foot intervals. To install the chimney support, place the crimped end of the flue and outlet air duct portions into the last section of chimney pipe. Push down until the outside or inlet air duct of the chimney support overlaps and snap locks the chimney support into the chimney section. Nail the support straps tightly to a building frame member or ceiling joist as shown by Figure 18. You must use at least two 8-penney nails per strap.
Elbow Installation
NOTE: If triple wall elbow is to be placed directly to the top of the fireplace, it will be necessary to bend a tab located on each of the four (4) inlet air collar brackets. Bend these tabs over only when using a triple wall elbow to start a chimney run. The tabs may be easily bent with your fingers or pliers. Figure 19 The following are important points that should be observed when installing elbows on the fireplace:
- The support straps of all elbows not installed directly on top of the fireplace should be nailed securely to the surrounding structure. This allows the support strap to carry the weight of the chimney above the elbow and prevents this weight from breaking the elbow or chimney sections apart. Figure 18
- Elbows should not be used in any combination that inclines the chimney more than 30 degrees from vertical.
- The limitations on the quantity of elbows per chimney are as follows: If the total height of the fireplace and chimney is—16’0” or more — two elbows may be used in the chimney. 21’ – 0” or more — four elbows may be used in the chimney.
- The inclined portions of chimneys that pass through living spaces likely to be used for storage should be enclosed to avoid contact with and possible damage to the chimney. The minimum air space of two inches between the chimney and enclosing materials must be maintained. Figures 20 and 21 illustrate elbow installations.
- The length of the inclined portion of the chimney between elbows must not exceed 6 feet when unsupported or 20 feet if the chimney is supported at six-foot intervals with support such as metal support straps.
- When enclosing the elbows and inclined portions of the chimney, enclosing materials must be installed vertically to maintain the required two-inch minimum air space clearance to the chimney at the extremities of the offset. It is recommended that enclosing material not follow the inclined portions of the chimney.
Offset Installation Sequence
- Determine the location and amount of offset required, then select the combinations of chimney sections and el-bows required from the offset chart. Refer to.
- Install the first LE30 elbow by placing the extended flue into the mating part of the fireplace or chimney section. Push down until the outside or inlet air duct of the elbow overlaps and the snaps lock the elbow into the fireplace or chimney section.
- Nail the support straps to the framing member with a minimum of two 8-penny nails per strap.
- Install the sections of pipe between elbows until the proper number of chimney sections have been installed.
- Install the second elbow to return the run of the chimney to vertical.
- Nail the support straps of the second elbow to a building frame member.
- Continue installing the vertical portion of the chimney.
NOTE: If the inclined portion of the chimney passes through a floor or ceiling, an SF30 firestop spacer should be installed to provide the firestop and support required. Be sure proper spacing in maintained between the chimney and combustibles.
CHIMNEY OFFSET AND CAP INSTALLATION
Table 2
Select desired offset and read across Table to obtain rise, quan- tity of chimney sections and elbows
30° Elbow
Offset
|
Rise
| 1ft.
Sections
| 1¹⁄₂ ft.
Sections
| 3 ft.
Sections
| 4 ft.
Sections
| Elbows
Req’d
9³⁄₈”| 25⁵⁄₁₆”| 1| —| —| —| 1 pr.
12³⁄₈”| 30¹⁄₂”| —| 1| —| —| 1 pr.
17³⁄₄”| 39¹³⁄₁₆”| 1| 1| —| —| 1 pr.
20³⁄₄”| 45”| —| 2| —| —| 1 pr.
23¹⁄₈”| 49¹⁄₈”| 2| 1| —| —| 1 pr.
26³⁄₄”| 55³⁄₈”| 1| —| 1| —| 1 pr.
32³⁄₄”| 65¹³⁄₁₆”| 1| —| —| 1| 1 pr.
35³⁄₄”| 71”| —| 1| —| 1| 1 pr.
38³⁄₄”| 76³⁄₁₆”| —| —| 2| —| 1 pr.
41¹⁄₈”| 80⁵⁄₁₆”| 1| 1| —| 1| 1pr.
44³⁄₄”| 86⁹⁄₁₆”| —| —| 1| 1| 1 pr.
47¹⁄₈”| 90¹¹⁄₁₆”| —| 1| 2| —| 1 pr.
50³⁄₄”| 97”| —| —| —| 2| 1 pr.
56¹⁄₈”| 106”| —| —| 3| —| 1 pr.
59¹⁄₈”| 111¹⁄₂”| —| 1| —| 2| 1 pr.
68¹⁄₈”| 127”| —| —| 1| 2| 1 pr.
*RISE is the number of inches in vertical height reached by the combinations shown.
**OFFSET is the number of inches which the centerline of the chimney is moved horizontally by the combinations shown.
Model SC Chimney Cap
SPECIAL NOTE: The proper height as previously explained is important to assure proper draft and safety. The chimney cap extends the flue outlet four inches above the top of the last section of chimney. This should be kept in mind when determining the proper height for the chimney. The chimney should not be extended more than 90 inches above the supporting roof structure without additional support. In the case of an “A” frame type construction or other steep pitch roofs that require more than 90 inches of the chimney above the roof, support should be attached to the chimney at the 90 inch level that is strong enough to support a wind load of 3-1/8 pounds for each inch the chimney extends above 90 inches. The flue outlet must be a minimum of three feet above the point where in penetrates the roof.
CAUTION: Be careful to avoid electrical shock hazard when contacting wires to the metal chimney components.
- Extend the regular chimney sections until the top of the chimney is 4 inches below the total flue height desired. Do not snap the last section of the inlet air duct or the largest diameter pipe in place until Step 3 is completed.
- Remove the shingles from around the chimney so that the flashing may be installed, with the upper part of the flash-ing under the shingles.
- Set the flashing on the roof and scribe a line around the flashing, then cut the top off the flashing by cutting 1/4 inch below the scribed line. This should increase the diameter of the flashing outlet sufficiently to allow the flashing to be placed over the chimney. Figure 23
- Snap the last section of inlet air duct in place and slide the flashing over the chimney. Adjust the chimney to ensure that the proper minimum clearances are maintained.
- Nail the flashing securely in place with eight nails.
- Seal the crack between the top of the flashing and the chimney with mastic. Leave some excess mastic at this area to be used in step eight. NOTE: Use pliers and wear gloves when performing step seven to minimize the danger of cutting your hands on the edge of the storm collar.
- Place the storm collar around the chimney and put the collar together like a belt in belt loops. Slide the end of collar under the two loops on the other end with the loops facing up. Overlap the ends of the collar until it is tight against the chimney. Bend the free end of the collar back over the loops to hold the storm collar securely together. The excess end of the storm collar may be trimmed off.
- Slide the storm collar down snugly against the flashing until the excess mastic left in step six is forced up into the crack between the storm collar and the chimney. This should make the joint between the flashing and the chimney watertight.
- Install the chimney cap by placing the cap into matching parts of the last chimney section. Push down until the brackets on the bottom of the chimney cap sit on the chimney pipe. Then punch or drill 1/8 inch diameter holes in the inlet air duct (chimney pipe) where specified on the brackets and fasten it down with the No. 8 screws provided. Do not penetrate the inner stainless steel pipe while installing the screws.
- Check all the parts of the fireplace, chimney and chimney termination cap to assure that no parts have been damaged or bent during installation and that all parts have been installed properly.
NOTE: The metal used for the chimney cap has a rust-protective coating but the cut edges of the parts are not protected. To prevent rusting and rust staining of nearby structures, exposed parts of the chimney and chimney cap should be detergent washed and painted with a galvanized primer paint.
OUTSIDE COMBUSTION AIR PRECAUTIONS & RECOMMENDATIONS
NOTE: The use of outside air for combustion is optional unless required by building codes. It is only necessary to supply outside combustion air to one side of the fireplace. Use the Model OAC4 combustion air kit.
Outside Combustion Air Recommendations
- Extremely long runs and numerous turns in the duct leading from the fireplace to the combustion air assembly should be avoided. These conditions will increase the resistance to the free flow of air through the duct. Refer to Figure 24 for methods of installing the outside air for combustion assemblies.
- The combustion air assembly should be located at an exterior location, which is not likely to be accidentally blocked in any manner. The assembly should be located above the snow line to prevent blockage by snow accumulation.
- The combustion air inlet assembly should never be mounted in a garage or storage area where combustible fumes such as gasoline might be drawn into the fireplace.
- Combustion air can be drawn form the crawl space under a house when an adequate supply of air is provided by open ventilation.
- Do not take combustion air from attic space or garage space.
COMBUSTION AIR ASSEMBLY
Model OAC4 Combustion Air Assembly
- Remove the cover cap from the 4” outlet opening location on the left or right outside surface of the fireplace. DO NOT REMOVE THE COVER IF THE OUTSIDE AIR WILL NOT BE CONNECTED.
- Fasten the 4” starting collar over the hole on the left or right side of the fireplace with the four (4) sheet metal screws provided. Figure 24
- Cut a 6” diameter opening for model OAC4 in the outside wall covering where the model OAC4 outside grille is to be located. Figure 26
- Select and cut a piece of duct of sufficient length to attach to the fireplace and protrude at least 3” beyond the face of the wall to which the OAC4 inlet air box assembly will be attached. The duct may be cut with a standard pocket knife. Use FP-4-U duct for maximum efficiency and safety. Do not use a combustible duct. Always use UL listed Class 0 or 1 duct material.
- If the duct is the insulated type, push the insulation back from one end of the duct approximately 2”. Figure 27
- Slip the exposed end of the duct over the flange tube of the fireplace.
- Place the duct clamp around the exposed end of the aluminum duct.
- Slip the band through the housing, then pull the band tight around the duct.
- Snap the band locking screw down and tighten it with a screwdriver or nut driver. Figure 27
- Nail or screw the combustion air assembly to the surface of the wall.
NOTE: If the wall covering is brick or stone, use appropriate masonry fasteners. Mount the combustion air assembly with “TOP” up to prevent rain from entering the assembly. Be sure the 6” diameter opening around the air duct is sealed with insulating material to prevent cold air from entering through the wall. If it is necessary to splice the duct, a model 403 duct connector should be installed as described in Figure 26.
Combustion Air Assy. Model OAC4 Installation of the Model 403 Duct Connector
- Push the insulation back approximately 2” from the end of each duct.
- Slip each duct over the duct connector until an equal length of the connector extends into each duct.
- Place a duct clamp over the end of each duct and tighten it down snugly.
- Push the insulation back into place and over the duct clamp.
GAS APPLIANCE INSTALLATION
WARNING: Improper installation or operation of a gas appliance in this fireplace can allow unburned gas to leak out which will cause a fire or explosion hazard, or the release of poisonous carbon monox-ide into the dwelling which can cause serious injury or death to its inhabitants. To reduce these risks to a minimum, the following important notices and instructions should be read and followed carefully.
IMPORTANT NOTICES:
-
The provision for a gas line is intended for connection to a decorative gas appliance which and complies with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSIZ21.60. If a decorative gas appliance is installed, it must be installed in accordance with the National Fuel Gas Code, ANSIZ223.1.
CAUTION: “When a decorative gas appliance is installed, the fireplace damper must be fixed in a manner which will maintain the minimum permanent vent opening at all times.”
WARNING: This fireplace has not been tested with an unvented gas log set. To reduce risk of fire or injury, do not install an unvented gas log set into fireplace. The installer of the fireplace and gas appliance must describe the operation of the fireplace and ap-pliance to the people who will be operating them and leave all instruction manuals with the operator of the appliance. -
An approved gas shut off valve must be located outside the fireplace in an area accessible to the users of the fireplace.
-
All gas piping and fitting must be either steel or malleable iron.
-
Some code authorities prohibit or place restrictions on the use of gas appliances in fireplaces. Check with local code authorities before proceeding with the installation.
-
The gas appliance and all connecting gas piping should only be installed by a licensed gas appliance installer. Refer to Page 14, Figure 11 for the gas line opening dimensions on the fireplace.
The following instructions only apply to passing the gas line through the fireplace wall. Follow the in-structions provided by the appliance for the gas line, testing and adjusting it.
- Remove the side brick form the fireplace and locate the dimple “B” referred to by Figure 29.
- Tap out a round hole in the brick liner with a hammer by tapping lightly on the recessed area.
- Remove the two screws that hold the cover plate on the jacket wrap and discard the cover plate.
- Use a screwdriver or similar tool to push the loose insulation out of the tube between the firebox and the outer jacket of the fireplace.
- Install the gas pipe through the tube between the firebox and jacket.
- Attach the gas appliance to the gas pipe according to the instructions provided with the gas appliances.
- Pack the insulation removed in Step 4 around the pipe to prevent air flowing through the tube either into or out of the firebox.
- Be sure the gas is turned off at the appliance, then turn the gas on at the cut-off valve and test the gas line connections for leaks with soapy water solution or a liquid leak detector. DO NOT USE A MATCH OR OTHER FLAME SOURCE TO CHECK FOR GAS LEAKS. If a gas leak is detected, turn the gas off immediately and fix the leak.
- Proceed with installation and adjustment of the gas appliance as directed by the instructions provided with the gas appliance. If a gas leak is detected, turn the gas off immediately and fix the leak.
TRIM INSTALLATION
The face of your fireplace may be left exposed or trimmed with any
noncombustible material such as brick, stone or marble. Figure 30. If a
noncombustible trim is installed, be sure it is fastened snugly to the face of
the fireplace. A crack between the material and the face of the fireplace could
pose a fire hazard and impair the proper operation of the fireplace. Blocking
the fireplace with framing and attaching the base to the supporting floor will
further reduce the possibility of such a crack developing.
CAUTION: Do not allow any trim materials to extend closer than 3/8” to the vertical edges of the firebox opening if you plan to equip the fireplace with glass doors. Wall ties should be fastened to the face of the replaced with sheet metal screws and placed in the mortar joints of masonry trim. Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the fireplace face. Seal the face of the fireplace to the surrounding wall with noncombustible caulk or trim materials to prevent cold air leakage around the fireplace.
CAUTION: No trim should block or restrict in any way the flow of air into the air inlets in the face of the fireplace. Figures 30 and 31 Be sure to provide the required floor protection as described in a preceding section of this manual. Page 13, Figure 10 Combustible mantels and trim must be installed in accordance with the National Fire Protection Association – ANSI NFPA 211 Standard – Section 7-2.3.3.
Glass Door Installation
This fireplace has been tested and listed for use with Model MGD36B or MGD36PB
glass doors. For installation of the Model MGD36B or MGD36PB glass doors,
refer to the instructions provided with the doors.
Installation of Noncombustible Facing Materials to the Front Face of the Fireplace
NOTE: On B36LA or B36RA Models, noncombustible facing materials may be installed to the top of the fireplace opening. This facing material must be secured and sealed to the face of the fireplace. Failure to properly secure and seal noncombustible facing material to the fireplace can cause a possible fire hazard and will void the warranty.
FIREPLACE OPERATION
WARNING: If a decorative gas appliance is used in the fireplace the fireplace damper must be fixed in an open position. (See additional operation information in the section titled “Operation Guide-lines”.)
Which Woods Are Best?
Each wood species offers something different in aroma or heat value, and you
should consider your needs and desires before building your fire. Softwoods,
like pine, spruce, and fir are easy to ignite because they are resinous.
However, a fire built entirely of softwoods burns out quickly and requires
frequent replenishment. While a softwood fire is not too desirable for a long
evening, it’s fine in the morning when you want quick warmth, or late in the
evening when you want a fire that will burn out before you go to bed.On
occasion when a longer fire is desired, it’s best to combine softwoods with
heavier hardwoods such as ash, beech, birch, maple, oak and hickory. These
hardwood species burn less rapidly, with shorter flames, and produce steady,
glowing coals. For the most pleasing aroma, you’ll want to burn the wood of
fruit trees such as apple and cherry, or nut trees such as beech, hickory and
pecan. Such wood is generally more expensive, but a little combined with other
wood, goes a long way. Start your fire with a mixture of softwood and hardwood,
then add some fruit or nut wood for a nostalgic aroma. Since most woods will
not burn well when freshly cut, the wood you purchase should be reasonably
dry. The sizes you buy are dictated by the size of your fireplace. Purchase
logs that will fit when laid across your grate, and ask that the larger,
heavier logs be split. Kindling should be short, easily split lengths of
softwood, lumber yard or mill scraps, or twigs and branches gathered from your
yard.
How To Build A Better Fire
The first three fires should be of moderate size to allow the fireplace to
adjust and the bricks to cure before being subjected to larger fires. First,
make sure your room is well-ventilated, your damper open and the flue is
unobstructed. Then make sure your wood is dry and seasoned. Unseasoned wood
burns poorly and coupled with poor ventilation or an obstructed chimney, leads
to smoking problems.If your fireplace is equipped with an outside combustion
air assembly, open the combustion air inlet by pushing upward on the lever
located above the firebrick on the left side of the firebox.
NEVER USE GASOLINE, GASOLINE-TYPE LANTERN FUEL, KEROSENE, CHARCOAL LIGHTER
FLUID, OR SIMILAR LIQUIDS TO START OR “FRESHEN UP” A FIRE IN THIS FIRE-PLACE.
KEEP ALL SUCH LIQUIDS AWAY FROM THE FIREPLACE WHILE IT IS IN USE. USE OF THIS
FUEL CAN CAUSE A SERIOUS EXPLOSION.
Prepare your fire by placing two logs on the iron grate or fire basket, and
laying the tinder between them. Tinder may be dry scrap paper, twigs, or bark.
On top place a small handful of twigs or split softwood kindling. Place more
dry logs over this base. Keep logs close together, as narrow air spaces
between them promote better drafts, and heat reflected between adjacent
surfaces aids in raising and maintaining combustion temperatures. You’ll need
a minimum of three logs, preferably four, to make a good fire. Add kindling and
new logs as needed to rekindle a dying fire. New logs should be added at the
rear grate after raking the coals toward the front. DO NOT OVERFIRE THE
FIREPLACE. Overfire conditions may be created by large amounts of kindling,
building scraps, or other improper fuels. Ashes, important because they form a
bed of glowing coals, should only be left to accumulate within an inch or two
of the bottom of the grate. Excess ashes can be used to check a flaming fire; or
to “bank” your fire, cover the logs with ashes. A “banked” fire will hold
glowing coals for 8-10 hours, thereby saving a fire for later use.
Wood vs. Fossil Fuels
Compared to fossil fuels, a full cord of dry hickory weighs about two tons and
is approximately equal in heating value to a ton of hard coal. On a pound
basis, heavy hardwoods have about half the heating value of coal. The
tabulation shows the relative densities and heat values of a variety of dry
woods. Varieties at the top of the list (Dogwood) burn longer and those near
the bottom (White Pine) ignite and burn quicker. A combination of both light
and heavy wood is desired.
Species| Density| Heat Value| Species| Density|
Heat Value
---|---|---|---|---|---
Dogwood| .70-.79| 100-107| Ash| .57-.61| 81-82
Hickory| .70-.74| 100| Southern Pine| .51-.60| 73-81
Oak| .60-.73| 86-99| Elm| .50-.59| 71-80
Black Locust| .69-.70| 95-98| Cherry| .50-.52| 70
Beech| .64-.66| 89-91| Douglas Fir| .45-.51| 64-69
Hard Maple| .58-.65| 83-88| Spruce| .41-.44| 59
Birch| .55-.64| 79-86| Redwood| .33-.40| 47-54
Apple| .58-.62| 83-84| White Pine| .35-.37| 50
A Few Words Of Caution
Beware of burning certain materials in your fireplace. Among these are
plastics, poison ivy twigs and stems, and chemically treated woods such as
discarded poles and railroad ties. These not only create air pollution, but
can induce extreme irritation for some individuals. Use hemlock, spruce,
juniper and other resinous woods with caution. They contain moisture pockets
which, upon heating, “pop” with considerable vigor. Always use a fire screen.
And always “bank” a fire, or at least push all unburned fuel to the rear of the
grate before leaving a fire unattended. Do not use this fireplace as an
incinerator. Because the termination of the chimney above the roof is exposed
to wind and cold and the pressure changes these and other environmental
conditions may cause, a sufficient chimney draft may be hard to establish at
times. At other times the draft may be sufficiently disrupted to cause smoke to
spill from the fireplace opening. If problems with the chimney draft occur,
help start the chimney draft before you build a fire by holding a piece of
burning paper near the flue opening at the top of the firebox to preheat the
chimney. If smoke spills from the fireplace opening after the fire is burning,
open a window on the upwind side of the house that is far enough away from the
fireplace that the wind will not blow across the fireplace opening, push the
burning wood as near the back of the fireplace as possible, and if the fireplace
is equipped with glass doors, close them. DO NOT LEAVE CHILDREN OR PHYSICALLY
OR MENTALLY HANDICAPPED, OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE.
MAINTENANCE & SAFETY
Fuel Storage
Wood can be dried sufficiently for burning within a few weeks if protected from
rain in a low-humidity area. It is far better to cut wood and allow it to dry
for a year. In all cases, the wood should be stacked so that both ends of the
sticks are exposed to the air and protected from rain. The drier the wood, the
more usable heat produced by the fire and less likely rapid accumulation of
soot and creosote within the chimney is to occur. See the section of this
manual concerning chimney maintenance for information concerning the hazards
of soot a creosote accumulation. Small quantities of wood required for fire
tending must be kept at least 30 inches from the fireplace.
Disposal Of Ashes
Ashes should be placed in a metal container with a tight fitting lid. The
closed container of ashes should be placed on a noncombustible floor or on the
ground well away from all combustible materials pending final disposal. If the
ashes are disposed of by burial in soil or otherwise locally dispersed, they
should be retained in the closed container until all cinder has thoroughly
cooled. Ashes should never be placed in a container with combustible
materials.
Chimney Maintenance
Creosote, Formation and Need for Removal: When wood is burned slowly, it
produces tar and other organic vapors, which combine with expelled moisture to
form creosote. The creosote vapors condense in the relatively cool chimney flue
of a slow-burning fire. As a result, creosote residue accumulates on the flue
lining. When ignited, this creosote makes an extremely hot fire. The chimney
should be inspected at least twice a year during the heating season to
determine if a creosote buildup has occurred. If creosote has accumulated it
should be removed to reduce the risk of a chimney fire. The chimney cap can be
removed for inspection, maintenance and cleaning by removing three screws from
the support legs and lifting upward. When the fireplace is first in use, inspect
the chimney frequently and clean the chimney any time an accumulation is
observed on the flue walls. The frequency of these inspections can be increased
or reduced appropriately after a pattern of accumulation has been established.
Please note, how-ever, that changes in the outside environmental conditions
such as temperature and humidity or changes in the operation of the fireplace
can lead to rapid buildup of soot and/or creosote. To clean the chimney,
obtain the services of a qualified and reputable chimney sweep, or remove the
accumulation with brushes on wooden or fiberglass poles. Do not use metal
pipes, chains, wires, etc., to clean the chimney because such items can
scratch the surface of the stainless steel flue which can shorten the life of
the flue and provide a rough surface for soot particles to attach to. Be sure
to cover nearby furnishing and arrange some method of catching soot and
creosote parti-cles that may fall during the chimney cleaning process. If
glass doors are installed on the fireplace, they should be closed. Extra
caution must be used to avoid damage to the flue damper during the cleaning
process. In addition to checking and cleaning the chimney on a regular basis,
be sure to inspect the chimney before starting a fire at the beginning of each
heating season. Make sure the chimney is clear from any accumulation of soot,
creosote or any other debris, and that all joints are intact. MHSC does not
recommend chemical cleaners because some may contain elements that corrode the
metal parts of the chimney or fireplace.
Fireplace Maintenance
At the end of each heating season or when the fireplace will not be in use for
an extended time, the ashes should be removed and the hearth area should be
swept as clean as is practical. The slow ab-sorption of moisture into the
ashes over a long period of time could cause a condition which would be
corrosive to the metal fireplace parts.
At the beginning of each heating season, always operate the flue damper and
make sure it has not become stuck from soot, creosote, etc., during the period
of inactivity. Keep the lower and upper grille panels clean and free from dirt
and lint accumulation at all times to get the maximum efficiency from your
fireplace. As you use the fireplace, expansion and contraction will cause minor
cracking of the hearth, back, and side refractory materials. This is normal
and unavoidable. If the cracks become large enough or parts dislodge and metal
behind the refractory is exposed, the refractory panels should be replaced
with new panels that can be obtained from you fireplace dealer.
Glass Door Maintenance
For glass door maintenance, see instructions provided with the glass doors.
Checklist of Do’s and Dont’s DO’S
- Do check with local building officials to be sure the installation of the fireplace complies with all building codes and requirements and obtain required building permits. Do plan your installation with safety as you primary consideration.
- Do use only the prescribed material and parts for the installation of the fireplace.
- Do insulate the exterior walls surrounding the fireplace to prevent excessive heat loss from the fireplace.
- Trim the face of the fireplace only with noncombustible materials.
- Do attach the noncombustible face trim material firmly to the face of the fireplace.
- Do block in or fasten the fireplace to prevent the possibility of the fireplace shifting out of position.
- Do connect the air circulation blower to a properly grounded and fused electrical circuit.
- Do enclose the chimney where it passes through living spaces or spaces accessible for storage purposes to prevent contact with and possible damage to the chimney.
- Do install firestop spacers at each ceiling level when the chimney is installed in a multistory building.
- Do install the proper chimney cap or chimney housing on the chimney to prevent rain and debris from entering the chimney.
- Do keep all flammable liquids, gases and pressurized containers away from the fireplace.
- Do check the fireplace for proper adjustment and operation before leaving it unattended for long periods of time.
- Do inspect and clean the fireplace chimney regularly.
- Do keep the fire screens closed when the fireplace is left unattended to minimize the danger of sparks popping out of the fireplace.
- Do use the grate furnished with and for this fireplace.
- Do start a fire only with paper, kindling or solid composition fire starters specifically designed for starting a fire. The use of a liquid fire starter can cause an explosion within the fireplace.
- Do place all ashes in a metal container with a tight fitting lid and place them on a noncombustible surface well away from other combustible materials until they have completely cooled.
- Do store your fuel supply at a distance equal to or greater than the spacing recommended for combustible materials from the fireplace.
- Do build fires of moderate intensity in the fireplace for the first three fires to allow materials to adjust and cure before being subjected to the intense heat of a large fire.
DONT’S
- Don’t allow other installations or operation considerations to take priority over safety considerations.
- Don’t attempt to use the fireplace until the installation is complete.
- Don’t use unlisted parts and accessories with the fireplace except for special flashings that may be fabricated locally.
- Don’t use damaged parts or accessories with this fireplace.
- Don’t install the fireplace in an exposed or uninsulated area.
- Don’t install the fireplace over carpeting.
- Don’t install the fireplace on a poorly constructed base or fail to fasten down or attach the fireplace to prevent it from shifting out of position.
- Don’t create or allow a crack to develop between the metal face of the fireplace and noncombustible trim.
- Don’t use power blowers or air circulation systems with this fireplace that are not specifically recom-mended by MHSC.
- Don’t connect accessory air circulation blowers to improperly fused or ungrounded electrical circuits.
- Don’t install the fireplace where flammable or explosive liquids or vapors are likely to be present.
- Don’t neglect all the considerations mentioned in this manual concerning clearances to combustibles, spacing from obstructions and proper chimney height when selecting the location and installing the chimney.
- Don’t allow insulating materials to contact the chimney.
- Don’t neglect to apply caulking or mastic to the required joints of the flashing and between the flashing roof.
- Don’t dry clothing or other articles near the fireplace.
- Don’t store or place flammable liquids, gases or pressurized containers near the fireplace.
- Don’t neglect to instruct all responsible persons in the proper and safe operation of the fireplace.
- Don’t fail to instruct all persons, especially children and elderly persons, concerning the hazards of improper operation and unauthorized tampering with the fireplace.
- Don’t use this fireplace to burn paper, cardboard, or other debris.
- Don’t neglect to inspect and clean the chimney regularly.
- Don’t operate the fireplace with the glass fire screen doors partially open. The doors should always be fully open or fully closed.
- Don’t use gasoline, kerosene, engine oil,or charcoal lighter fluid.
- Don’t store fuel supply closer to the fireplace than the minimum spacing required for combustible ma-terials.
- Don’t subject the fireplace to the intense heat of a large fire the first three times the fireplace is used, but build moderate fires to allow the materials to cure and adjust.
- Don’t clean the chimney with metallic devices or chemical cleaners.
- Don’t use the fireplace or chimney for venting wood or coal burning heaters or inserts unless approved in writing by MHSC.
- Don’t put combustibles within 24 inches of the fireplace opening.
“WARNING: IF NOT INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MAN-UFACTURERS INSTRUCTIONS, THIS PRODUCT COULD EXPOSE YOU TO SUBSTANCES IN FUEL OR FROM FUEL COMBUSTION WHICH CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM. ALSO, OPERATION, INSTALLATION AND SERVICING OF THIS PRODUCT COULD EXPOSE YOU TO AIRBORNE PARTICLES OF GLASS WOOL FIBERS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER THROUGH INHALATION.”
PARTS DIAGRAM AND LIST
All repair part orders should be placed through your local dealer. To ensure prompt and accurate ser-vice, please provide the following information when placing a repair part order: Model number of your Appliance, Part Name, Part Number, and Quantity of parts needed.
- Technical Service Department MHSC
- 149 Cleveland Drive
- Paris, KY 40361
- www.mhsc.com
LIMITED WARRANTY
FACTORY-BUILT FIREPLACE AND COMPONENTS (except blowers)
What is Covered and For How Long
- Five-Year Coverage – For five years from the date this fireplace and components are first purchased for use, MHSC will, at its option, repair or replace any defective part of this fireplace or components, or refund to you a sum not to exceed the factory retail price in effect at the time of purchase.
- Ten-Year Coverage – From the sixth through the tenth year following the date this fireplace or accessory is first purchased for use, MHSC will make available to you, at our factory, a free replacement for any defective part in this fireplace or accessory.
- Twenty-Five-Year Availability of Replacement Parts – From the eleventh through the twenty-fifth year following the date this fireplace or accessory is first purchased for use, MHSC will make available at our factory replacement parts for this fireplace or accessory, which you may purchase for the list price current at the time your purchase order is received.
What is Not Covered
This limited warranty does not cover:
- Transportation or shipping cost.
- The cost of a service call to diagnose trouble.
- Painted surfaces.
- Damage or defect caused by improper installation, accident, misuse, abuse or alteration.
- Poor ventilation of smoke or gases caused by air-conditioning and heating systems, exhaust fans or pressure differentials produced by wind.
- Broken glass components.
- Cracks in ceramic and castable parts that do not affect safe operation.
- We do not warrant this fireplace to be in compliance with your local building code. Building codes vary greatly throughout the country, and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchase it.
- Blowers or fans, which are warranted separately.
- Heat loss due to the passage of heat or air through or around the fireplace.
Also, under our five year coverage, we do not pay the cost of removal and replacement of any portion of the structure in which the fireplace is situated, made necessary by the repair, removal or re-installation of the fireplace. And under our twenty-five year warranty of availability of replacement parts, we only promise to maintain a supply of replacement parts at our factory for you to purchase.
Limitations and Exclusions
- No one has authority to add to or vary this limited warranty, or to create for MHSC any other obligation of liability in connection with this fireplace and accessory.
- MHSC shall not be liable for incidental, consequential, special or contingent damages you might suffer as a result of its breach of the written warranty or any implied warranty. Some states do not allow the exclusion of limitation of incidental or consequential damages, so the above limitations may not apply to you.
- This warranty applies only to the original purchaser of the fireplace or to the original owner of the dwelling when the fireplace is installed in a new dwelling and may not be transferred.
- This warranty applies only to a fireplace sold and used in the United States. Your Duties This fireplace must be installed by a qualified installer according to your local building codes and installation instructions and operated according to the owner’s instructions. You must keep an invoice, canceled check or payment record to verify the purchase date of the fireplace.
If Warranty Service is Needed…
- Contact your supplier. Make sure you have your warranty, your sales receipt and the model/serial number of your MHSC product.
- DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
- 149 Cleveland Drive
- Paris, Kentucky 40361
- www.mhsc.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>