INSTRUCTIONS
FIELD-ADJUSTABLE RBAY17™ INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE
REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside. Suitable for damp locations.
FOR V-HOOK / CHAIN MOUNTING
Mount Housing to sturdy ceiling structure as follows:
-
V-Hook (2) and 3.28ft Chain (2) are provided for mounting. Secure V-Hooks through Side Slots on housing as shown in Fig. 1 and 2.
Secure Chain to V-Hooks as shown in Fig. 2 and 3. -
Remove Access Plate ( See Fig. 2 for RBAY17S & RBAY17M, see Fig. 3 for RBAY17L) and feed supply wires with strain relief connector. Make electrical connections as shown in wiring diagram (Fig. 14). Use approved wiring connectors and wire to local NEC codes. Push all wires back into Housing. Be careful not to pinch wires.
-
Reinstall Access Plate and secure with supplied Screw (1).
RBAY17S / RBAY17M PENDANT MOUNTING
(Accessory ordered separately – Model# PMKRBAY17S and PMKRBAY17M)
- Choose length of a 3/4” NPS Pendant Stem (by others).
- Install Pendant Junction Box (ordered separately) to Pendant Stem (by others) and secure with Locknuts (by others) as shown in Fig. 5.
- Mount Housing onto the Pendant Junction Box by securing with Hook feature and tightening (2) Screws (provided) as shown in Fig. 6.
- Remove the Knockout from Side Panel ( Fig. 6). Pull supply wires through side Knockout and feed supply wires through Flex Conduit (provided) as shown in Fig. 6. Secure Flex Conduit to Side Panel and secure Side Panels with (2) Screws (provided) as shown in Fig. 4. Wire the Housing leads to supply wires using UL listed wire connectors according to NEC and local codes.
- Push all wires back into Housing. Be careful not to pinch wires.
- Secure Flex Conduit to Access Plate (Fig. 6).
RBAY17L PENDANT MOUNTING
(Accessory ordered separately – Model# PMKRBAY17L)
- Choose length of a 3/4” NPS Pendant Stem (by others).
- Install Pendant Junction Box (ordered separately) to Pendant Stem ( by others) and secure with Locknuts (by others) as shown in Fig. 5.
- Pull supply wires and connect to Housing leads using UL listed wire connectors according to NEC and local codes.
- Push all wires back into Housing and secure Access Plate with provided Screw (1).
- Mount Housing onto the Pendant Junction Box by securing into the Hook feature and tightening (2) Screws (provided) as shown in Fig. 8
- Install Side Panels with provided (2) Screws (provided) (Fig. 8). Be careful not to pinch wires.
RBAY17S / RBAY17M SURFACE MOUNTING
Mount Surface Mounting Bracket to sturdy structure as follows:
(Accessory ordered separately – Model# SMKRBAY17S and SMKRBAY17)
- Install Surface Mounting Bracket (ordered separately) to sturdy surface with Fastener (by others) as shown in Fig. 9.
- Wire the Housing leads to supply wires using UL listed wire connectors according to NEC and local codes. Secure Access Plate with (1) Screw (provided).
- Mount Housing onto the Surface Mounting Bracket by securing with Hook (4) feature and (2) Screws (provided) as shown in Fig. 10.
RBAY17L SURFACE MOUNTING
Mount Surface Mounting Bracket to sturdy surface as follows:
(Accessory ordered separately – Model# SMKRBAY17)
- Install Surface Mounting Bracket (ordered separately) to sturdy surface with Screws (by others) as shown in Fig. 9.
- Wire the Housing leads to supply wires using UL listed wire connectors according to NEC and local codes. Secure Access Plate with (1) Screw (provided).
- Mount Housing onto the Surface Mounting Bracket by securing with Hook (4) feature and (2) Screws (provided) as shown in Fig. 11.
FIELD ADJUSTMENT
Follow instructions below to change the Fixture Power (W) and/or Color Temperature (CCT ) from factory settings:
Factory Settings:
RBAY17S 130/100/80W| 130W / 4000K
RBAY17M 260/220/160W| 260W / 4000K
RBAY17L 400/320/260W| 400W / 4000K
- Locate the selector switches located on the side of the housing as shown (RBAY17S, RBAY17M Fig. 12, RBAY17L Fig. 13).
- Select Color Temperature (CCT) and/or Power (W) by sliding the respective switch to the desired value.
MVS/PIR SENSOR INSTALLATION
For units ordered with MVS or PIR Sensor follow directions below.
- Remove Sensor Base Plug located on the Housing as shown in Fig. 14.
- Insert MVS or PIR Sensor into the Sensor Base Plug and turn to secure as shown in Fig. 15.
- See MVS/PIR Sensor instructions for pre-sets and programmable settings.
- Use optional remote Model# MSR1(ordered separately) for user programming.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60
Hz. Units ordered with /480 suffix are 480V, 50 or 60Hz only.
For 0-10V dimming, follow the wiring directions as shown in Fig. 16.
- Connect the black fixture lead to the LINE supply lead.
- Connect the white fixture lead to the COMMON supply lead.
- Connect the GROUND wire from fixture to supply ground.
- Connect the purple fixture lead to the (V+) DIM lead.
- Connect the pink fixture lead to the (V-) DIM lead.
NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.
- Lens can be washed only after removing from fixture and only in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Do not use chemicals to clean Lens or fixture.
- Do not open fixture to clean the LED. Do not touch the LED.
Note: These instructions do not cover all details or variations in equipment nor do they provide every possible situation during installation, operation or maintenance.
TROUBLESHOOTING
- Check that the line voltage at the fixture is correct.
- Be sure the fixture is grounded properly.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
BATTERY BACKUP MODELS
WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY.
To prevent high voltage from being present on output leads, Inverter connector
must be open. Do not join BATTERY connector until installation is complete.
NOTE: Make sure that the necessary branch circuit wiring is available. An
UNSWITCHED AC source of power is required.
The emergency driver must be fed from the same branch circuit as the LED
driver. Reference Fig. 18 for wiring diagram.
CAUTION: Do not use any supply voltage other than 120-277V.
- Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect SWITCHED HOT lead to the switch.
- For 0-10V dimming, connect DIM (+) purple and DIM (-) pink leads to 0-10V dimming connection.
- All unused leads must be capped and insulated.
- After installation is complete connect the battery as shown in Fig. 17.
- When power is on, the fixture should be on and the CHARGING INDICATOR LIGHT should illuminate to indicate the battery is charging.
- Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button as shown in Fig. 19.
- After the battery has charged for 24 hours, a long duration test can be performed by disconnecting power to the fixture.
|
---|---
OPERATION
- When AC power is applied the charging indicator light is illuminated indicating that the BATTERY is being charged.
- When power fails the standby power automatically switches to emergency power (internal battery) operating at reduced illumination.
- When AC power is restored the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Be sure the fixture is grounded properly.
- If the charging indicator light does not illuminate after pressing and releasing the Test Button (Fig. 19), check power and check if battery is connected properly.
© 2022 RAB LIGHTING Inc.
RBAY17 S-M-L – IN – 1222
P-100141
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request
RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found
at rablighting.com/warranty.
References