Carrier 40MHHA High Wall Ductless System Instruction Manual
- June 13, 2024
- Carrier
Table of Contents
- Carrier 40MHHA High Wall Ductless System
- INDUSTRY LEADING FEATURES / BENEFITS
- MODEL NUMBER NOMENCLATURE
- STANDARD FEATURES AND ACCESSORIES
- DIMENSIONS
- CLEARANCES
- SPECIFICATIONS (HEAT PUMP)
- COMPATIBILITY
- SPECIFICATIONS (COOLING ONLY)
- APPLICATION DATA
- WIRING All wires must be sized per NEC (National Electrical Code) or CEC
- AIR FLOW DATA
- AIR THROW DATA
- AIR MOISTURE
- SOUND PRESSURE
- FAN AND MOTOR SPECIFICATIONS
- WIRING DIAGRAM
- GUIDE SPECIFICATIONS
- Documents / Resources
Carrier 40MHHA High Wall Ductless System
INDUSTRY LEADING FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN BUDGET LIMITS, ENERGY SAVINGS AND COMFORT.
The 40MHHA series ductless systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the wall, near the ceiling. This selection of fan coils permits creative solutions to design problems such as:
- Add-ons to current space (an office or family room addition)
- Special space requirements
- When changes in the load cannot be handled by the existing system
- When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork
- Historical renovations or any application where preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork. These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors.
Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.
LOW SOUND LEVELS
When noise is a concern, the ductless systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since the outdoor units can be installed close to an outside wall, coils are protected from vandals and severe weather.
FAST INSTALLATION
This compact ductless system is simple to install. A mounting bracket is standard with the indoor units and only wire and piping need to be run between the indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in the home or workplace. This makes the 40MHHA ductless systems the equipment of choice, especially in retrofit situations.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel on outdoor units provides immediate access to the control compartment, providing a service technician access to check unit operation. In addition, the draw-thru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent. On all indoor units, service and maintenance expense is reduced. In addition, these high wall systems have extensive self-diagnostics to assist in troubleshooting.
BUILT-IN RELIABILITY
Ductless system indoor and outdoor units are designed to provide years of
trouble-free operation.
The high wall indoor units include protection against freeze-up and high
evaporator temperatures on heat pumps.
The condensing units on heat pumps are protected by a three minute time delay
before the compressor starts the over-current protection and the high
temperature protection.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year around comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The ductless system design allows individual room heating or cooling when required. Equipped with a New Occupancy Sensor, the system can be set to only operate when the room is being utilized. There is no need to run large supply- air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted while air moves through the ducts.
EASY-TO-USE CONTROLS
EASY-TO-USE CONTROLS
The high wall units have microprocessor-based controls to provide the ultimate
in comfort and efficiency. The user friendly wireless remote control provides
the interface between the user and the unit.
ACCESSORIES
Customizing these ductless systems to your application is easily accomplished. Adding a condensate pump accessory to the high wall fan coil provides installation flexibility.
OPTIONAL WIRED CONTROLLER
OPTIONAL 24V INTERFACE FOR THIRD PARTY CONTROL
OPTIONAL WI-FI KIT FOR SMART PHONE CONTROL
AGENCY LISTING
All systems are listed with AHRI (Air Conditioning, Heating & Refrigeration Institute), and UL.
MODEL NUMBER NOMENCLATURE
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting Brackets| S
Low Voltage Controls| S
Mounting Template| S
Comfort Features|
Microprocessor Controls| S
Wired Remote Controller| A
Wireless Remote Controller| S
Automatic Up-Down Airflow Louver Swing| S
Air Direction Control| S
Auto Restart Function| S
Wi-Fi Control| A
Cold Blow Protection On Heat Pumps| S
Freeze Protection Mode on Heat Pumps| S
Turbo Mode| S
Silence Mode| S
Auto Changeover on Heat Pumps| S
Follow Me| S
ECO Mode| S
Energy Saving Features|
Sleep Mode| S
Stop/Start Timer| S
46° F Heating Mode (Heating Setback)| S
Safety And Reliability|
Indoor Coil Freeze Protection| S
Indoor Coil High Temp Protection in Heating Mode| S
Aluminum Hydrophilic pre-coated fins| S
Ease Of Service And Maintenance|
Cleanable Filters| S
Diagnostics| S
Carbon Filter| S
Application Flexibility|
Condensate Pumps| A
Accessories
Accessory No. | Description | For Models |
---|---|---|
KSAIF0601AAA | Wi-Fi™ Kit High Wall | All Sizes |
KSACN0101AAA | Wired Remote Control with Timer Function | All Sizes |
KSAIC0301230 | 24V Interface Kit 230V | 208/230V models |
KSACN0901AAA | Wired Remote Control 7 Day Programmable | All Sizes |
DIMENSIONS
HIGH WALL UNIT SIZE| | 9K| 1 2 K| 9K|
12K| 18K| 24K| 3 0K| 36K
---|---|---|---|---|---|---|---|---|---
(Voltage)| | (115V)| (115V)| (208/230V)| (208/230V)| (208/230V)| (208/230V)|
(208/230V)| (208/230V)
DIMENSIONS
Height (H)| In/
(mm)
| 11.5(292)| 11.61(295)| 11.5(292)| 11.61(295)| 12.64(321)| 13.27(337)|
14.25(362)| 14.25(362)
Width (W)| In/
(mm)
| 28.7(729)| 31.57(802)| 28.7(729)| 31.57(802)| 38.23(971)| 42.60(1082)|
49.57(1259)| 49.57(1259)
Depth (D)| In/
(mm)
| 7.87(200)| 7.87(200)| 7.87(200)| 7.87(200)| 8.98(228)| 9.21(234)| 11.14(283)| 11.14(283))
PACKING
Height| In/
(mm)
| 14.76(375)| 14.96(380)| 14.76(375)| 14.96(380)| 15.94(405)| 12.40(315)|
15.16(385)| 15.16(385)
Width| In/
(mm)
| 31.1(790)| 34.45(875)| 31.1(790)| 34.45(875)| 41.14(1045)| 45.47(1155)|
52.76(1340)| 52.76(1340)
Depth| In/
(mm)
| 10.63(270)| 11.22(285)| 10.63(270)| 11.22(285)| 12.01(305)| 16.34(415)|
17.72(450)| 17.72(450)
Material| –|
Double corrugated
Weight – Gross| lbs. (kg)| 22.71(10.3)| 24.03(10.9)| 22.49(10.2)| 24.03(10.9)|
31.75(14.4)| 38.14(17.3)| 55.56(25.2)| 55.56(25.2)
Weight-Net| lbs. (kg)| 17.64(8.0)| 18.52(8.4)| 17.64(8.0)| 18.74(8.5)|
24.47(11.1)| 29.98(13.6)| 42.99(19.5)| 42.77(19.4)
CLEARANCES
NOTE: The top clearance recommended for proper return airflow is 5.9in (15cm). Reduction of this clearance may decrease unit performance. This may be reduced to 2.0in (50mm) as long as the right and left clearances are achieved.
SPECIFICATIONS (HEAT PUMP)
System| Size| | 09| 12| 09| 12| 18|
24| 30| 36
---|---|---|---|---|---|---|---|---|---|---
Indoor Model| | 40MHHAQ
09XA1
| 40MHHAQ
12XA1
| 40MHHAQ09 XA3| 40MHHAQ12 XA3| 40MHHAQ18 XA3| 40MHHAQ24 XA3| 40MHHAQ30 XA3|
40MHHAQ36 XA3
Electrica| Voltage, Phase, Cycle| V/Ph/Hz| 115-1-60| 208/230-1-60|
208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60|
208/230-1-60
Power Supply| | Indoor unit powered from outdoor unit
Controls| Wireless Remote Controller
(°F/°C
Convertible)
| | Standard| Standard| Standard| Standard| Standard| Standard| Standard|
Standard
Wired Remote Controller (°F/°C
Convertible)
| | Optional| Optional| Optional| Optional| Optional| Optional| Optional|
Optional
24V Interface for 3rd Part Thermostat
Control
| | | | Optional| Optional| Optional| Optional| Optional| Optional
Wi-Fi Control for Phone App
Control
| | Optional| Optional| Optional| Optional| Optional| Optional| Optional|
Optional
Operating Range| Cooling Indoor DB Min -Max| °F(°C)| 63~90 (17~32)|
63~90 (17~32)| 63~90 (17~32)| 63~90 (17~32)| 63~90 (17~32)| 63~90 (17~32)|
63~90 (17~32)v| 63~90 (17~32)
Heating Indoor DB Min -Max| °F(°C)| 32~86 (0~30)| 32~86 (0~30)| 32~86 (0~30)|
32~86 (0~30)| 32~86 (0~30)| 32~86 (0~30)| 32~86 (0~30)| 32~86 (0~30)
Piping| Pipe Connection Size – Liquid| in (mm)| 1/4 (6.35)| 1/4 (6.35)|
1/4 (6.35)| 1/4 (6.35)| 1/4 (6.35)| 3/8 (9.52)| 3/8 (9.52)| 3/8 (9.52)
Pipe Connection Size – Suction| in (mm)| 3/8 (9.52)| 1/2 (12.7)| 3/8 (9.52)|
1/2 (12.7)| 1/2 (12.7)| 5/8 (16)| 5/8 (16)| 5/8 (16)
Indoor Coil| Face Area| Sq. Ft.| 1.66| 2.05| 1.66| 2.05| 2.67| 2.67|
3.90| 3.90
No. Rows| | 2| 2| 2| 2| 2| 2| 3| 3
Fins per inch| | 20| 20| 20| 20| 21| 20| 20| 20
Circuits| | 2| 2| 2| 2| 4| 4| 7| 7
Indoor| Unit Width| in (mm)| 28.7 (729)| 31.57 (802)| 28.7 (729)| 31.57
(802)| 38.23 (971)| 42.60 (1082)| 49.57 (1259)| 49.57 (1259)
Unit Height| in (mm)| 11.5 (292)| 11.61 (295)| 11.5 (292)| 11.61 (295)| 12.64
(321)| 13.27 (337)| 14.25 (362)| 14.25 (362)
Unit Depth| in (mm)| 7.87 (200)| 7.87 (200)| 7.87 (200)| 7.87 (200)| 8.98
(228)| 9.21 (234)| 11.14 (283)| 11.14 (283)
Net Weight| lbs (kg)| 17.64 (8.0)| 18.52 (8.4)| 17.64 (8.0)| 18.74 (8.5)|
24.47 (11.1)| 29.98 (13.6)| 42.99 (19.5)| 42.77 (19.4)
Fan Speeds| | 4| 4| 4| 4| 4| 4| 4| 4
Airflow (lowest to
highest)
| CFM| 137/170/239/
312
| 176/241/300/
341
| 141/176/246/
312
| 156/197/291/
347
| 271/329/459/
550
| 330/402/546/
728
| 380/536/702/
741
| 330/447/753/
795
Sound Pressure (lowest to
highest)
| dB(A)| 28/32/36/43| 30/36/40/44| 27/31/36/43| 30/35/40/45| 31/38/44/49|
32/38/44/51| 34/40/44/50| 36/38/43/51
Air throw Data| ft (m)| 22.6(6.9)| 24.3(7.4)| 22.6(6.9)| 24.3(7.4)| 26.2(8)|
27.2(8.3)| 29.8(9.1)| 31.2(9.5)
Moisture removal| Pint/h (L/h)| 1.5
(0.69)
| 2.9
(1.39)
| 1.5
(0.69)
| 3.0
(1.47)
| 3.6
(1.72)
| 5.3
(2.54)
| 7.9
(3.73)
| 10.6
(5.03)
Field Drain Pipe Size O.D.| in (mm)| 5/8 (16)| 5/8 (16)| 5/8 (16)| 5/8 (16)| 5/8 (16)| 5/8 (16)| 5/8 (16)| 5/8 (16)
COMPATIBILITY
Indoor Unit| 40MHH- AQ09XA1| 40MHH- AQ12XA1| 40MHH-
AQ09XA3| 40MHH- AQ12XA3| 40MHH- AQ18XA3| 40MHH- AQ24XA3|
40MHH- AQ30XA3| 40MHH- AQ36XA3
---|---|---|---|---|---|---|---|---
Outdoor Unit Single Zone| 38MHRC- Q09AA1| 38MHRC- Q12AA1|
38MHRC- Q09AA3| 38MHRC- Q12AA3| 38MHRC- Q18AA3| 38MHRC-
Q24AA3| 38MHRC- Q30AA3| 38MHRC- Q36AA3
Outdoor Unit Multi- zone| | | 38MGRBQ18BA3| | | |
| | 38MGHBQ24CA3| | |
| | 38MGHBQ30DA3 / 38MGRBQ36DA3| |
| | 38MGHBQ36DA3 / 38MGRBQ48EA3 / 38MGHBQ48EA3
SPECIFICATIONS (COOLING ONLY)
System | Size | – | 9 | 12 | 12 | 18 | 24 |
---|---|---|---|---|---|---|---|
Indoor Model | – | 40MHHAC09XA3 | 40MHHAC12XA1 | ||||
40MHHAC12XA3 | 40MHHAC18XA3 | 40MHHAC24XA3 | |||||
Electrical | Voltage, Phase, Cycle | V/Ph/ Hz | 208/230-1-60 | 115-1-60 | |||
208/230-1-60 | 208/230-1-60 | 208/230-1-60 | |||||
Power Supply | – | Indoor unit powered from outdoor unit | |||||
Controls | Wireless Remote Controller (°F/°C) | – | Standard | Standard | |||
Standard | Standard | Standard | |||||
Wired Remote Controller (°F/°C) | – | Optional | Optional | Optional | Optional |
Optional
24V Interface for 3rd Party T-stat| –| Optional| N/A| Optional| Optional|
Optional
Wi-Fi Control for Phone App Control| –| Optional| Optional| Optional|
Optional| Optional
Operating Range| Cooling Indoor DB Min -Max| °F(°C)| 63~90 (17~32)|
63~90 (17~32)| 63~90 (17~32)| 63~90 (17~32)| 63~90 (17~32)
Piping| Pipe Connection Size – Liquid| in (mm)| 1/4 (6.35)| 1/4 (6.35)|
1/4 (6.35)| 1/4 (6.35)| 3/8 (9.52)
Pipe Connection Size – Suction| in (mm)| 3/8 (9.52)| 1/2 (12.7)| 1/2 (12.7)|
1/2 (12.7)| 5/8 (15.9)
Indoor Coil| Face Area| Sq. Ft.| 1.66| 2.05| 2.05| 2.71| 2.67
No. Rows| –| 2| 2| 2| 2| 2
Fins per inch| –| 20| 20| 20| 21| 20
Circuits| –| 2| 2| 2| 4| 4
Indoor| Unit Width| in (mm)| 28.7 (729)| 31.57 (802)| 31.57 (802)| 38.23
(971)| 42.60 (1082)
Unit Height| in (mm)| 11.5 (292)| 11.61 (295)| 11.61 (295)| 12.64 (321)| 13.27
(337)
Unit Depth| in (mm)| 7.87 (200)| 7.87 (200)| 7.87 (200)| 8.98 (228)| 9.21
(234)
Net Weight| lbs. (kg)| 17.37 (7.88)| 19.18 (8.7)| 18.96 (8.6)| 24.69 (11.2)|
29.98 (13.6)
Number of Fan Speeds| –| 4| 4| 4| 4| 4
Airflow (lowest to highest)| CFM| 147/206/246/312| 212/253/333/347|
194/232/324/347| 306/353/471/500| 400/471/588/706
Sound Pressure (lowest to highest)| dB(A)| 31/32/36| 32/36/41| 31/36/41|
31/38/44| 33/41/48
Air throw Data| ft (m)| 22.6 (6.9)| 24.3 (7.4)| 24.3 (7.4)| 26.2 (8)| 27.2
(8.3)
Moisture removal| Pint/h (L/h)| 2.0 (0.97)| 2.58 (1.22)| 2.6 (1.23)| 4.5
(2.14)| 4.9 (2.34)
Field Drain Pipe Size O.D.| in (mm)| 5/8 (16)| 5/8 (16)| 5/8 (16)| 5/8 (16)|
5/8 (16)
APPLICATION DATA
Unit Selection
Select equipment that either matches or supports slightly more than the anticipated peak load. This provides better humidity control, fewer unit cycles, and less part-load operation. For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total anticipated load. Adjust for anticipated room wet bulb temperature to avoid undersizing the equipment.
Unit Mounting (Indoor)
Refer to the unit’s installation instructions for further details.
Unit leveling – For reliable operation, units should be level in all
planes.
Clearance – Provide adequate clearance for airflow. See Fig. 3 — on page
6.
Unit location – Select a location which provides the best air circulation
for the room. These units should be positioned as high as possible on the wall
for the best air circulation. The unit return and discharge should not be
obstructed by furniture, curtains, or anything which may cause unit short
cycling or air recirculation. Place the unit in the middle of the selected
wall (if possible). Use an outside wall, if available, to make piping easier,
and place the unit so it faces the normal location of room occupants.
Unit Mounting (Outdoor)
Refer to the unit’s installation instructions for further details. Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your Carrier representative.
Mounting Template
Refer to the unit’s installation instructions for further details. The fan coil units are furnished with mounting to mark the location of the wiring, and the refrigeration line hole locations.
Support
Adequate support must be provided to support the weight of all the fan coils. Refer to the Physical Data section for fan coil weights, and the base unit dimensional drawings for the mounting bracket locations.
System Operating Conditions
OPERATING RANGE MIN/MAX °F(°C)
|
COOLING
|
HEATING
INDOOR DB
|
63° / 90°(17°/ 32°)
|
32° / 86° (0° / 30°)
INDOOR WB
|
59° / 84° (15° / 29°)
|
NOTE: Reference the product installation instructions for more information.
WIRING All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/ 3
stranded wire with ground with a 600 volt insulation rating, power/
communication wiring from the outdoor unit to indoor unit consists of four (4)
wires and provides the power for the indoor unit.
Two wires are line voltage AC power, one is communication wiring (S) and the
other is a ground wire. Wiring between indoor and outdoor unit is polarity
sensitive. The use of BX wire is NOT recommended.
If installed in a high Electromagnetic field (EMF) area and communication
issues exists, a 14/2 stranded shielded wire can be used to replace L2/N and
(S) between outdoor unit and indoor unit landing the shield onto ground in the
outdoor unit only.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Be sure to comply with local codes while running wire from the indoor unit to
the outdoor unit.
Every wire must be connected firmly. Loose wiring may cause the terminal to
overheat or result in unit malfunction. A fire hazard may also exist. Ensure
all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or any moving parts.
Disconnecting means must be provided and shall be located within sight and
readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the hole in the conduit
panel.
Drain Connections
Install drains to meet the local sanitation codes. If adequate gravity drainage cannot be provided, the unit should be equipped with an accessory condensate pump.
NOTE: High wall fan coil units have internal condensate traps. A trap is not required.
Drain connections can be routed through alternate locations on most fan coils (see Fig. 4).
Control System
The indoor unit is equipped with a microprocessor control to perform two functions:
- Provide safety for the system
- Control the system and provide optimum levels of comfort and efficiency.
The main microprocessor is located on the control board of the fan coil unit (outdoor units also have a microprocessor) with thermistors located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation to maintain the unit within acceptable parameters and controls the operating mode.
Wireless Remote Controller
- A wireless remote control is supplied for system operation of all high wall units.
- Each battery operated wireless (infrared)
WIRED REMOTE CONTROLLER KSACN0901AAA (OPTIONAL
-
Optional wired remote controller used for system operation of all high wall units.
-
Kit includes a wired remote controller and a connecting cable. NOTE: Extension wire available through RCD.
-
Connect with wire terminal between the remote controller and the
indoor unit. -
Display in °F or °C and temperature increments every 1°F or every 1°C.
24V INTERFACE (OPTIONAL)
P/N KSAIC0301230 for 208-230V models
Allows the Ductless System to be controlled using a Third Party Thermostat.
Wi-Fi Kit for Smart Phone Control (Optional)
P/N KSAIF0601AAA
Allows the Ductless System to be controlled using a connected smart phone
application
AIR FLOW DATA
40MHHA SYSTEM SIZE| | 9K| 12K| 9K| 12K| 18K|
24K| 30K| 36K
---|---|---|---|---|---|---|---|---|---
| (115 V)| (208/230 V)
**INDOOR (CFM)**| Turbo| 312| 341| 312| 347| 550| 728| 741| 795
High| 239| 300| 246| 291| 459| 546| 702| 753
Medium| 170| 241| 176| 197| 329| 402| 536| 447
Low| 137| 176| 141| 156| 271| 330| 380| 330
AIR THROW DATA
HIGH WALL UNIT CAPACITY | Max. Approximate Air Throw ft. (m) |
---|---|
9K (115V) | 22.6(6.9) |
12K (115V) | 24.3(7.4) |
9K (230V) | 22.6(6.9) |
12K(230V) | 24.3(7.4) |
18K (230V) | 26.2(8) |
24K (230V) | 27.2(8.3) |
30K (230V) | 29.8(9.1) |
36K (230V) | 31.2(9.5) |
AIR MOISTURE
SIZE| 9| 12| 9| 12| 18| 24| 30|
36
---|---|---|---|---|---|---|---|---
Voltage, Phase, Cycle| V/Ph/Hz| 115-1-60| 208/230-1-60
Dehumidifying Volume| L/h| 0.69| 1.39| 0.69| 1.47| 1.72| 2.54| 3.73| 5.03
SOUND PRESSURE
SIZE| 9K (115V)| 12K (115V)| 9K (208/230V)| 12K
(208/230V)| 18K (208/230V)| 24K (208/230V)| 30K (208/230V)|
36K (208/230V)
---|---|---|---|---|---|---|---|---
Cooling Operation Indoor| dB(A) at (Turbo / High / Med /Low CFM)| 43/36/32/28|
44/40/36/30| 43/36/31/27| 45/40/35/30| 49/44/38/31| 51/44/38/32| 50/44/40/34|
51/43/38/36
Heating oper- ation Indoor Sound Pressure| dB(A) at (Turbo / High / Med /Low CFM)| 42.4/36.3/
31.6/25.9
| 44.0/38.2/
32.2/26.7
| 43.1/36.9/
31.8/26.1
| 44.9/41.6/
35.3/29.3
| 49.7/43.5/
37.1/30.3
| 51.2/44.7/
40.5/35.9
| 49.7/43.4/
39.3
| ****
53.7/46.1/
41.3
FAN AND MOTOR SPECIFICATIONS
High Wall Unit Size| 9K (115 V)| 12K( (115 V)| 9K (208/230 V)| 12K (208/230
V)| 18K (208/230 V)| 24K (208/230 V)| 30K (208/230 V)| 36K (208/230 V)
---|---|---|---|---|---|---|---|---
High Wall Fan| Material| | Acrylontrile Styrene +30%GF
High Wall Fan Motor| Model| | ZKFP-20-8-113| ZKFP-20-8-113| ZKFP-13-8-4|
ZKFP-13-8-4| ZKFP-30-8-3-10| ZKFP-58-8-1-5| ZKFP-58-8-1-5| ZKFP-58-8-1-5
Volts| V| 140| 140| 310| 310| 310| 310| 310| 310
Phase| | 3| 3| 3| 3| 3| 3| 3| 3
FLA| | 0.15| 0.41| 0.4| 0.63| 0.4| 0.45| 0.5| 0.5
Type| | DC| DC| DC| DC| DC| DC| DC| DC
Insulation class| | E| E| E| E| E| E| E| E
Safe class| | IP20| IP20| IPX0| IPX0| IPX4| IP20| IP20| IP20
Input| W| 35.8| 35.8| 19.4| 19.4| 36| 64.1| 64.1| 64.1
Output| W| 20| 20| 13| 13| 30| 58| 58| 58
Rated current| Amps| 0.257| 0.257| 0.58| 0.58| 0.11| 0.26| 0.26| 0.26
Rated HP| HP| 0.027| 0.027| 0.017| 0.017| 0.04| 0.077| 0.077| 0.077
Speed| rev/min| 1050/810/690| 850/750/450| 1050/810/690| 1250/1070/800|
1200/1000/700| 1200/1080/600| 1200/1050/950| 1200/960/600
Rated RPM| rev/min| 1050| 850| 1050| 1250| 1200| 1200| 1200| 1200
Max. input| W| 68| 68| 104.6| 104.6| 70| 125| 125| 125
NOTE: Refer to the outdoor unit installation instructions (indoor unit powered by the outdoor unit).
WIRING DIAGRAM
Part 1 – GENERAL
1.01 System Description
Indoor, wall−mounted, direct−expansion fan coils are matched with the heat
pump outdoor unit.
1.02 Agency Listings
Unit are rated per AHRI Standards 210/240 and listed in the AHRI directory as
a matched system.
1.03 Delivery, Storage, And Handling
Units are stored and handled per the unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
Part 2 – PRODUCTS
2.01 Equipment
A. General: Indoor, direct-expansion, wall-mounted fan coil Unit is complete with a cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit is furnished with an integral wall mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles are attractively styled, high-impact
polystyrene. Cabinet is fully insulated for improved thermal and acoustic
performance.
C. Fans:
-
. Fans:
1. Fan is the tangential direct-drive blower type with air intake at the top of the unit and discharge at the bottom front. An automatic, motor-driven vertical and horizontal air sweep is provided as standard equipment. -
The air sweep operation is user selectable. The vertical and horizontal sweep may be adjusted (using the remote control)
D. Coil:
The coil is a copper tube with aluminum fins and galvanized steel tube sheets.
The fins are bonded to the tubes by mechanical expansion and anti-corrosive
fin coating. A drip pan under the coil has a drain connection for the hose
attachment to remove condensate. The condensate pan has an internal trap.
E. Motors:
Motors are open drip−proof, with a permanently lubricated ball bearing. The
fan motor is 3−speed.
F. Controls:
Controls consist of a microprocessor-based control system which controls space
temperature, determines optimum fan speed, and runs self diagnostics. The
temperature control range is 62°F to 86°F (17°C to 30°C) in increments of 1°F
or 1°C, and has a 46°F Heating Mode (Heating Setback). The wireless remote
controller has the ability to act as the temperature sensing location for room
comfort.
GUIDE SPECIFICATIONS
INDOOR WALL-MOUNTED DUCTLESS UNITS
Size Range: 1/2 to 3 Ton Nominal Cooling and Heating Capacity Model Number: 40MHHA
The unit has the following functions as a minimum:
- An automatic restart after a power failure at the same operating conditions as at the failure.
- A timer function to provide a minimum 24−hour timer cycle for system Auto Start/Stop.
- Temperature−sensing controls sense return air temperature.
- Indoor coil freeze protection.
- Wireless infrared remote control to enter set points and operating conditions.
- Automatic air sweep control to provide on or off activation of air sweep louvers.
- Fan−only operation to provide room air circulation when no cooling is required.
- Diagnostics provide continuous checks of unit operation and warn of possible malfunctions. Error messages appear on the unit.
- Fan speed control is user−selectable: turbo, high, medium, low, or microprocessor controlled automatic operation during all operating modes.
- Automatic heating−to−cooling changeover in the heat pump mode. Control includes deadband to prevent rapid mode cycling between heating and cooling.
- Indoor coil high temperature protection detects excessive indoor discharge temperature when the unit is in the heat pump mode.
G. Filters:
Unit has a filter track located at the top of the unit with factory supplied
cleanable filters for easy cleaning.
H. Electrical Requirements:
Indoor fan motor to operate on 115V on model sizes 9-12 and on 208-230V on
model sizes 9-36, as specified. Power is supplied by the outdoor unit.
I. Operating Characteristics:
The 40MHHA system has a minimum SEER (Seasonal Energy Efficiency Ratio) and
HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units have refrigerant lines that can be oriented to connect from the
left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
Condensate Pump:
The condensate pump removes condensate from the drain pan when gravity
drainage cannot be used. The pump is designed for quiet operation. The pump
consists of two parts: an internal reservoir/sensor assembly, and a remote
sound-shielded pump assembly. A liquid level sensor in the reservoir stops the
cooling operation if the liquid level in the reservoir is unacceptable.
Wi-Fi Compatible
BACNet Compatible
Documents / Resources
|
Carrier 40MHHA High Wall Ductless
System
[pdf] Instruction Manual
40MHHA High Wall Ductless System, 40MHHA, High Wall Ductless System, Wall
Ductless System, Ductless System
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>