smappee MID 100A Series DIN Rail Smart Meters User Manual
- June 13, 2024
- smappee
Table of Contents
MID 100A SERIES
DIN rail smart meters for single and three phase electrical systems
User manual v1.0
Introduction
This document provides operating, maintenance and installation instructions.
These units measure and display the characteristics of single phase two wires
(1p2w), three phase three wires (3p3w) and three phase four wires (3p4w)
networks. The measuring parameters include voltage (V), frequency (Hz),
current (A), power (kW/kVa/kVar), import, export and total Energy (kWh/kVarh).
The units can also measure Maximum demand current and power, this is measured
over preset periods of up to 60 minutes.
These units are max 100A direction operated and do not need to connect with
external current transformers (CT).Built-in pulse, RS485 Modbus RTU/Mbus
outputs. Configuration is password protected.
1.1 Unit characteristics
The Smappee MID 100A SERIES meters have seven models, 1 is used:
Model | Measurement | Output | Tariff |
---|---|---|---|
i1-EN3-1 | kWh/kVarh, kW/kVar, kVA, P, F,PF, dmd, V, A, THD… | pulse/Modbus | — |
1.2 RS485 serial Modbus RTU
RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit. Setup screens are provided for setting up
the RS485 port.
1.3 Mbus
This uses an MBus port with EN13757-3 protocol to provide a means of remotely
monitoring and controlling the Unit. Set-up screens are provided for setting
up the MBus port.
1.4 Pulse output
Two pulse outputs that pulse measured active and reactive energy. The constant
of pulse output 2 for active energy is 400imp/kWh (unconfigurable), its width
is fixed at 100ms.
The default constant of configurable pulse output 1 is 400imp/kWh, default
pulse width is 100ms. The configurable pulse output 1 can be set from the set-
up menu.
Start-up screens
The first screen lights up all display segments and can be used as a display check.
Software version information.
The interface performs a selftest and indicates the result if the test passes.
After a short delay, the screen will display active energy interface as
follows:
Total active energy in kWh.
Measurements
The buttons operate as follows:
| Selects the Voltage and Current display screens.In Set-up mode, this is the
“Left” or “Back” button.
---|---
| Select the Frequency and Power factor display screens. In Set-up mode, this
is the “Up” button.
| Select the Power display screens. In Set-up mode, this is the “Down” button.
| Select the Energy display screens. In Set-up mode, this is the “Enter” or
“Right”.
3.1 Voltage and current
Each successive press of the button selects a new parameter:
Phase to neutral voltages.
Current on each phase.
Phase to neutral voltage THD% of 2 nd to 19 th .
Each phase Current THD% of 2 nd to 19 th.
3.2 Frequency, power factor and demand
Each successive press of the button selects a new range:
Frequency and Power Factor (total).
Power Factor of each phase.
Maximum Power Demand.
Maximum Current Demand.
3.3 Power
Each successive press of the button selects a new range:
Instantaneous Active Power in kW.
Instantaneous Reactive Power in kVar.
Instantaneous Volt-Amps in KVA.
Total kW, kVarh, kVA.
3.4 Energy measurements
Each successive press of the button selects a new range:
Import active energy in kWh.
Export active energy in kWh.
Total active energy in kWh.
Import reactive energy.
Export reactive energy.
Total reactive energy.
*The date and time can only be set via RS485 communication.
Set-up
To enter set-up mode, press the button for 3 seconds, until the password screen appears. Setting up is passwordprotected so you must enter the correct password (default 1000) before processing. Press the button for 3 seconds to confirm.
If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is
restored.
4.1 Set-up entry methods
Some menu items, such as password, require a fourdigits number entry while
others, such as supply system, requireselection from a number of menu
options.
4.1.1 Menu option selection
- Use the and buttons to scroll through the different options of the set-up menu.
- Press to confirm your selection.
- If an item flashes, then it can be adjusted by the and buttons.
- Having selected an option from the current layer, press to confirm your selection. The SET indicator will appear.
- Having completed a parameter setting, press to return to a higher menu level. The SET indicator will be removed and you will be able to use the and buttons for further menu selection.
- On completion of all setting-up, press repeatedly until the measurement screen is restored.
4.1.2 Number entry procedure
When setting up the unit, some screens require the entering of a number. In
particular, on entry to the setting up section, a password must be entered.
Digits are set individually, from left to right. The procedure is as follows:
- The current digit to be set flashes and is set using the and buttons.
- Press to confirm each digit setting. The SET indicator appears after the last digit has been set.
- After setting the last digit, press to exit the number setting routine. The SET indicator will be removed.
4.2 Change password
Use and to choose the change password option.
Press to enter the change password routine. The new password screen will appear with the first digit flashing.
Use and to set the first digit and press to confirm your selection. The next digit will flash.
Repeat the procedure for the remaining three digits.
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET
will be removed.
4.3 Supply system
*The unit has a default setting of 3Phase 4wire (3P4).
Use this section to set the type of electrical system.
From the set-up menu, use and to select the system option. The screen will show the currently selected power supply.
Press to enter the selection routine. The current selection will flash.
Use a and to select the required system option: 1P2 (W), 3P3 (W), 3P4 (W).
Press to confirm the selection. SET indicator will appear.
Press to exit the system selection routine and return to the menu. SET will
disappear and you will be returned to the main set-up Menu.
4.4 Backlit set-up
Backlit lasting time is settable, default is 60minutes.
If it’s setted as 5, the backlit will be off in 5 minutes if there is no more further operation.
Press to enter the selection routine. The current time interval will flash.
The options are: 0 (always on) /5/10/30/60/120
Press and to select the time interval. Then press to confirm the set-up.
4.5 Communication
There is RS485/Mbus port can be used for communication Modbus RTU protocol.
For Modbus RTU, parameters are selected from front panel.
The first screen below shows a range from 001 to 247.
From the set-up menu, use and to select the address ID.
Press to enter the selection routine. The current setting will flash.
Use and to choose Modbus address (001 to 247).
On completion of the entry procedure, press to confirm the setting and press
to return to the main set-up menu.
4.6 Demand integration time (DIT)
This sets the period in minutes over which the current and power readings are
integrated for maximum demand measurement. The options are: 0, 5, 8, 10, 15,
20, 30, 60 minutes.
From the set-up menu, use and to select the DIT option. The screen will show the currently selected integration time.
Press to enter the selection routine. The current time interval will flash.
Use and to select the time required.
Press to confirm the selection. SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
4.7 Demand integration time (DIT)
This sets the period in minutes over which the current and power readings are
integrated for maximum demand measurement. The options are: 0, 5, 8, 10, 15,
20, 30, 60 minutes.
From the set-up menu, use and to select the DIT option. The screen will show the currently selected integration time.
Press to enter the selection routine. The current time interval will flash.
Use and to select the time required.
Press to confirm the selection. SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
4.8 CLR
The meter provides a function to reset the maximum demand value of current and
power.
From the set-up menu, use and to select the reset option.
Press to enter the selection routine. The MD will flash.
Press to confirm the setting and press to return to the main set-up menu.
4.9 Pulse output
This option allows you to configure the pulse output 1. The output can be set
to provide a pulse for a defined amount of energy active or reactive. Use this
section to set up the pulse output for:
- Total kWh/Total kVarh
- Import kWh/Export kWh
- Import KVarh/Export KVarh
From the set-up menu, use and to select the Pulse output option.
Press to enter the selection routine. The unit symbol will flash.
Use and to choose kWh or kVarh.
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
4.9.1 Pulse rate
Use this to set the energy represented by each pulse.
Rate can be set to 1 pulse per dFt/0.01/0.1/1/10/100 kWh/ kVarh. The first
screen below shows 1 pulse = 10kWh/ kVarh.
From the set-up menu, use and to select the Pulse rate option.
Press to enter the selection routine. The current setting will flash. When
it’s dFt (default), it means 2.5Wh/Varh.
Use and to choose pulse rate. On completion of the entry procedure, press
to confirm the setting andpress to return to the main set-up menu.
4.9.2 Pulse duration
The pulse width can be selected as 200ms (non-MID version meters only), 100ms
(default) or 60ms.
The first screen below shows default pulse width.
From the set-up menu, use and to select the Pulse width option.
Press to enter the selection routine. The current setting will flash.
Use and to choose pulse width. On completion of the entry procedure, press to
confirm the setting and press to return to the main set-up menu.
Specifications
5.1 Measured parameters
The unit can monitor and display the following parameters of a single phase
two wire (1p2w), three phase three wire (3p3w) or three phase four wire (3p4w)
system.
5.1.1 Voltage and current
- Phase to neutral voltages 176 to 276V a.c. (not for 3p3w supplies).
- Voltages between phases 304 to 480V a.c. (3p supplies only).
- Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies).
- Percentage voltage TH D% between phases (three phase supplies only).
- Current THD% for each phase.
5.1.2 Power factor, frequency and max demand
- Frequency in Hz
- Instantaneous power:
- Power 0 to 99999 W
- Reactive power 0 to 99999 Var
- Volt-amps Oto 99999 VA
- Maximum demanded power since last Demand reset Power factor
- Maximum neutral demand current, since the last Demand reset (for three phase supplies only)
5.1.3 Energy measurements
- Import active energy: 0 to 999999.99 kWh
- Export reactive energy: 0 to 999999.99 kVarh
- Import active energy: 0 to 999999.99 kWh
- Export reactive energy: 0 to 999999.99 kVarh
- Total active energy: 0 to 999999. 99 kWh
- Total reactive energy: 0 to 999999.99 kVarh
5.2 Measured inputs
Voltage inputs through 4-way fixed connector with 25mm2 stranded wire
capacity, single phase two wire (1 p2w), three phase three wire (3p3w) or
three phase four wire (3p4w) unbalanced. Line frequency measured from L1
voltage or L3 voltage.
5.3 Interfaces for external monitoring
Three interfaces are provided:
- RS485/Mbus communication channel that can be programmed via protocol remotely. (not for SDM630Pulse V2)
- Pulse output (pulse1) indicating real-time measured energy (configurable)
- Pulse output (pulse2) 400imp/kWh (not configurable) The Modbus/Mbus configuration (baud rate, etc) and the pulse relay output assignments (kW/kVarh, import/ export, etc) are configured through the set-up screens.
5.3.1 Pulse output
The pulse output can be set to generate pulses to represent
kWh or kVarh. Rate can be set to generate 1 pulse per:
- dFt = 2.5 Wh/Varh (default)
- 0.01 = 10 Wh/Varh
- 0.1 = 100 Wh/Varh
- 1 = 1 kWh/kVarh
- 10 = 10 kWh/kVarh
- 100 = 1 00 kWh/kVarh
Pulse width: 200/100/60 ms
Pulse output 2 is non-configurable. It is fixed up with active kWh. Its constant is 400imp/kWh.
5.3.2 RS485/Mbus output for communication
For Modbus RTU, the following RS485 communication parameters can be configured
from the set-up menu:
- Baud rate: 2400, 4800, 9600, 19200, 38400
- Parity: none, odd, even
- Stop bits: 1 or 2
- RS485 network address (nnn): 001 to 247
If the Modbus/Mbus protocol document is required, please contact us.
5.4 Accuracy
- Voltage: 0.5 % of range maximum
- Current: 0.5 % of nominal
- Frequency: 0.2 % of mid-frequency
- Power factor: 1 % of unity (0.01)
- Active power (W): ± 1 % of range maximum
- Reactive power (VAr): ± 1 % of range maximum
- Apparent power (VA): ± 1 % of range maximum
- Active energy (Wh): Class 1 IEC 62053-21,
- Reactive energy (VARh): Class B EN504 70-3
- Response time to step input: ± 1 % of range maximum 1s, typical, to >99% of final reading, at 50 Hz
5.5 Reference conditions of influence quantities
Influence Quantities are variables that affect measurement errors to a minor
degree. Accuracy is verified under nominal value (within the specified
tolerance) of these conditions.
-
Ambient temperature: 23°c ± 2°c
-
Input frequency: 50 Hz (MID), 50 or 60Hz ±2% (non-MID)
-
Input waveform: Sinusoidal (distortion factor < 0.005)
Terrestrial flux -
Magnetic field of ext. origin:
5.6 Environment
- Operating temperature: -25°C to +55°C*
- Storage temperature: -40°C to +70°C*
- Relative humidity: 0 to 95%, non-condensing
- Altitude: Up to 2000m
- Warm up time: 1 minute
- Vibration: 10Hz to 50Hz, IEC 60068-2-6, 2g 30g in 3 planes
- Shock:
*Maximum operating and storage temperatures are in the context of typical daily and seasonal variation.
5.7 Mechanics
- DIN rail dimensions: 72×100mm (W×H) per DIN 43880
- Mounting: DIN rail (DIN 43880)
- Sealing: IP51 (indoor)
- Material: Self-extinguishing Ul94 V-0
5.8 Reference conditions of influence quantities
We, Smappee n.v., Declare under our sole responsibility as the manufacturer
that the poly phase multifunction electrical meter “SMAPPEE MID 100A series”
correspond to the production model described in the EU-type examination
certificate and to the requirements of the Directive 2014/32/EU EU type
examination certificate number 0120/SGS0462. Identification number of the
NB0120.
Dimensions
Wiring diagram
Interface for external monitoring:
7.1 Single phase two wires (1P2)
7.2 Three phase three wires (3P3 )
7.3 Three phase four wires (3P4)
Safety warnings
Important Safety lnformation is contained in the Maintenance section.
Familiarize yourself with this information before attempting installation or
other procedures.
Symbols used in this document:
Risk of Danger: These instructions contain important safety information.
Read them before starting installation or servicing of the equipment.
Caution: Risk of Electric Shock.
Evolis 104, 8530 Harelbeke, Belgium
info@smappee.com
www.smappee.com
Documents / Resources
|
smappee MID 100A Series DIN Rail Smart
Meters
[pdf] User Manual
MID 100A Series, MID 100A Series DIN Rail Smart Meters, DIN Rail Smart Meters,
Rail Smart Meters, Smart Meters, Meters
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>