PANDUIT CCALTR5056-X Aluminum Trefoil Cable Cleat Installation Guide
- June 13, 2024
- PANDUIT
Table of Contents
PANDUIT CCALTR5056-X Aluminum Trefoil Cable Cleat
Product Information
The Aluminum Trefoil Cable Cleat is designed for the protection and support of cables in a trefoil arrangement. It is part of the CCALTR Family of Cable Cleats manufactured by Panduit Corp. USA.
Product Specifications
- Model: CCALTR Family of Cable Cleats
- Material: Aluminum
- Rung Height:
- 12mm (.47) or less
- 12mm (.47) to 17mm (.67)
- 17mm (.67) to 22mm (.87)
- 22mm (.87) to 27mm (1.06)
Contact Information
- Email: techsupport@panduit.com.
- EU Website: www.panduit.com/emea.
- EU Email: emeatoolservicecenter@panduit.com.
- Tel: 800-777-3300 (Panduit Corp. USA Technical Support)
Product Usage Instructions
Preparing for Order
- Contact Panduit Sales for assistance with Cleat and hardware selection.
- Measure the actual diameter of the cables. Select a cleat part number based on the actual diameter of the cables.
- Measure the height of the ladder rung. If using a bracket, refer to the chart below. If using a bolt, procure M8 or 5/16 hex bolts, washers, and nylon locknuts with sufficient length to pass through the ladder rung.
Rung Height | Bracket Family Number |
---|---|
12mm (.47) or less | CBH15L50 |
12mm (.47) to 17mm (.67) | CBH20L50 |
17mm (.67) to 22mm (.87) | CBH25L50 |
22mm (.87) to 27mm (1.06) | CBH30L50 |
Mounting Method 1: Bracket
- Insert the bracket into the slot in the bottom portion of the cleat.
- Slide the cleat over the rung until centered, with the bracket encompassing the rung.
- Rotate the M6 swing bolt until the carriage head rests within the matching opening in the top of the bracket. Tighten to 70 in-lbs [7.9Nm].
Mounting Method 2: Bolt
- Measure the height of the ladder rung. Procure M8 bolts with an appropriate length to pass through both the cleat and ladder rack. Stainless or Zn-Al coated steel fasteners are recommended.
- Position the cleat over the appropriate hole in the rung.
- Assemble the securing bolt through the hole in the bottom of the cleat. Tighten to 60 in-lbs [6.8Nm].
Securing the Cables
- Ensure that the sides are open and place the cables in the opening in a trefoil configuration.
- Close the sides around the cables. The center bolt installation is shown. Securing cable procedures are the same regardless of cleat mounting method.
- Assemble the included clamping bolt through the flange. Tighten to 60 in-lbs [6.8Nm].
INSTALLATION INSTRUCTIONS
Preparing for Order
Rung Height | Bracket Family Number |
---|---|
12mm (.47”) or less | CBH15L50 |
12mm (.47”) to 17mm (.67”) | CBH20L50 |
17mm (.67”) to 22mm (.87”) | CBH25L50 |
22mm (.87”) to 27mm (1.06”) | CBH30L50 |
Mounting Method 1: Bracket
Mounting Method 2: Bolt
Securing the Cables
CONTACT
- Email: techsupport@panduit.com.
- EU Website: www.panduit.com/emea.
- EU Email: emeatoolservicecenter@panduit.com.
- Panduit Corp.
- USA Technical Support
- Tel: 800-777-3300Panduit Europe
- EMEA Service Center
- Tel: +31 546 580 452
- Fax: +31 546 580 441
- www.panduit.com.
TO REDUCE THE RISK OF INJURY, USER MUST READ INSTALLATION INSTRUCTIONS BEFORE ATTEMPTING TO INSTALL
- NOTE: In the interest of higher quality and value, Panduit products are continually being improved and updated. Consequently, pictures may vary from the enclosed product.
- NOTE: Updates to this Installation Instructions may be available. Check www.panduit.com. for the latest version of this manual.
© Panduit Corp. 2022 RW319 Rev. AB [12-2022]
References
Read User Manual Online (PDF format)
Loading......