CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors Installation Guide

June 13, 2024
CP electronics

WD966 Issue 4 Installation Guide
EBMPIR-MB-AD-LT30
Mini PIR Detector for Luminaire Integration (Batten Mount)

EBMPIR-MB-AD-LT30

1–10V analogue dimming, miniature, low temp, luminaire mounted, PIR, presence detector
CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence
Detectors Warning

This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.

Dimensions (mm)

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 1

Downloads and Videos

cpelectronics.co.uk/cp/966

Detection pattern

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 2

Walk across

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 3

Height Range Diameter
9m 14m
7m 13m
5m 11m
3m 8m

Walk towards

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 4

Height Range Diameter
9m 7m
7m 7m
5m 7m
3m 5m

Walk towards & walk across explained

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors - QR
Code 2

cpelectronics.co.uk/cp/wta

Wiring

Dimming outputs

Basic insulation only. Although low voltage, this is not an SELV output and should be treated as if mains potential. Use mains rated wiring.

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 5

Key

  1. Neutral
  2. Live
  3. 10A circuit protection if required
  4. Load

IP luminaire fitting

Cut mounting hole

Mounting without key

Mounting with key. Note: Key to be at the top of the sensor.

Wire in plugs & connect to detecto

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 8

Key

  1. M20 nut
  2. 5° washer (optional)
  3. Silicone washer
  4. IP spacer
    • Note: Use the 5° spacers where the luminaire has a draft angle.
    • Ensure that the silicone washer and/or IP spacer are used to maintain IP rating.

Default Settings

Time out: 20 minutes.
LUX on level: 9
LUX off level: 9
Sensitivity: 9
Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.

Testing

Presence Detection

CP electronics EBMPIR-MB-AD-LT30 Ceiling Mounted PIR Presence Detectors -
Fig 9

  1. Power up the sensor. The load should come on immediately.
  2. Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
  3. Enter the room or make some movement and check that the load switches on.

Technical Data

Part code EBMPIR-MBAD-LT30
Weight 0.100kg
Supply voltage AC 230 VAC +/- 10%
Supply frequency 50Hz
Power consumption parasitic 817mW
Max load:
Incandescent lighting 2A
Fluorescent lighting 2A
Compact fluorescent lighting 2A
LED lighting 2A
Resistive heaters 2A
Cable specification 1m 1/1.13 solid core cable 105ºC
Number of drivers/ballasts Up to 4
SON lighting Switch loads via a contactor
Working temperature range -30 to 35°C
Humidity 5 to 95% noncondensing
Material (casing) Flame retardant ABS/PC
Insulation class 2
IP rating 65
Compliance **** EMC-2014/30/EU

LVD-2014/35/EU

Accessories & associated products

Part Number
Description

| Compact, programming/commissioning handset
---|---
| Compact, user handset
| Universal LCD IR handset/commissioning handset

CP Electronics
A Business unit of Legrand Electric Limited,
Brent Crescent, London NW10 7XR, UK
t. +44 (0)333 900 0671
enquiry@cpelectronics.co.uk

www.cpelectronics.co.uk
connect with us

Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
WD966 Issue 4 Installation Guide, EBMPIR-MB-AD-LT30

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CP electronics User Manuals

Related Manuals