inELS RFATV-2 Wireless Thermo-Valve Instruction Manual

June 4, 2024
inELS

02-4/2022 Rev.0 Wireless thermo-valve

Characteristics

  • The wireless Thermo valve measures room temperature and humidity by the internal sensor; based on a set program in the system unit, it opens/closes the radiator valve.
  • it can be combined with these three system units: eLAN-RF 103 or RF Touch 2.
  • It measures temperature in a range of 0…+50 °C and sends it to the system unit in regular 2-min. intervals.
  • Monitoring function Open window, whereupon a sudden change in temperature, it shuts the valve for a preset period.
  • Setting the hysteresis and off set is performed in the system unit or application.
  • The low battery indicator on the display of the system unit or in the application.
  • Battery power (1.5 V / 2x AA – included in supply) with a battery life of about 1 year based on the frequency of use.
  • Range up to 100 m (in open space), if the signal is insuffi cient between the controller and unit, use the signal repeater RFRP-20N or protocol component RFIO 2 that supports this feature.
  • Communication frequency with bidirectional protocol iNELS RF Control.
  • Package includes: 2x battery AA

Description

inELS RFATV 2 Wireless Thermo Valve

Assembly

  1. Assembly:
    – if necessary, mount on a suitable adapter to the existing heating valve.
    – mount the coupling ring to the valve (adapter).inELS RFATV 2 Wireless
Thermo Valve - adapter

  2. Power:
    – open the battery cover.
    – insert the batteries (included in the packaging, observe the polarity).
    – close the battery cover.inELS RFATV 2 Wireless Thermo Valve -
battery

  3. Calibration takes approx. 4 s, as soon as the diode starts fl ashing, the device is ready for pairing.
    Use the address to pair with RF Touch, eLAN-RF or RFTC-100 / G (see RF Touch, eLAN-RF or RFTC-100 / G manual). The RFATV-2 address is located on the bottom of the thermocouple.inELS RFATV 2 Wireless Thermo Valve -
pairing.

  4. Pairing:
    1. Press the control button for 10 seconds, which is located on the front of the product
    2. The calibration takes place for approx. 4 s, as soon as the diode starts fl ashing, the device is ready for pairing
    3. Pair with eLAN-RF 103 or RF-Touch-2 using the address or QR code. The address is indicated on the body of the device under the battery cover
    4. If the head does not pair with any device within 1 minute, it will return to the pre-pairing mode

Communication

RF Touch 2, eLAN-RF-103, eLAN-RF-Wi-103
Interval communication with the control unit in saving mode is 12 minutes.
Interval communication with the control unit in normal mode is 6 minutes.

Radio frequence signal penetration through various construction materials

| | | |
---|---|---|---|---
60 – 90 %| 80 – 95 %| 20 – 60 %| 0 – 10 %| 80- 90 %
brick walls| wooden structures with plasterboards| reinforced concrete| metal partitions| common glass

Replacing batteries

  1. open the battery cover
  2. remove the batteries
  3.  insert new batteries (observe the polarity)
  4. close the battery cover
  5. perform calibration by pressing the central button for 5 s
  6. the head returns to operation

Notice:
Only use 1.5V AA batteries correctly inserted in the device!
Do not use rechargeable batteries!
Immediately replace weak batteries with new ones.
Do not use new and used batteries together.
If necessary, clean the battery and contacts prior to using.
Avoid the shorting of batteries! Do not dismantle batteries, do not charge them and protect them from extreme heating – the danger of leakage! Upon contact with acid, immediately rinse the affected area with a stream of water and seek medical attention.
Keep batteries out of the reach of children.
Batteries must be recycled or returned to an appropriate location (e.g. collection container) in accordance with local legal provisions.

Technical parameters

Supply voltage: 2x 1.5 V battery / batterie AA
Battery life: 1 year/rok

Control

Communication protocol: RFIO 2
Frequency: 866–922 MHz
RF command via controller: eLAN-RF-103, RF Touch-2
Range: up to / až 100 m

Other data

Operating temperature: 0 až +50 °C
Working temperature: any /
Protection: IP40
Dimensions: 52 x 52 x 70 mm
Thermovalve nut: M 30 x 1.5
Related standards: EN 60730

Attention: When you install the iNELS RF Control system, you have to keep a minimal distance 1 cm between each unit.
Between the individual commands must be an interval of at least 1s.

Warning

The instruction manual is designated for mounting and also for user of the device. It is always a part of its packing. Installation and connection can be carried out only by a person with adequate professional qualification upon understanding this instruction manual and functions of the device, and while observing all valid regulations. The trouble-free function of the device also depends on transportation, storing and handling. In case you notice any sign of damage, deformation, malfunction or missing part, do not install this device and return it to its seller. It is necessary to treat this product and its parts as electronic waste after its lifetime is terminated. Before starting the installation, make sure that all wires, connected parts or terminals are de-energized. While mounting and servicing observe safety regulations, norms, directives and professional, and export regulations for working with electrical devices. Do not touch parts of the device that are energized – life threat. Due to the transmissivity of RF signals, observe the correct location of RF components in a building where the installation is taking place. RF Control is designated only for mounting in interiors. Devices are not designated for installation in exteriors and humid spaces. The must not be installed into metal switchboards and into plastic switchboards with metal doors – transmissivity of RF signal is then impossible. RF Control is not recommended for pulleys etc. – the radiofrequency signal can be shielded by an obstruction, interfered with, a battery of the transceiver can get flat etc., and thus disable the remote control.

ELKO EP, s.r.o.
e-mail: [email protected]
Support: +420 778 427 366 |
Technická podpora: +420 775 444 609
www.elkoep.com

Made in Czech Republic

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

inELS User Manuals

Related Manuals