PANDUIT CCPLTR3745-X Plastic Trefoil Cable Cleat Instruction Manual

June 13, 2024
PANDUIT

PANDUIT CCPLTR3745-X Plastic Trefoil Cable Cleat

Safety Precautions

| TO REDUCE THE RISK OF INJURY, USER MUST READ INSTALLATION INSTRUCTIONS BEFORE ATTEMPTING TO INSTALL
---|---
| NOTE: In the interest of higher quality and value, Panduit products are continually being improved and updated. Consequently, pictures may vary from the enclosed product.

NOTE: Updates to this Installation Instructions may be available. Check _ _www.panduit.com__ for the latest version of this manual.

---|---

Preparing for Order

Step Picture Description
1 **** Contact Panduit Sales for assistance with Cleat and hardware

selection.
2|


| Measure actual diameter of the cables. Select a cleat part number based on the actual diameter of the cables.
3|


| Measure height of the ladder rung. If using center securing bolt (Method 1), procure M10 or 3/8” hex bolts, washers, and nylon locknuts with sufficient length to pass through the ladder rung. Procure fastening M10 or 3/8” hex bolts based on the chart below. If using side bolts for both securing and fastening (Method 2), procure M10 or 3/8” hex bolts with sufficient length to pass through the ladder rung and the cleat with cables installed. Dock washers can be used to span the opening at the bottom of the rung if there is insufficient clearance between the flanges.

Center Bolt

Cleat Part Number Minimum Bolt Length
CCPLTR2228-X 90mm (3 1/2”)
CCPLTR2633-X 90mm (3 1/2”)
CCPLTR3139-X 100mm (4”)
CCPLTR3745-X 100mm (4”)
CCPLTR4352-X 120mm (4 3/4”)
CCPLTR5060-X 120mm (4 3/4”)
Step Picture

Description

---|---|---
1|


| Assemble M10 or 3/8” fastening bolts through the cleat base. Fully threaded bolts are shown but not required.
2| ****| Position cleat over the appropriate hole in the rung.
3|


| Assemble M10 or 3/8” securing bolt through the hole in the bottom of the cleat. Tighten to 90 in-lbs [10.2Nm]. Skip to “Securing the Cable” section.

Side Bolts

Step

| Picture|

Description

---|---|---
1|


| Position cleat over the appropriate hole in the rung. Assemble M10 or 3/8” securing bolt through the holes in the bottom of the cleat. Fully threaded bolts are shown but not required. Continue to “Securing the Cables” section.
1A|


| OPTIONAL. Thread a
regular hex nut onto each
bolt until it bottoms out on
the bottom plastic shell.
This will hold the bolts in
place. Nuts do not need
to be removed before
assembly. Requires fully
threaded bolt. Continue
to “Securing the Cables”
section.

Securing the Cables

Step

| Picture|

Description

---|---|---
1|


| Place cables in the opening between the fastening bolts, careful not to damage the cables on the bolts. Center securing bolt is not used if using Method 2.
2|


| Assemble top of cleat on fastening bolts.
3|


| Assemble washer and nylon locknut on fastening bolts. Tighten to 90 in-lbs [10.2Nm]. Ensure top remains level during tightening process.
END| ****| Completed product.

Customers Support

Email:
techsupport@panduit.com
EU Website:
www.panduit.com/emea
EU Email:
emeatoolservicecenter@panduit.com

Panduit Corp.
USA Technical Support
Tel: 800-777-3300
Panduit Europe • EMEA Service Center
Tel: +31 546 580 452 • Fax: +31 546 580 441

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals